5.1.6 Setting the pump bank sensors
5.1.6.1 Setting the pressure sensor for the pump bank
The controller must be unlocked.
This task is about setting the differential pressure sensor installed
over the pump bank.
1.
Go to
Pump bank
>
Pump-bank input-output settings
.
2.
Make sure that the differential pressure sensor is enabled.
3.
Differential pressure sensor range
, enter the maximum
pressure that the sensor can measure.
Related information
9.1 Navigating the display. See page 14.
5.1.6.2 Setting the temperature sensor for the pump bank
The controller must be unlocked.
This task is about setting the temperature sensor installed at the
pump bank outlet (T1).
1.
Go to
Pump bank
>
Pump-bank input-output settings
.
2.
Make sure the temperature sensor is enabled.
3.
Enter the parameters for the temperature sensor:
a.
Temperature sensor range
: Enter the maximum
temperature that the sensor can measure.
b.
Temperature sensor offset
: Set the offset, if any.
The offset is zero by default.
Related information
4.2 Mechanical installation. See page 5.
9.1 Navigating the display. See page 14.
5.1.7 Setting the chillers sensors
5.1.7.1 Setting the pressure sensors for the chillers
The controller must be unlocked.
This task is about setting the differential pressure sensor installed
over a chiller.
1.
Go to
Chiller bank
>
Chiller bank status
.
2.
Select the chiller where the sensor is located.
3.
Go to
Input-output settings
.
4.
Differential pressure sensor range
: Enter the maximum
pressure that the sensor can measure.
Related information
9.1 Navigating the display. See page 14.
5.1.7.2 Setting the temperature sensor for the chiller bank
The controller must be unlocked.
This task is about setting the temperature sensor installed at the
chiller bank outlet (T2).
1.
Go to
Chiller bank
>
Chiller-bank input-output settings
.
2.
Make sure the temperature sensor is enabled.
3.
Enter the parameters for the temperature sensor:
a.
Temperature sensor range
: Enter the maximum
temperature that the sensor can measure.
b.
Temperature sensor offset
: Set the offset, if any.
The offset is 0 by default.
Related information
4.2 Mechanical installation. See page 5.
4.2 Mechanical installation. See page 5.
9.1 Navigating the display. See page 14.
5.1.8 Setting the zone bank sensors
5.1.8.1 Setting the pressure sensors for the zones
The controller must be unlocked.
This task is about setting the differential pressure sensor installed
over each zone.
1.
Go to
Zone bank
>
Zone bank status
.
2.
Select the zone where the sensor is located.
3.
Go to
Input-output settings
.
4.
Differential pressure sensor range
: Enter the maximum
pressure that the sensor can measure.
Related information
9.1 Navigating the display. See page 14.
5.1.8.2 Setting the temperature sensor for the zone bank
The controller must be unlocked.
This task is about setting the temperature sensor installed at the
bypass valve outlet (T3).
1.
Go to
Zone bank
>
Zone-bank input-output settings
.
2.
Make sure the temperature sensor is enabled.
3.
Enter the parameters for the temperature sensor:
a.
Temperature sensor range
: Enter the maximum
temperature that the sensor can measure.
b.
Temperature sensor offset
: Set the offset, if any.
The offset is zero by default.
Related information
4.2 Mechanical installation. See page 5.
9.1 Navigating the display. See page 14.
5.1.9 Tuning the pump controller
The bypass valve controller must be tuned in order to have the
most suitable reaction time for your system.
1.
Go to
Menu
>
Tuning
.
2.
Select the tuning method:
•
Manual tuning
•
Auto tuning
3.
If you have selected
Manual tuning
, enter the
Proportional
gain (Kp)
and
Integral time (Ti)
.
If you want a faster reaction, increase the gain and reduce the
integral time. If you want a slower reaction, reduce the gain and
increase the integral time.
4.
If you have selected
Auto tuning
, enter the percentage of the
maximum speed for the pump bank that the controller should
use to start the auto tuning.
We recommend to start with 25 % of the maximum speed.
Related information
7.8 Controller tuning. See page 13.
5.1.10 Tuning the bypass valve controller
The controller must be tuned in order to have the most suitable
reaction time for your system. You can either tune the controller
manually by choosing the gain (Kp) and integral time (Ti) yourself or
let the controller determine these values automatically, based on
the configuration of your system.