English (GB)
45
Parameter settings
Required pH value: e.g. pH 7.00.
Connection diagram
Fig. 62
Connection diagram for dosing pump,
contact input
SP 1
Above the required pH value, e.g. 52 % (correlates with pH 7.28).
Pulse frequency for SP 1
72 (maximum value (correlates with 7,200 strokes per hour).
The dosing capacity of the pump is then fully utilised.
SP 2
Below the required pH value, e.g. 48 % (correlates with pH 6.72).
Pulse frequency for SP 2
72 (maximum value (correlates with 7,200 strokes per hour).
The dosing capacity of the pump is then fully utilised.
X
p
According to local conditions, e.g. 100 %
• Higher setting results in smaller control steps.
• Lower setting results in larger control steps.
T
n
According to local conditions, e.g. 300 sec
• Higher setting results in slower control.
• Lower setting results in faster control.
T
v
0
Hysteresis
e.g. 1 %
Interpulse period
-
Actuating time
0
Minimum pulse width
≥
0.3 sec
Required code functions
None
Other code functions
As required
TM
03
71
1
5
1
613
15 16 17 18 19 20 21 22 23
24 25 26
L1 N PE
L1 N PE
L1 N PE
1
2a
3
4
4
2b
Pos.
Description
1
Free relay outputs
2a
Dosing pump for leach
2b
Dosing pump for acid
3
Power supply
4
Contact input