10
English (US)
7.2.4 Manual % dial (when dip switch D is off)
The manual % dial allows the speed of the pump
to be manually adjusted and set by the user.
The speed of the pump may be manually
adjusted anywhere from "Min" to "100 %", but
once set remains fixed at that speed. The "Min"
position on the dial will either be equal to OFF or
15 % depending on the position of dip switch C.
The factory default is 50 %.
Insert power cord from the pump into a properly
grounded 115 V outlet. This will apply power to
the pump/controller.
7.2.5 Performance indicator LEDs
"Power On" (green) indicates that power is
applied.
"% Out" (yellow) indicates the speed of the
pump by flashing at different speeds.
Fig. 6
Performance indicator LEDs
8. After installation
•
Place this manual, and all other manuals
relating to the installation, in a location near
the controller for future reference.
•
It is important to explain the operation of this
controller to the end user and to anyone else
who may be operating the system.
9. Quick reference
Voltage speed control signal circuit rating:
Terminals: "Com (-)" and "Os/V"
•
0-10 VDC
•
5 mA max.
Current speed control signal circuit rating:
Terminals: "Com(-)" and "Ret/l"
•
0-20 mA DC
•
5 VDC max.
Fig. 7
Dip switches
TM
05
46
37
25
12
Power On
% Out
T
M
05
46
32
25
12
Switch
Dip switch position
ON
OFF
Default
A
mA
(V) DC
mA
B
2-10 V
4-20 mA
0-10 V
0-20 mA
2-10 V
4-20 mA
C
Min. speed
off
Min. speed
15 %
Min. speed
off
D
Speed
control
external
Speed
control
manual %
dial
Speed
control
external