Dimensions
[mm]
[inch]
Main cabinet
600 x 600 x 250
23.5 x 23.5 x 10
Subcabinet
380 x 380 x 210
15 x 15 x 8.5
The dimensions are indicative. They can vary slightly depending on
the local regulations and the cabinet builder.
13.2 Controller technical data
The controller is located at the back of the display. The inputs and
outputs of the controller are located underneath the controller.
1
4
5
7
6
3
2
TM067861
Pos.
Description
1
COM output, for connection to external
display
2
Micro SD card
3
USB port for data logging and firmware
installation
4
EtherCAT connection to input and output
terminals
5
LAN connection to GRM, BACnet IP,
Modbus TCP (optional)
6
24 VDC power supply for the controller
7
Ground. It can be connected to the main
cabinet for proper grounding.
Fig.
CP2611 11.6" controller
13.3 I/O modules and terminals
Digital inputs
Name
Description
Indicator light
EL1004
4-channel digital input,
24 VDC, 3 ms filter time
•
On: The connected device
is active.
•
Off: The connected device
is not active.
EL1008
8-channel digital input,
24 VDC, 3 ms filter time
•
On: The connected device
is active.
•
Off: The connected device
is not active.
Digital outputs
Name
Description
Indicator light
EL2004
4-channel digital
output, 24 VDC, 0.5 A
•
On: The connected device
is active.
•
Off: The connected device
is not active.
EL2008
8-channel digital
output, 24 VDC, 0.5 A
•
On: The connected device
is active.
•
Off: The connected device
is not active.
Analog inputs
Name
Description
Indicator light
EL3058
8-channel analog input,
4-20 mA, single-ended,
12-bit
•
On: The signal is off or
outside the range
(fault).
•
Off: The signal is within
the range (OK).
EL3051
1-channel analog input,
4-20 mA, single-ended,
12-bit, only for version
with 4-20 mA bypass
valve
•
On: The signal is within
the range (OK).
•
Off: The signal is off or
outside the range
(fault).
EL3061
1-channel analog input,
0-10 V, single-ended, 12-
bit, only for version with
0-10 V bypass valve
•
On: The signal is within
the range (OK).
•
Off: The signal is off or
outside the range
(fault).
Analog outputs
Name
Description
Indicator light
EL4004
4-channel analog
output 0-10 V, 12-bit
•
On: The controller is
connected to the device.
•
Off: No connection
between the controller and
the device.
EL4008
8-channel analog
output 0-10 V, 12-bit
•
On: The controller is
connected to the device.
•
Off: No connection
between the controller and
the device.
EL4001
1-channel analog
output 0-10 V, 12-bit,
only for version with
0-10 V bypass valve
•
On: The controller is
connected to the device.
•
Off: No connection
between the controller and
the device.
EL4021
1-channel analog
output, 4-20 mA, 12-
bit, only for version
with 4-20 mA bypass
valve
•
On: The controller is
connected to the device.
•
Off: No connection
between the controller and
the device.
Other
Name
Description
EK1100
EtherCAT terminal.
In the main cabinet: It enables bus communication
between the main controller, the "EL" terminals and the
first subcabinet.
In subcabinets: It enables communication with the main
cabinet and/or other subcabinets.
EL9011 It terminates the right end of a terminal block.
14. Disposing of the product
This product or parts of it must be disposed of in an
environmentally sound way.
1.
Use the public or private waste collection service.
2.
If this is not possible, contact the nearest Grundfos company
or service workshop.
See also end-of-life information at
18
English (US)