Disturbance variable feedforward
OFF
Without disturbance variable
feedforward.
ON
With disturbance variable feedforward.
15
Enabling of third operator level
OFF Third operator level disabled.
ON
Third operator level enabled (a colon
flashes in display)
16
Inversion of disturbance variable
OFF Disturbance variable not inverted.
ON
Disturbance variable inverted.
17
Controller configuration
OFF
Device operates as two two-position
controllers for SP 1 and SP 2 (if code
function 18 is also OFF).
ON
Device operates as three-position
controller with feedback of positioning
angle.
18
Controller configuration
OFF
Device operates as two two-position
controllers for SP 1 and SP 2 (if code
function 17 is also OFF).
ON
Device operates as three-position
controller without feedback of
positioning angle.
19
Signal of current output 1 (control output for
SP 1)
OFF Signal 0 to 20 mA.
ON
Signal 4 to 20 mA.
20
Signal of current output 2 (position of
feedback potentiometer or control output for
SP 2)
OFF Signal 0 to 20 mA.
ON
Signal 4 to 20 mA.
21
Function of current output 2
OFF Position of feedback potentiometer.
ON
Control output for switching point 2.
No.
22
Controller configuration
OFF Device operates as setpoint controller.
ON
Device operates as ratio controller.
Setpoint is entered via current input 2.
23
Assignment of LEDs for display of control
deviation
OFF
LEDs indicate deviation of actual value
from SP 1.
ON
LEDs indicate deviation of actual value
from SP 2.
24
Assignment of current input 2
OFF
0 (4) mA correspond to 0 %.
20 mA correspond to 100 %.
ON
When used as a ratio controller or
controller with disturbance variable
feedforward:
Current input is assigned to a specific
range (third operator level).
No.