3 Storage and Transportation
Installation 4
WARNING
Ø
Ensure to read the Guidance before installation in order to
understand product information and safety cautions/ Assurez-vous de
lire le guide avant l'installation afin de comprendre les informations
sur le produit et les précautions de sécurité;
Ø
Operators should be well trained technicians and fully understand
the whole photovoltaic system, grid network, working principle and
national regional standards/ Les opérateurs doivent être des
techniciens bien formés et bien comprendre l'ensemble du système
photovoltaïque, le réseau électrique, le principe de fonctionnement et
les normes régionales nationales;
Ø
Installers must use insulating tools and wear safety equipment/ Les
installateurs doivent utiliser des outils isolants et porter des
équipements de sécurité;
Ø
Device damages caused by failure to comply with storage,
transportation, installation and use requirements specified in
Guidance are not coved by Warranty/ Les dommages à l'appareil
causés par le non-respect des exigences de stockage, de transport,
d'installation et d'utilisation spécifiées dans le guide ne sont pas
couverts par la garantie.
Ø
The PACK can only be installed indoors. Regarding indoor
installation, please do not install it in the bedroom, living room,
kitchen, etc/ Le PACK ne peut être installé qu'en intérieur. En ce qui
concerne l'installation à l'intérieur, veuillez ne pas l'installer dans la
chambre, le salon, la cuisine, etc.
Ø
Different types of batteries are not recommended to be mixed and
used in parallel/ Il est déconseillé de mélanger et d'utiliser différents
types de batteries en parallèle.
Ø
The battery system cannot be installed, dismantled, and maintained
when it has been powered on/ Le système de batterie ne peut pas être
installé, démonté et entretenu lorsqu'il a été mis sous tension.
4.1 Installation environment
The ambient temperature for the installation of the battery system shall be above 0
℃
,
below 50
℃
, and the humidity shall between 5% and 85%.
Fig 4.1: Installation environment requirements
Max
. +
50
℃
Min
.
0℃
Indoor installation
7
8
Avertissement
3.1 Storage Requirements
Ø
Place the PACK follow the identification on the packing case during storage.
Ø
Do not put the PACK upside down or sidelong.
Ø
The defective PACK needs to be separated from other PACKs.
Ø
The storage environment requirements are as follows:
1) Install the PACK in a dry and clean place with proper ventilation.
2) The storage temperature for a short week is between -20
℃
to 50
℃
.
3) If you store the PACK over a long period of six months, the storage temperature is
between-20°C to 40°C, relative humidity: 5%~85%RH.
4) Place the PACK away from corrosive and organic substances (including gas exposure).
5) Free from direct exposure to sunlight and rain .
6) At least two meters away from heat sources (such as a radiator).
7) Free from exposure to intensive infrared radiation.
Ø
If the PACK has not been used for more than six months, it needs to be charged, The
charging procedure is as follows:
1) Identify the PACK that needs charging;
2) Refer to quick installation guidance, complete the installation and wire connection.
Ensure PACK in off status during all the steps.
3) Set the power system as “CC
≤
25A, CV=55.8V” , activate the PACK and start
recharging.
4) Recharge until LED2 flicks.
5) Having completed recharge, leave circuit open for five minutes before check voltage. If
voltage is not less than 52V, the recharge succe.
3.2 Transportation Requirement
PACK has been certified in UN38.3 (Section 38.3 of the sixth Revised Edition of the
Recommendations on the Transport of Dangerous Goods: Manual of Tests and Criteria)
and SN/T 0370.2-2009 (Part 2: Performance Test of the Rules for the Inspection of
Packaging for Exporting Dangerous Goods). PACK is classified as category 9 dangerous
goods.
Ø
The PACK shall not be transported with other inflammable, explosive or toxic
substances.
Ø
Ensure the original Package and label complete and recognizable.
Ø
Prohibit direct exposure to sunlight, rain, condensing water caused by temperature
difference and mechanical damages.
Ø
There will be a drop in capacity during transportation and storage.
Ø
Transportation temperature is between-20°C to 45°C, relative humidity: 5%~85%RH.
RH
.+
5
%~+