A fault indication can be reset in one of the following ways:
• By briefly pressing the button
or on the pump. This will
not change the setting of the pump.
A fault indication cannot be reset by means of
or if the
buttons have been locked.
• By switching off the electricity
supply
until the indicator lights
are off.
• By switching the external start/stop input off/on.
• By means of the R100, see section
When the R100 communicates with the pump, the red
indicator light will flash rapidly.
12. Megging
13. Technical data – single-phase pumps
13.1 Supply voltage
1 x 200-240 V ±10 %, 50/60 Hz, PE.
Cable: 0.5 - 1.5 mm² / 14-12 AWG.
See nameplate.
Recommended fuse size
Motor sizes from 0.37 to 1.1 kW: Max. 10 A.
Standard as well as quick-blow or slow-blow fuses may be used.
13.2 Leakage current
Earth leakage current < 3.5 mA.
The leakage currents are measured in accordance with
EN 60 355-1.
13.3 Inputs/output
Start/stop
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Digital
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Setpoint signals
• Potentiometer
0-10 VDC, 10 k
Ω
(via internal voltage supply).
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Maximum cable length: 100 m.
• Voltage signal
0-10 VDC, R
i
>
50 k
Ω.
Tolerance: +0 %/–3 % at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Maximum cable length: 500 m.
• Current signal
DC 0-20 mA/4-20 mA, R
i
= 175
Ω.
Tolerance: +0 %/–3 % at maximum current signal.
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Maximum cable length: 500 m.
Sensor signals
• Voltage signal
0-10 VDC, R
i
>
50 k
Ω
(via internal voltage supply).
Tolerance: +0 %/–3 % at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Maximum cable length: 500 m.
• Current signal
DC 0-20 mA/4-20 mA, R
i
= 175
Ω
.
Tolerance: +0 %/–3 % at maximum current signal.
Screened cable: 0.5 - 1.5 mm² / 28-16 AWG.
Maximum cable length: 500 m.
• Electricity supply to sensor:
+24 VDC, max. 40 mA.
+10 VDC, max. 2.5 mA.
Signal output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A.
Minimum contact load: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm² / 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm² / 28-16 AWG.
Maximum cable length: 500 m.
14. Technical data – three-phase pumps,
0.75-7.5 kW
14.1 Supply voltage
3 x 380-480 V +-10 %, 50/60 Hz, PE.
3 x 208-230 V +-10 %, 50/60 Hz, PE.
Cable: 2.5 - 4 mm² / 10 - 8 AWG
See nameplate
Recommended fuse sizes
USA and Canada see page 24
Motor sizes from 0.75 to 5.5 kW: Max. 16 A.
Motor size 7.5 kW: Max. 32A.
Standard as well as quick-blow or slow-blow fuses may be used.
14.2 Leakage current
The leakage currents are measured in accordance with
EN 60 355-1.
Note
Megging of an installation incorporating E-pumps
is not allowed, as the built-in electronics may be
damaged.
Motor size
[kW]
Leakage current
[mA]
0.75 to 3.0 (supply voltage < 460 V)
0.75 to 3.0 (supply voltage > 460 V)
< 3.5
< 5
4.0 to 5.5
< 5
7.5
< 10