![background image](http://html1.mh-extra.com/html/grunbeck/delta-p/delta-p_operation-manual_2270826055.webp)
Other information
55 | 74
BA_
T
D
3-
BM
001e
n_
01
4_D
el
ta-
p.docx
12.3
Sodium content in the water
When softening water by 1 °dH (0.18 mmol/l), the sodium content increases by approx.
8.2 mg/l. The German Drinking Water Ordinance specifies that the sodium content of
drinking water must not exceed 200 mg/l. Select a soft water hardness with a sodium content
less than 200 mg/l.
The local water suppliers will inform you about the sodium content of your raw water.
Sample calculation:
Raw water hardness: 28 °dH (50 °f)
Sodium content in the raw water: 10.5 mg/l
Admissible increase of the sodium content by softening:
● 200 mg/l - 10.5 mg/l = 189.5 mg/l
● 189.5 : 8.2 = 23 °dH (41 °f)
The raw water hardness is allowed to be reduced from 28 °dH (50 °f, 5 mmol/l) to 5 °dH (9 °f,
0.9 mmol/l).
12.4
Hardness range
Recommendation soft water hardness
Soft water hardness
Remark
3 °dH
5.3 °f
0.53 °mmol/l
Minimum value as per DIN 12502 Corrosion
Protection.
4 – 6 °dH
7.1 – 10.7 °f
0.71 – 1.07 mmol/l
Ideal soft water, highest comfort.
Содержание Delta-p
Страница 1: ...We understand water Softening Water softener Delta p Operation manual ...
Страница 57: ...Mounting instructions 57 74 BA_TD3 BM001en_014_Delta p docx ...
Страница 58: ...Mounting instructions 58 74 BA_TD3 BM001en_014_Delta p docx ...
Страница 59: ...Mounting instructions 59 74 BA_TD3 BM001en_014_Delta p docx ...
Страница 60: ...Mounting instructions 60 74 BA_TD3 BM001en_014_Delta p docx ...
Страница 62: ...Mounting instructions 62 74 BA_TD3 BM001en_014_Delta p docx ...
Страница 72: ......