3.5 Electrical connection – three-phase pumps,
0.75-7.5 kW
3.5.1 Mains switch
The pump must be connected to an external all-pole mains switch
with a contact separation of at least 3 mm in each pole according
to IEC 364.
3.5.2 Protection against electric shock – indirect contact
Protective earth conductors must always have a yellow/green
(PE) or yellow/green/blue (PEN) colour marking.
The leakage current of the motor can be found in section
EN 50 178 and BS 7671 specify the following:
Leakage current > 3.5 mA:
The pump must be stationary and installed permanently.
Furthermore, the pump must be connected permanently to the
electricity supply.
• The earth connection must be carried out as duplicate
conductors.
3.5.3 Additional protection
If the pump is connected to an electric installation where an earth
leakage circuit breaker is used as additional protection, this
circuit breaker must be of the type:
• which is suitable for handling leakage currents and cutting-in
with short pulse-shaped leakage.
• which trips out when alternating fault currents and fault
currents with DC content, i.e. pulsating DC and smooth DC
fault currents, occur.
For these pumps an earth leakage circuit breaker
type B
must be
used.
This circuit breaker must be marked with the following symbols:
The leakage current of the motor can be found in section
3.5.4 Motor protection
The pump requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking (IEC 34-11: TP 211).
TM
02
07
95
09
04
Caution
The user or the installer is responsible for the
installation of the correct earthing and protection
according to valid national and local standards.
All operations must be carried out by a qualified
electrician.
Warning!
All electric supply circuits must be interrupted
before working in the pump terminal box.
Never make any connections in the pump
terminal box unless the electricity supply has
been switched off for at least 5 minutes.
0/1
10K
RUN
STOP
NC C NO
N PE L
1 9 8 7
6 5 4 3 2
B Y A
0-10 V
0/4-20 mA
4-20 mA
0/4-20 mA
0-10 V
Gr
ou
p
2
G
rou
p 3
G
rou
p 1
1: Digital input
9: GND (frame)
8: +24 V
7: Sensor input
B: RS-485B
Y: Screen
A: RS-485A
6: GND (frame)
5: +10 V
4: Setpoint input
3: GND (frame)
2: Start/stop
The pump must be earthed and protected against
indirect contact in accordance with national
regulations.
Caution
As the leakage current of 4 kW to 7.5 kW motors
is > 3.5 mA, these motors must be connected to
especially reliable/sturdy earth connections.
Note
When an earth leakage circuit breaker is
selected, the total leakage current of all the
electrical equipment in the installation must be
taken into account.