Page 7

Page 7

Setting Dip Switches

Figure 7A -

Dip Switches

Dip  switch  settings

POSITION

Feature  Explanation

Dip switch C

 - minimum speed off/minimum speed

15%.  When dip switch C is in the 

ON

 position the

variable speed of the pump will have a range from
minimum speed = off to maximum speed = 100%.
When dip switch C is in the 

OFF

position the variable

speed of the pump will have a range from minimum
speed = 15% to a maximum speed = 100%.

Dip switch D

 - speed control external/speed control

maximum % dial.  When dip switch D is in the

ON

position an external V(dc)/mA signal will cause the
pump speed to vary and the dial on the terminal box
will function in the -5% to +5% mode.  When dip switch
D is in the 

OFF

position turning the manual % dial will

vary the pump speed.  The pump will not respond to an
external V(dc)/mA signal even if one is present.  The
terminal box and the dial will function in the minimum
to 100% mode.

 7.

Settings

ON

OFF

DEFAULT

SWITCH

m A

(V) DC

m A

0-10V

0-20mA

2-10V

4-20mA

min  speed

15%

min  speed

off

speed control

external

2-10V

4-20mA

min  speed

off

speed control

manual % dial

speed control

external

A

B

C

D

 6.

 

Settings

Setting Dip Switches:

Figure 5 -

Dip Switches

Dip Switch Settings:

Feature Explanation
Dip Switch C

 - minimum speed off/minimum speed

15%. When dip switch C is in the 

ON

 position the

variable speed of the pump will have a range from
minimum speed = off to maximum speed = 100%.
When dip switch C is in the 

OFF

 position the variable

speed of the pump will have a range from minimum
speed = 15% to a maximum speed = 100%.

Dip Switch D

 - speed control external/speed control

maximum % dial.  When dip switch D is in the 

ON

position an external V(dc)/mA signal will cause the
pump speed to vary and the dial on the terminal box
will function in the -5% to +5% mode.  When dip switch
D is in the 

OFF

 position turning the manual % dial will

vary the pump speed.  The pump will not respond to an
external V(dc)/mA signal even if one is present.  The
terminal box and the dial will function in the minimum
to 100% mode.

Page 7

Setting Dip Switches

Figure 7A -

Dip Switches

Dip  switch  settings

POSITION

Feature  Explanation

Dip switch C

 - minimum speed off/minimum speed

15%.  When dip switch C is in the 

ON

 position the

variable speed of the pump will have a range from
minimum speed = off to maximum speed = 100%.
When dip switch C is in the 

OFF

position the variable

speed of the pump will have a range from minimum
speed = 15% to a maximum speed = 100%.

Dip switch D

 - speed control external/speed control

maximum % dial.  When dip switch D is in the

ON

position an external V(dc)/mA signal will cause the
pump speed to vary and the dial on the terminal box
will function in the -5% to +5% mode.  When dip switch
D is in the 

OFF

position turning the manual % dial will

vary the pump speed.  The pump will not respond to an
external V(dc)/mA signal even if one is present.  The
terminal box and the dial will function in the minimum
to 100% mode.

 7.

Settings

ON

OFF

DEFAULT

SWITCH

m A

(V) DC

m A

0-10V

0-20mA

2-10V

4-20mA

min  speed

15%

min  speed

off

speed control

external

2-10V

4-20mA

min  speed

off

speed control

manual % dial

speed control

external

A

B

C

D

Содержание UP15-42F

Страница 1: ...nd Operation 1 2 3 4 5 6 7 Electrical Pump Installation Operational Limits General Features Shipment Inspection Settings Quick Reference GRUNDFOS INSTRUCTIONS Pumps Incorporating the VS Variable Speed...

Страница 2: ...roper installation and operation of this control could result in damage to the equipment and possibly even personal injury It is your responsibility to ensure that this control is safely installed acc...

Страница 3: ...and safety devices must be added Offset dial provides fine tuning for input signal Manual dial provides manual speed control Range of signal is selected through Dip Switch A Type of signal used is se...

Страница 4: ...re intended for use with water or a 50 50 mixture by weight of propylene glycol UP15 42F VS 115V 60 Hz Maximum Fluid Temperature 205 F 96 C Maximum Ambient 107 F 42 C with control module vertical Fig...

Страница 5: ...freely Remove the large screw in the middle of the nameplate insert a small flat blade screwdriver into the end of the shaft and turn gently If the shaft does not turn easily repeat the disas sembly...

Страница 6: ...ge remaining air from the bearing chamber This is especially important when installing the pump during the off season 5 Electrical Warning All electrical work should be performed by a qualified electr...

Страница 7: ...he wires Current Speed Control Signal Connections Connect the current signal wires to terminals Com and Ret I Fig 3 Test the Speed Control Signal Wiring Make sure exposed wires and bare terminals are...

Страница 8: ...f the pump will have a range from minimum speed 15 to a maximum speed 100 Dip Switch D speed control external speed control maximum dial When dip switch D is in the ON position an external V dc mA sig...

Страница 9: ...al allows the speed of the pump to be manually adjusted and set by the user The speed of the pump may be manually adjusted anywhere from min to 100 but once set remains fixed at that speed The min pos...

Страница 10: ...10V 4 20mA min speed off speedcontrol manual dial speedcontrol external A B C D 7 Quick Reference Setting Dip Switches Figure 7A DipSwitches Dip switch settings POSITION Feature Explanation Dip switc...

Страница 11: ...s must be min 300V rating Sup Com Ret I Com Os V Boil Boil Dem Dem tN4 Fuse Transformer 1 VA 115 V 18 V 100 H 6 A inductor Pot 0 1 F 250V R Class 2 only Off On A B C D 1008 02 599395 May 2006 12345 Ma...

Страница 12: ...te and sup porting installation data Unless otherwise provided the distributor or dealer will contact the GRUNDFOS factory or authorized service station for instructions Any defective product to be re...

Отзывы: