8.4. EZ Boost controller fault finding chart

Fault

Possible Cause

Remedy

1.  No light in the front cover.

a)  The ribbon cable connection is loose or 
 

defective.

•  Is the control indicator LED flashing? 
 

If not, the EZ Boost controller is 

 

defective.

•  Check that the ribbon cable connection 
 

is secure.

2.  The pump does not start. The green 
 

indicator light in the on/off button 

 

is on. No alarm is indicated.

a)  The EZ Boost controller, the pressure 
 

sensor or the pump is defective.

Check : 
•  That the control indicator LED is 
 

flashing. If not, the EZ Boost controller is 

 

defective. 

•  That the system pressure is 7 PSI below 
 

the pressure setting.

 

If so, the pump is supposed to start. 

 

Open a tap to be sure.

 

If the pump starts, the system is 

 

probably OK. The system pressure can 

 

be read on the pressure gauge.

•  Refer to fault 13 to troubleshoot the 
 

pressure sensor. If the pump has not 

 

started yet, proceed as follows:

 

Press the on/off button for 5 seconds.  

 

If the pump starts, the EZ Boost 

 

controller or the sensor may be 

 

defective.

 

Note: 

The pressure is not controlled 

 

and may rise to a high level. 

3. The pressure is not constant.

a)  The pump is not of the correct type 
 

or the pre-charge pressure of the 

 

diaphragm tank is incorrect.

Check
•  That the LED for Max. speed or Min. 
 

speed is on. If so, this indicates that the 

 

pump has reached a limit. See section 

 

3, EZ Boost Quick Select Guide. Replace 

 

the pump, if necessary.

•  The pre-charge pressure of the 
 

diaphragm tank.

 

Note:

 Remember to stop and drain the 

 

system pressure before the pressure is  

 

checked.

•  Make sure the diaphragm tank is the 
 

2 gal. size.

•  Whether the sensor is positioned far 
 

away from the tap. If so, the pressure 

 

variations may be caused by friction  

 

losses, see section 6.4, Positioning the 

 

Pressure Sensor.

b)  No contact between BMQE pump and 
 

EZ Boost controller.

•  Check that the LED for “No contact to 
 

pump” is on. If so, go to fault no. 14.

(continued next page)

15

Содержание EZ Boost

Страница 1: ...GRUNDFOS INSTRUCTIONS EZ BoostTM System USA Installation and operating instructions Please leave these instructions with the pump for future reference...

Страница 2: ...a Operating Conditions 6 Storage 6 Frost Protection 6 6 Installation Electrical Connection 6 Cable Sizing 7 Positioning 7 Controller Connection 7 Pressure Sensor 8 Pressure Tank 8 Pressure Relief Valv...

Страница 3: ...e controller adjusts the pump performance accordingly to maintain constant pressure by changing the pump speed At low flow the pressure will drop slowly When the pres sure in the tank is 7 PSI below t...

Страница 4: ...V or rises above 280 V With a rated voltage of 110 115 V 60 Hz the pump will be cut out if voltage falls below 75 V or rises above 150 V The motor is automatically cut in when the voltage is again wi...

Страница 5: ...am The EZ Boost Constant Pressure System should consist of Pos 1 EZ Boost BMQE pump 2 EZ Boost controller 3 Diaphragm tank recommended size 2 U S gallons 8 liter 130 psi 2 3 4 1 5 6 6 Additional boost...

Страница 6: ...and when installed in the vertical position the air vent must be at the top of the unit Insert BMQE pump into the open mounting bracket Secure mounting brackets Apply pressure to the BMQE pump until t...

Страница 7: ...Consult Troubleshooting Section 11 Verify that EZ Boost controller is operating 11 Verify EZ Boost controller is operating These lights are on These lights are on 12 Optional Lock the buttons 12 Opti...

Страница 8: ...f button on the EZ Boost con troller must not be used as a safety switch when installing and servicing the pump Rain tight or wet location hubs that comply with the requirements in the standard for Fi...

Страница 9: ...System 6 1 2 Cable sizing Single phase 60 HZ maximum cable length motor service to entrance Motor rating Copper wire size AWG Volts HP 14 12 10 Maximum cable length ft m 115 0 50 100 30 5 160 48 8 250...

Страница 10: ...signed to work with a 2 gal diaphragm tank Install a diaphragm tank to insure that the BMQE will shut off at zero flow The diaphragm tank must be installed at some point between the BMQE pump and the...

Страница 11: ...um flow for BMQE pumps in parallel will exceed 35 GPM a 4 gallon or two 2 gallon dia phragm tank s should be used 6 9 Generator Operation Power may be supplied to BMQE pumps by an adequately sized gen...

Страница 12: ...on the EZ Boost controller face the pipe shows run lights when the pump is operat ing When the pump is not operating none of the flow indicator lights are on see fig 7 Fig 7 7 2 3 Pressure setting Th...

Страница 13: ...d pressure drops causing the motor to increase speed If the power consumption falls below the dry run setting for an accumulated time of 5 seconds and the motor speed is within 1000 rpm of the max spe...

Страница 14: ...eed Sensor defective Overload Over temperature Speed reduction Voltage alarm No contact to pump see Fig 14 Flashing green light when the pump control is working correctly Permanent yellow light when t...

Страница 15: ...2 Parts list for SQE with instructions for dismantling and assembly of pump and motor 8 2 EZ Boost Controller Service Before starting any work on the EZ Boost con troller make sure that the electricit...

Страница 16: ...and repair replace the pump e Leakage in the pipe work Check and repair the pipe work f Under voltage has occurred Check the electricity supply 4 Frequent starts and stops a The supply voltage is unst...

Страница 17: ...sure sensor If the pump has not started yet proceed as follows Press the on off button for 5 seconds If the pump starts the EZ Boost controller or the sensor may be defective Note The pressure is not...

Страница 18: ...motor communication part is defective Reduce the length of the pump cable Switch off the main power supply to the EZ Boost controller Switch on the main power supply again The pump is now connected d...

Страница 19: ...ording to the values in Section 5 Note As the voltage is detected at the motor allow for the voltage drop in the pump cable 8 The EZ Boost controller indicates Dry running If the power consumption is...

Страница 20: ...ed Replace pump or motor 13 The EZ Boost controller indicates Sensor defective a The pressure sensor is defective Check that the sensor is wired correctly If the sensor type is 4 20 mA measure the DC...

Страница 21: ...faults Poor connection in leads possibly in the cable joint Too low supply voltage see item 1 9 Factory settings Alarm 200 240 V motors 100 115 V motors SQ SQE SQE NE 03A and 05A models SQ SQE SQE NE...

Страница 22: ...4 54 7 8 0 95 2 2 9 15 0 5 5 55 5 8 1 96 0 2 9 15 7 5 5 56 2 8 1 96 7 3 0 16 5 5 6 57 0 8 2 97 5 3 0 17 2 5 6 57 7 8 2 98 2 3 1 18 0 5 7 58 5 8 3 99 0 3 1 18 7 5 7 59 2 8 3 99 7 3 2 19 5 5 8 60 0 8 4...

Страница 23: ...ce under this warranty the defective product must be returned to the distributor or dealer of GRUNDFOS products from which it was purchased together with proof of purchase and installation date failur...

Страница 24: ...Road Oakville Ontario L6H 6C9 Telephone 905 829 9533 Fax 905 829 9512 Bombas Grundfos de Mexico S A de C V Boulevard TLC 15 Parque Stiva Aeropuerto Apodaca N L 66600 Mexico Telephone 52 81 8144 4000 F...

Отзывы: