Voltage Speed Control Signal Connections:

Connect the voltage signal wires to terminals
“Com(-)” and “Os/V” (Fig 4.).

Electrical Connections To The Control:

CAUTION:

 The installer should confirm 

that no current/voltage is present at any 
of the wires.

Current Speed Control Signal Connections:

Connect the current signal wires to terminals
“Com(-)” and “Ret/I” (Fig 3.).

Test the Speed Control Signal Wiring.

Make sure exposed wires and bare terminals are
not in contact with other wires or grounded
surfaces.  Turn on the control signal and measure
the voltage/mA across the leads using a voltmeter
to confirm the pump signal is present.

Note:

 Control signal wires must be run through and

secured by the stain relief on the terminal board.

Note: 

No speed control signal is necessary if speed

is to be regulated using the manual % dial.

Содержание UP15-42F

Страница 1: ...nd Operation 1 2 3 4 5 6 7 Electrical Pump Installation Operational Limits General Features Shipment Inspection Settings Quick Reference GRUNDFOS INSTRUCTIONS Pumps Incorporating the VS Variable Speed...

Страница 2: ...roper installation and operation of this control could result in damage to the equipment and possibly even personal injury It is your responsibility to ensure that this control is safely installed acc...

Страница 3: ...and safety devices must be added Offset dial provides fine tuning for input signal Manual dial provides manual speed control Range of signal is selected through Dip Switch A Type of signal used is se...

Страница 4: ...re intended for use with water or a 50 50 mixture by weight of propylene glycol UP15 42F VS 115V 60 Hz Maximum Fluid Temperature 205 F 96 C Maximum Ambient 107 F 42 C with control module vertical Fig...

Страница 5: ...freely Remove the large screw in the middle of the nameplate insert a small flat blade screwdriver into the end of the shaft and turn gently If the shaft does not turn easily repeat the disas sembly...

Страница 6: ...ge remaining air from the bearing chamber This is especially important when installing the pump during the off season 5 Electrical Warning All electrical work should be performed by a qualified electr...

Страница 7: ...he wires Current Speed Control Signal Connections Connect the current signal wires to terminals Com and Ret I Fig 3 Test the Speed Control Signal Wiring Make sure exposed wires and bare terminals are...

Страница 8: ...f the pump will have a range from minimum speed 15 to a maximum speed 100 Dip Switch D speed control external speed control maximum dial When dip switch D is in the ON position an external V dc mA sig...

Страница 9: ...al allows the speed of the pump to be manually adjusted and set by the user The speed of the pump may be manually adjusted anywhere from min to 100 but once set remains fixed at that speed The min pos...

Страница 10: ...10V 4 20mA min speed off speedcontrol manual dial speedcontrol external A B C D 7 Quick Reference Setting Dip Switches Figure 7A DipSwitches Dip switch settings POSITION Feature Explanation Dip switc...

Страница 11: ...s must be min 300V rating Sup Com Ret I Com Os V Boil Boil Dem Dem tN4 Fuse Transformer 1 VA 115 V 18 V 100 H 6 A inductor Pot 0 1 F 250V R Class 2 only Off On A B C D 1008 02 599395 May 2006 12345 Ma...

Страница 12: ...te and sup porting installation data Unless otherwise provided the distributor or dealer will contact the GRUNDFOS factory or authorized service station for instructions Any defective product to be re...

Отзывы: