The pump must be installed with the motor shaft
positioned horizontally. Under no circumstances
should the pump be installed with the shaft vertical or
where the shaft falls below the horizontal plane (Fig. 1).
• Ensure that water does not enter the terminal box
during the installation process.
•
DO NOT START THE PUMP UNTIL THE SYSTEM
HAS BEEN FILLED AND CHECKED FOR LEAKS.
• Do not use the pump to vent the system.
• Never operate the pump dry. The bearings require
water lubrication and will be damaged otherwise.
• Fill system with water. This will result in immediate
lubrication of the bearings.
• Operate the pump for 5 minutes, when control
installation is complete, to purge remaining air from
the bearing chamber. This is especially important
when installing the pump during the off-season.
5.
Electrical
Warning:
All electrical work should be
performed by a qualified electrician in
accordance with the latest edition of the
National Electrical Code, local codes and
regulations.
CAUTION:
Power must not be applied to any of the
wires during the rough-in wiring stage.
CAUTION:
All field wiring must pass through a suitable
listed conduit fitting, to ensure proper strain relief.
CAUTION:
All field installed wiring should meet or
exceed requirements for Class 2 wiring per article 725
of the National Electrical Code rated at 30VAC 250VA.
Ensure that enough wiring is in the control box to
reach the terminal strip.
NOTE:
All field wiring shall have insulation stripped
exposing 5-7mm of conductor before placement into
control box terminal strip.