background image

English (GB)

15

6.8 Pipework connection 

If a tool, e.g. a chain pipe wrench, is used when the 
riser pipe is fitted to the pump, the pump must only 
be gripped by the pump discharge chamber.

When connecting plastic pipes, a compression 
coupling should be used between the pump and the 
first pipe section.

Where flanged pipes are used, the flanges should 
be slotted to take the submersible drop cable.

Figure 11 shows a pump installation with indication of:

position of cable clips, pos. 1, and distance 
between the clips.

fitting of straining wire, pos. 2.

maximum installation depth below the static 
water level.

Fig. 11

6.8.1 Cable clips

Cable clips must be fitted every 3 metres. 
See fig. 11.

When connecting plastic pipes, some slackness 
must be left between each cable clip as plastic pipes 
expand when loaded. 

Where flanged pipes are used, the cable clips 
should be fitted above and below each joint. 

6.8.2 Installation depths

Maximum installation depth below the static water 
level: 150 metres. See fig. 11. 

Minimum installation depths below the dynamic 
water level: 

Vertical installation:
During start-up and operation, the pump must 
always be completely submerged in water.

Horizontal installation: 
The pump must be installed and run at least 
0.5 metres below the dynamic water level.
If there is a risk that the pump might be covered 
by mud, the pump must always be fitted in a flow 
sleeve.

6.8.3 When lowering the pump into the borehole

It is recommended to secure the pump by an 
unloaded straining wire. See fig. 11, pos. 2.

Slacken the straining wire so that it becomes 
unloaded and lock it to the borehole seal by means 
of wire locks. 

Note

For pumps fitted with plastic pipes, the 
expansion of the pipes when loaded 
should be taken into consideration, 
when deciding on the installation depth 
of the pump.

TM

01

 04

80

 43

97

3 metres

Max.
150 
metres

1

2

Caution

The straining wire must not be used for 
pulling the pump with riser pipe out of 
the borehole.

Caution

Do not lower or lift the pump by means 
of the motor cable. 

Содержание SQE-NE Series

Страница 1: ...on 12 6 1 General 12 6 2 Assembly of pump part and motor 12 6 3 Removal of non return valve 12 6 4 Fitting the cable plug to the motor 13 6 5 Fitting the cable guard 13 6 6 Cable sizing 14 6 7 Fitting...

Страница 2: ...ator As a minimum the generator output must be equal to the motor P1 kW 10 Starting current The motor starting current is equal to the highest value stated on the motor nameplate Power factor PF 1 Mot...

Страница 3: ...ng a screwdriver or a similar tool 4 Inject motor liquid into the motor with a filling syringe or the like 5 To allow possible air to escape move the motor from side to side 6 Refit the filling plug a...

Страница 4: ...arked with the following symbol Supply voltage 1 x 200 240 V 10 6 50 60 Hz PE The current consumption can only be measured by means of a true RMS instrument If other instruments are used the value mea...

Страница 5: ...be used on the clamping faces of the pump part See fig 6 Fig 6 When pump part and motor have been assembled correctly there must not be a clearance between pump part and motor 6 3 Removal of non retur...

Страница 6: ...earance between the motor and the cable plug 6 5 Fitting the cable guard To fit the cable guard proceed as follows 1 Make sure that the submersible drop cable lies flat in the cable guard 2 Place the...

Страница 7: ...Fitting the submersible drop cable It is recommended to join the submersible drop cable and the motor cable by means of a Grundfos cable termination kit type KM For larger cross sections please contac...

Страница 8: ...lation depths Maximum installation depth below the static water level 150 metres See fig 11 Minimum installation depths below the dynamic water level Vertical installation During start up and operatio...

Страница 9: ...switch and diaphragm tank during starting will be lower than the pump cut in pressure set on the pressure switch pcut in This lower pressure is called minimum pressure pmin pmin is equal to the desir...

Страница 10: ...ce tools are available from Grundfos The Grundfos Service Manual is available on request The pumps can be serviced at a Grundfos service centre 9 1 Contaminated pumps If Grundfos is requested to servi...

Страница 11: ...n the electric installation are blown Replace the blown fuses If the new ones blow too the electric installation and the submersible drop cable should be checked b The ELCB or the voltage operated ELC...

Страница 12: ...e is defective Replace the riser pipe i Undervoltage has occurred Check the power supply 4 Frequent starts and stops a The differential of the pressure switch between the start and stop pressures is t...

Страница 13: ...d neutral Connect the voltmeter to the terminals at the connection The voltage should when the motor is loaded be within the range specified in section 5 Electrical connection Large variations in supp...

Отзывы: