background image

Pump
bank
mode

Pump
mode

Operation

All pumps in automatic mode operate at the
same speed.

Manual

Manual

The pump operates according to the
settings set in the pump menu. It can either
start at a selected speed or stop.

Manual

Off

The pump is switched off. It cannot be
started via the display nor the remote
management system.

Related information

7.1.2 Bank menu. See page 10.

9.5 Operating the pump bank manually. See page 14.

8.2 System operating modes

The table below describes the three operating modes for the
controller that can be activated via the system selector switch.

Mode

Description

Auto/
Remote

The controller controls the pump bank and bypass
valve, if any, according to the data collected from the
HVAC system. The controller can be controlled and
monitored via the remote management system.

Manual/
Local

The communication to the remote management
system is disabled. The controller operates according
to the user input set via the display. The user can
start and stop the pump bank and set the speed.

Off

The controller is switched off. It cannot be activated
via the display nor by the remote management
system. The display is still on and settings can be
changed.

Related information

7.1.2 Bank menu. See page 10.

7.2 The selector switches. See page 11.

9.2 Operating the controller remotely. See page 14.

9.3 Operating the controller manually. See page 14.

8.3 Bypass valve operating modes

The table below describes the two operating modes for the bypass
valve that can be activated via the display.

Mode

Description

Auto

The valve is controlled by the controller.

Manual

The valve is not controlled by the controller. Its position
can be set via the display.

Off

The valve is not controlled by the controller.

Related information

7.1.2 Bank menu. See page 10.

9.4 Setting the position of the bypass valve manually. See
page 14.

9. Operating the product

9.1 Navigating the display

In the dashboard, press the bank icon to enter the bank menu.

Under each bank menu, press the device icon to enter the
device menu.

Use the right and left arrows to switch between the submenus,
such as status, settings, etc.

9.2 Operating the controller remotely

1.

Make sure that the system selector switch is in position 

Auto/

Remote

.

2.

Go to 

Menu

 > 

Settings

 > 

Communication channel

.

3.

Enable the communication channel, which you want to use to
operate the controller remotely.

When remote access is enabled and it is not possible to start nor
stop the controller nor change the settings from the display.

Related information

8.2 System operating modes. See page 14.

9.3 Operating the controller manually

It is possible to switch the controller to manual mode in order to
operate the pump bank and the valve, if any, manually from the
display, regardless of the system data or Building Management
System data collected by the controller. This can be useful during
fault finding and service operation.

Set the system selector switch to 

Manual/Local

.

The communication with the remote management system, if any, is
now disabled and the pump bank starts operating in manual mode.
By default, the pump bank starts at the manual speed that was set
the last time the pump bank was operated manually. The first time
that the pump bank starts in manual mode, the speed is zero.

Related information

8.2 System operating modes. See page 14.

9.4 Setting the position of the bypass valve manually

1.

Go to 

Zone bank

 > 

Zone bank status

.

2.

Set the operating mode of the valve to 

Manual

.

The valve opening is set to the value that was set the last time
the valve was operated manually.

3.

Set the opening of the valve by dragging the pointer on the
scale.
The value indicated on the scale is in percentage of the
maximum opening.

Related information

8.3 Bypass valve operating modes. See page 14.

9.5 Operating the pump bank manually

The pumps that are in automatic mode can be operated together at
a manually defined speed.
1.

Set the system selector switch to 

Manual/Local

.

2.

Go to 

Pump bank

 > 

Pump bank status

.

3.

Set the speed by dragging the pointer on the scale.
The speed indicated on the scale is in percentage of the
maximum speed.

All the pumps that are in automatic mode operate at the same
speed. By default, the start speed is the manual speed that was last
set in manual mode. The pumps that are not in automatic mode
operate independently.

14

English (US)

Содержание Control HVAC

Страница 1: ...Control HVAC for VFD with selector switches 60 Hz North America Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ......

Страница 3: ...Control HVAC for VFD with selector switches English US Installation and operating instructions 4 3 Table of contents...

Страница 4: ...placed under warranty shall be warranted for twelve months from the date of the repair not to exceed the original warranty period This warranty does not cover parts damaged by decomposition from chemi...

Страница 5: ...ng the product 3 1 Inspecting the product Before installing the product do the following 1 Check that the product is as ordered 2 Check that no visible parts have been damaged 3 If parts are damaged o...

Страница 6: ...e next subcabinet if any differential pressure sensors from air handling zones 5 Commissioning the product 5 1 Setting the product 5 1 1 Setting the pump bank The controller must be unlocked 1 Go to P...

Страница 7: ...zone sensor fails a Enable alarm on bypass valve failure Enable if you want the controller to give an alarm when the bypass valve fails 1 The zone in focus is the zone in operation with the greatest...

Страница 8: ...formation 4 2 Mechanical installation See page 5 4 2 Mechanical installation See page 5 9 1 Navigating the display See page 14 5 1 8 Setting the zone bank sensors 5 1 8 1 Setting the pressure sensors...

Страница 9: ...pen the isolating valve of one chiller Do not start the chillers The controller prevents the pumps from starting if the isolating valves of all chillers are closed 4 Set the first pump selector switch...

Страница 10: ...settings 5 Speed of the pump bank 6 Speed reference currently calculated by the controller for the pump bank 7 Power consumption of the whole system Pos Description 8 Grundfos Eye It indicates the sta...

Страница 11: ...ge 10 7 1 4 Alarms Some devices of the system can send a warning or alarm signal depending on the degree of the issue It will be visible on the display The detailed description of the alarm or warning...

Страница 12: ...ing to the number of chillers in operation the controller adapts the pump operation to maintain a differential flow across the chillers within the allowed range If the bypass valve is controlled by th...

Страница 13: ...A system has three zone sensors with setpoints of 2 3 and 4 bar If the deadband has been set to 0 4 bar the bypass valve does not react when the measured value is between 3 6 and 4 4 bar The referenc...

Страница 14: ...h between the submenus such as status settings etc 9 2 Operating the controller remotely 1 Make sure that the system selector switch is in position Auto Remote 2 Go to Menu Settings Communication chan...

Страница 15: ...for user access 1 Go to Menu Settings General settings 2 Select the password you want to modify 3 Enter the new password 4 Press Enter Related information 7 11 User access See page 13 9 11 Unlocking t...

Страница 16: ...e front panel to Manual Local The chillers are switched off Switch on the chillers one at a time The chillers are defective Check the power supply isolating valve contactor etc of the chiller The cabl...

Страница 17: ...s on The VFD is on Cause Remedy Check the alarm log for alarms Fix the problem if needed Reset the alarm and check that it has been removed from the list The pump is stopped manually via the switch on...