background image

Pos.

Description

8

Air-handling zone: Air-handling unit (AHU),
fan, coil, etc.

Fig.

Example of a variable-primary-flow HVAC system with
three pumps, three chillers and three air-handling zones.

4.3 Electrical connection

The electrical installation must be carried out by an authorised
person in accordance with local regulations and the relevant wiring
diagram. Before connecting your devices to the main cabinet and
the subcabinets, check that the following requirements are met:

DANGER

Electric shock

Death or serious personal injury

Make sure that the power supply cannot be switched
on accidentally.

1.

The electrical installation must comply with enclosure class
IP54 or UL type 3R.

2.

The supply voltage and frequency must correspond to the
values stated on the nameplate.

3.

The wire cross-section must correspond to the specifications in
the wiring diagram.

4.

The type of control and/or feedback signal of connected
devices must correspond to the controller version. The signals
are described in the following table.

Connected device

Signal

Control

Feedback

External VFD

0-10 V

4-20 mA

Bypass valve

4-20 mA /0-10 V

4-20mA / 0-10 V

4.3.1 Connecting the main cabinet

The following devices must be connected according to the wiring
diagram delivered with the cabinet:

power supply

VFD

differential-pressure sensors over pumps, chillers and the two
first air-handling zones

chiller on/off signals from chiller controller, BMS or isolating
valve.

Optional

Bypass valve

temperature sensors

flow sensor

Hands / off / auto (HOA) switches for system

Hands / off / auto (HOA) switches for pumps.

If there is only one air-handling zone in your system, you can
connect a redundant differential-pressure sensor for the zone.
Connect the redundant sensor to the terminal for the sensor of the
second air-handling zone.

4.3.2 Connecting subcabinets

If you have ordered a subcabinet, the following devices must be
connected according to the wiring diagram delivered with the
subcabinet:

power supply

EtherCAT cable to main cabinet

EtherCAT cable to the next subcabinet, if any

differential pressure sensors from air-handling zones.

5. Commissioning the product

5.1 Setting the product

5.1.1 Setting the pump bank

The controller must be unlocked.
1.

Go to 

Pump bank

 > 

Pump bank settings

.

2.

Set the following parameters:
a.

Enable pump changeover

: Enable if you want the controller

to automatically change the operating pump after a defined
time.

b.

Time of day for changeover

: Enter the time for pump

changeover (1-24).

c.

Enable maximum number of running pumps

: Enable if

you do not want more than the specified maximum number
of pumps to operate at the same time.

d.

Maximum number of running pumps

: Enter the maximum

number of pumps to operate at a given time.

e.

Enable minimum number of running pumps

: Enable if

you want a minimum number of pumps to operate at the
same time when the controller is on.

f.

Minimum number of running pumps

: Enter the minimum

number of pumps to always operate.

g.

Minimum time between start and stop

: Enter the minimum

time in seconds for a pump to stop after having started.

h.

Ramp up / ramp down time

: Enter the time for the pump

ramp up, that is the time for the pump to accelerate to its
operating speed, and ramp down, that is the time for the
pump to decelerate to its stop speed.

i.

Number of pumps

: Enter the number of pumps in your

system.

j.

Enable terminal alarm

: Enable if you want the controller to

give alarms related to the pump terminal.

k.

Enable warning on single pump failure

: Enable if you

want the controller to give a warning when one pump fails.

l.

Enable alarm on all pump failure

: Enable if you want the

controller to give a warning when all pumps fail.

3.

Go to 

Pump bank

 > 

Cascade operation

.

4.

Set the following parameters:
a.

Cut-in speed

: Enter the speed at which a new pump is to be

cut in.

b.

Cut-out speed

: Enter the speed at which a pump is to be cut

out.
The cut-in and cut-out speed of a pump can be different
depending on the number of pumps running.

Related information

7.7 Pump cascade control. See page 12.

9.1 Navigating the display. See page 14.

9.11 Unlocking the controller. See page 15.

9.11 Unlocking the controller. See page 15.

5.1.1.1 Setting the pumps

1.

Go to 

Pump bank

 > 

Pump bank status

2.

Select the pump you want to set.

6

English (US)

Содержание Control HVAC

Страница 1: ...Control HVAC for VFD with selector switches 60 Hz North America Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ......

Страница 3: ...Control HVAC for VFD with selector switches English US Installation and operating instructions 4 3 Table of contents...

Страница 4: ...placed under warranty shall be warranted for twelve months from the date of the repair not to exceed the original warranty period This warranty does not cover parts damaged by decomposition from chemi...

Страница 5: ...ng the product 3 1 Inspecting the product Before installing the product do the following 1 Check that the product is as ordered 2 Check that no visible parts have been damaged 3 If parts are damaged o...

Страница 6: ...e next subcabinet if any differential pressure sensors from air handling zones 5 Commissioning the product 5 1 Setting the product 5 1 1 Setting the pump bank The controller must be unlocked 1 Go to P...

Страница 7: ...zone sensor fails a Enable alarm on bypass valve failure Enable if you want the controller to give an alarm when the bypass valve fails 1 The zone in focus is the zone in operation with the greatest...

Страница 8: ...formation 4 2 Mechanical installation See page 5 4 2 Mechanical installation See page 5 9 1 Navigating the display See page 14 5 1 8 Setting the zone bank sensors 5 1 8 1 Setting the pressure sensors...

Страница 9: ...pen the isolating valve of one chiller Do not start the chillers The controller prevents the pumps from starting if the isolating valves of all chillers are closed 4 Set the first pump selector switch...

Страница 10: ...settings 5 Speed of the pump bank 6 Speed reference currently calculated by the controller for the pump bank 7 Power consumption of the whole system Pos Description 8 Grundfos Eye It indicates the sta...

Страница 11: ...ge 10 7 1 4 Alarms Some devices of the system can send a warning or alarm signal depending on the degree of the issue It will be visible on the display The detailed description of the alarm or warning...

Страница 12: ...ing to the number of chillers in operation the controller adapts the pump operation to maintain a differential flow across the chillers within the allowed range If the bypass valve is controlled by th...

Страница 13: ...A system has three zone sensors with setpoints of 2 3 and 4 bar If the deadband has been set to 0 4 bar the bypass valve does not react when the measured value is between 3 6 and 4 4 bar The referenc...

Страница 14: ...h between the submenus such as status settings etc 9 2 Operating the controller remotely 1 Make sure that the system selector switch is in position Auto Remote 2 Go to Menu Settings Communication chan...

Страница 15: ...for user access 1 Go to Menu Settings General settings 2 Select the password you want to modify 3 Enter the new password 4 Press Enter Related information 7 11 User access See page 13 9 11 Unlocking t...

Страница 16: ...e front panel to Manual Local The chillers are switched off Switch on the chillers one at a time The chillers are defective Check the power supply isolating valve contactor etc of the chiller The cabl...

Страница 17: ...s on The VFD is on Cause Remedy Check the alarm log for alarms Fix the problem if needed Reset the alarm and check that it has been removed from the list The pump is stopped manually via the switch on...

Страница 18: ...he signal is within the range OK EL3051 1 channel analog input 4 20 mA single ended 12 bit only for version with 4 20 mA bypass valve On The signal is within the range OK Off The signal is off or outs...

Страница 19: ...Phone 281 994 2700 Toll Free 1 800 955 5847 Fax 1 800 945 4777 Peerless Pump 2005 Dr Martin Luther King Jr US 46202 Indianapolis Indiana U S A Phone 317 925 9661 Canada GRUNDFOS Canada Inc 2941 Brigh...

Страница 20: ...8 ECM 1236081 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos...

Отзывы: