20
(
ALM
Light
Flickers
)
Interior CAN
Communication
failure
Communication loss
between
two parallel
1. Check Can connection
between two batteries, CAN
connection between Linkin and
Linkout;
Parallel
connection
failure
protection
Communication
failure
between two
parallel
connected PACK
1. Check Can connection
between two batteries, CAN
connection between Battery and
PCS;
(ALM
Light on)
Discharge short
circuit
External short circuit
of
PACK
There is safety risk and user
should stop using battery
User should contact installer to
Precharger short
circuit
Precharger
overtime circuit
Type
inconsistency of
PACK
The pack type is
different
There is safety risk and user
should stop using battery
User should contact installer to
use the same PACK in Parallel.
Main circuit fault
BMS main power
circuit failure
There is safety risk and user
should stop using battery.
User should contact installer to
repair battery
Technical Specifications 7
19
No.
Items
Specification
1
Parallel number of Battery systems
1
2
2
Battery Model
AXE 5.0L-C1/X1
AXE 10.0L-C1/X1
3
Nominal Capacity/Energy
100Ah/5.0kWh
200Ah/10.0kWh
4
Rated Capacity/Energy
90Ah/4.6kWh
180Ah/9.2kWh
5
Rated Voltage
51.2V
6
Operating Voltage
46.4 - 57.6V
7
Rated Charging/discharging current
60A
120A
8
Max Charging/discharging current
80A
150A
9
Over current protection
90A
160A
10
Rated Charging/discharging power
3kW
6kW
11
Max Charging/discharging power
4kW
7.6kW
12
Battery Type
Cobalt Free Lithium Iron Phosphate (LFP)
13
Operative temperature range
0°C~50°C
14
Recommended operating
15°C~30°C
15
Storage conditions
Temperature: -20°C ~ +50°C/ 7 days
-20°C
~
40°C/6 months
Humidity
:
5%~85%RH
Within six months after initial charge
16
Cooling
Natural cooling
17
Dimension (W/D/H)
(
mm
)
650*350*140
650*350*280
18
Weight
40kg
80kg
19
Installation
Floor standing installation
20
Ingress protection
IP 20
21
Cell safety certification
IEC62619/UL1973
22
PACK certification
IEC 62619/IEC 63056/
UL1973/CE/UKCA/FCC/RoHS/UN38.3
23
Charging batteries
See Appendix II
24
Communication port
CAN
25
Battery Designation
IFpP/51/161/119
/[(1P16S)1P]M/0
+50/90
IFpP/51/161/119/
[(1P16S)2P]M/0+
50/90
26
Multiple clusters in parallel
Max.8 Clusters
Functional parameters of AXE 5.0L Energy Storage System are as shown below: