treated as prescribed in packaging, transportation and storage.

In order to prevent the daily treatment of lithium batteries caused casualties and property

losses, the following requirements are made for lithium battery management:

1.Basic requirements for battery warehouse management

The high temperature and wet temperature will accelerate the self-discharge of the

battery due to the characteristic problem of lithium battery. It is recommended that the battery

that does not open the package should be stored in a clean, dry and ventilated warehouse

with ambient temperature of -5

~35

and relative humidity of not more than 90%. The

warehouse should not contain corrosive gas.

Humidity requirements: effectively control warehouse humidity, avoid warehouse in

extreme humidity for a long time (relative humidity above 90%).

The lithium battery warehouse shall be separated by brick wall entities, and the

warehouse must be closed, explosion-proof or other corresponding safety electrical lighting

equipment.

Storage of batteries should be equipped with a sufficient number of fire fighting

equipment (carbon dioxide, dry powder fire extinguishers, fire hoses, fire sandboxes) and

ensure that in good condition. It is recommended to install automatic rain sprinkler system

under conditions. It can not be placed in the same warehouse with flammable materials (e.g.

packing materials cartons, cartons, etc.), it is recommended to use a separate warehouse.

Where there are lithium batteries, there must be no smoking and other prohibited

regulations.

Battery pack should be away from the source of fire and heat, not in the storage room,

near the site may cause fire operations.

2.Good battery storage requirements

Batteries should be stored in well-ventilated, dry and cool places where high

temperatures and humidity may impair battery performance or corrode battery surfaces.

Battery cartons should not be stacked above the arrival height of incoming materials,

otherwise the batteries in the underlying cartons may be deformed and may leak.

Batteries should be avoided from storage or display in direct sunlight or rain. When the

battery is drenched, the insulation resistance will decrease, and self-discharge and rust may
occur. The rising temperature may damage the battery.

Store and display batteries in original packaging to avoid stacking batteries after

removing packaging, which can easily cause battery short circuit and damage.

For contact with each other easy to cause combustion, explosion and fire extinguishing

methods of different items, should be isolated storage. After production, when the excess
battery is returned, it is necessary to restore the original packing state (insulation) and store it.

Содержание 640V2520AH

Страница 1: ...USER MANUAL 640V2520AH HIGH VOLTAGE LITHIUM IRON PHOSPHATE BATTERY Version 1 0 NEW ENERGY TECHNOLOGY LIFE CHANGING...

Страница 2: ...rface 10 2 5 Single cluster control interface 11 III Instructions for lithium battery charge 12 3 1 Electrical performance index 13 3 2 Instructions for use 13 IV Product profile 22 V Systemic stateme...

Страница 3: ...ing mark 5 Several Piece 6 Ground wire Yellow green Several Piece 7 Grounding screws Stainless Steel Combination M 5 12 Several Piece 8 Front shade panel 48 Piece 9 Front panel support 96 Piece 10 Fro...

Страница 4: ...pecified position and fix it pay attention to the direction of the battery rack and put the battery module on the shelf according to the battery layout diagram as shown below Partial drawing module wi...

Страница 5: ...3 384V500AH 640V2520AH Battery module layout and signal cable connection diagram Overall...

Страница 6: ...dule needs to charge and discharge separately so that the voltage difference is within 0 5 V When the battery module is connected in series use the battery connection we provide to ensure that the ter...

Страница 7: ...e positive voltage Close the battery breaker BAT SW of the fifth cluster power on the system with weak current and the display screen on the system cabinet starts to work press the ON OFF button switc...

Страница 8: ...1 pcs 8 Banding Black 1 Bag The system self check is correct the high voltage power on the system is running normally the running indicator RUN on the system cabinet is always on the battery informati...

Страница 9: ...play control screen function which can be used to solve the display control screen display data stuck screen 2 Chinese and English bilingual switching function 3 Cut into the main interface function 4...

Страница 10: ...icate in turn the actual number of high voltage access clusters the actual number of clusters with normal communication and the total number of clusters with full configuration 3 The last piece of dat...

Страница 11: ...election of cluster serial number to be queried Select to query the individual information of the cluster and enter the number selection by clicking the pop up keyboard 3 Switching interface function...

Страница 12: ...e information interface 2 3 2 Data display The position of each display data in the unit information interface is as shown below Detailed description of each display data 1 Display the general informa...

Страница 13: ...icate three level fault The severity of the fault level is 3 2 1 2 5 Single cluster control interface Click the strong control button on the main interface and enter the corresponding password in the...

Страница 14: ...be controlled click the strong control switch button to turn it on and if it succeeds the corresponding cluster indicator in the lower display box will light up green click the dry contact of charge...

Страница 15: ...SP LI 80V50A Input power three phase 380Vac 45 65HZ Input current 10A Input power 5KVA Output voltage range 30 100V Output current range 5 50A Rated power 4KW Product size 560 430 600 mm Weight 50KG P...

Страница 16: ...fix the switch on the rear panel to complete the wiring A The input terminal yellow green and red is connected to three phase power B The output terminal red and black is connected to the lithium bat...

Страница 17: ...00AH 640V2520AH As shown in the figure 3 2 2 Display description A After booting the panel will display the following The main interface will display the basic information of the machine and fault inf...

Страница 18: ...16 16 640V2520AH B On the main screen click the upper left corner to enter the maintenance options as Follows Maintenance options include parameter settings...

Страница 19: ...17 384V500AH 640V2520AH Enter the management password 123456 and enter the settings Then enter the password setting you can modify the password to ensure safety...

Страница 20: ...e settings You can set the system minimum voltage maximum current maximum voltage and BMS voltage into the protection settings which can limit the output over voltage output under voltage and output o...

Страница 21: ...19 384V500AH 640V2520AH Time setting you can calibrate the current system time Debug mode The charging voltage and charging current can be set...

Страница 22: ...0 20 640V2520AH Pile information Display the basic information of the machine Alarm query You can directly see the record of the last failure inside select other to see more historical failure records...

Страница 23: ...arging electricty You can set timed charging more humane and finally click back to return to the main interface C Click the battery directly to see the ID information message data and the set voltage...

Страница 24: ...me high voltage energy storage high voltage UPS and data room The product adopts modular design higher integration saving installation space adopts high performance lithium iron phosphate cathode mate...

Страница 25: ...BMU Master slave communication 4 48 series single cell voltage acquisition 4 channels channel temperature acquisition CSU Current sampling support Hall sensor and JDI shunt Wire harness Voltage detec...

Страница 26: ...temperature SOC SOH and other threshold alarm functions as well as limit alarm threshold circuit cut off protection function Support data storage function support local storage of system operating da...

Страница 27: ...25 384V500AH 640V2520AH power down save function 5 4 Product Graphics and Technical Parameters Battery module Battery cluster Stack only for sample showing...

Страница 28: ...387 410 Recommended discharge cutoff voltage VDC 92 183 210 342 366 Standard charging current A 40 80 40 80 40 80 40 80 40 80 Maximum continuous charge current A 100 200 100 200 100 200 100 200 100 2...

Страница 29: ...ng upper computer function window VCC voltage is equal to Key ON or charge detection signal If the difference is too large more than 3V please contact BMS manufacturer for support Charger output volta...

Страница 30: ...lick on monomer information to enter the monomer information interface which is mainly used as the visual display area of cell voltage and temperature information Calibration interface password jdi 12...

Страница 31: ...her metal items Use tools with insulated handles 6 2 Notes A The battery management system cannot be used in series B When using the battery management system the charging and discharging cabinet abov...

Страница 32: ...atic rain sprinkler system under conditions It can not be placed in the same warehouse with flammable materials e g packing materials cartons cartons etc it is recommended to use a separate warehouse...

Страница 33: ...termined that it can not be repaired After the completion of the waste application timely notification of professional qualifications of the disposal unit B for the bad battery in the storage period i...

Страница 34: ...ll be owned by the factory Product warranty services do not include damage due to Damage to equipment during transportation except for transportation by the factory Damage caused by improper installat...

Страница 35: ......

Страница 36: ...High Voltage Lithium Iron Phosphate Battery...

Отзывы: