4.5.3 Remove the power cord

PC

S

Press

Press

Upwards

Fig 4.11: Remove the power cord

  Power on and off the Battery 5

5.1 Power On

WARNING

Ø

The installation and use of batteries involve much specialized 

knowledge. Therefore, technicians should be given appropriate 
technical training and obtain operational certificates in compliance 
with local laws and regulations. Please ensure technicians have 
obtained training certificate before operation/ L'installation et 
l'utilisation des batteries impliquent des connaissances très 
spécialisées. Par conséquent, les techniciens doivent recevoir une 
formation technique appropriée et obtenir des certificats opérationnels 
conformément aux lois et réglementations locales. Veuillez vous assurer 
que les techniciens ont obtenu un certificat de formation avant 
l'utilisation.

Ø

Please stand on dry insulating objects and do not wear conductive 

material such as watches and necklace during operation. Insulated 
tools should be used/ Veuillez vous tenir sur des objets isolants secs et 
ne pas porter de matériaux conducteurs tels que des montres et des 
colliers pendant le fonctionnement. Des outils isolés doivent être 
utilisés.

Ø

Do not contact any positions with potential difference/ Ne contactez 

aucune position avec une différence de potentiel.

Ø

Prohibition sign should be hung on the battery: " Non - 

professionals, do not touch"/ Un panneau d'interdiction doit être 
accroché sur la batterie : " Non - professionnels, ne pas toucher ".

Ø

If any abnormalities occur during the startup phase, power off the 

PACK immediately. After problem confirmed, proceed again/ Si des 
anomalies surviennent pendant la phase de démarrage, mettez 
immédiatement le PACK hors tension. Une fois le problème confirmé, 
recommencez.ACK immediately. After problem confirmed, proceed 
again.

Ø

 Make sure the inverter is turned off before checking the PACK/ 

Assurez-vous que l'onduleur est éteint avant de vérifier le PACK.

15

16

Step 1: Remove the security screw

Step 2: Press the buttons on both sides of the terminal at the same time, and then pull it 

out forcefully

When multiple batteries are connected in parallel or multiple clusters of batteries are 

connected in parallel, press one of the battery power buttons and all the batteries 

connected in parallel can be turned on.

WARNING

Avertissemen

Power on the PACK by pressing power button(t>2S)

Serial

Procedures

Acceptation criteria

1

Connect the battery and PCS

Make sure the wiring harnesses are well 
connected

2

Close the breaker of the PACK

Make sure the breaker is ON

3

Press POWER button for three to 
five seconds. Observe the LED 
indication on panel.

1. If both RUN/ALM and SOC lights turn on 
normally, PACK is powered on successfully.

2. If RUN/ALM light turns red, there is a failure 
and should solve it before power on again.

4.6 About mixing old and new batteries in parallel

Please ensure batteries in parallel connection are from the same batch, same model 
and same manufacturer. Do not mix an old battery with a new battery. Batteries 
undergone less than 300 cycles are defined as new batteries.The installation time of 
the newly added battery and the installed battery is less than or equal to 1 year, and 
the newly added battery must be within the shelf life of 6 months.

Содержание AXE 5.0L-C1

Страница 1: ...ndustrial Park Hangcheng Ave Guxing Community Xixiang Subdistrict Bao an District Shenzhen China 86 755 2747 1942 www ginverter com T E W service ginverter com Download Manual Growatt New Energy Resid...

Страница 2: ...es the installation electrical connection operation commission maintenance and troubleshooting of AXE 5 0L C1and AXE 5 0L X1 Battery System hereafter simply put AXE 5 0L Before installing and operatin...

Страница 3: ...to 8 clusters in parallel to expand the capacity and power of the energy storage system The whole battery system communicates to Power Conversion System PCS via CAN Monitoring voltage current and tem...

Страница 4: ...ts such as wires Do not dispose the batteries in fire which may cause an explosion The PACK shall not come in contact with liquids The PACK can only be installed indoors Regarding indoor installation...

Страница 5: ...er frapper planter un clou ou pi tiner le PACK Cela peut provoquer un d gagement de chaleur une explosion ou un incendie En cas de fuite d lectrolyte ne pas mettre l lectrolyte en contact avec les yeu...

Страница 6: ...allation environment requirements Max 50 Min 0 Indoor installation 7 8 Avertissement 3 1 Storage Requirements Place the PACK follow the identification on the packing case during storage Do not put the...

Страница 7: ...Shoes 4 4 Check Check the package Check the PACK package before open it If any abnormity is detected do not open the Package and contact your distributor Check the power Check and confirm the PACK is...

Страница 8: ...n parall le 4 Please install indoors and ensure the level of the ground Veuillez installer l int rieur et assurer le niveau du sol Fig 4 5 Multiple AXE 5 0L with base installation process 4 5 2 Electr...

Страница 9: ...y cluster 4 5 2 3 Multi cluster wiring CAN communication Power Power PE To PCS Cluster 1 Cluster 2 Cluster 3 Cluster 8 Fig 4 9 Block diagram of multi cluster system PCS Link in Link out PCS Link in Li...

Страница 10: ...er off the PACK immediately After problem confirmed proceed again Si des anomalies surviennent pendant la phase de d marrage mettez imm diatement le PACK hors tension Une fois le probl me confirm reco...

Страница 11: ...e Suggested actions ALM ALM Light Flickers Discharge under voltage protection Single cell voltage below the threshold for under voltage protection There is over discharge risk User should stop dischar...

Страница 12: ...5 0L C1 X1 AXE 10 0L C1 X1 3 Nominal Capacity Energy 100Ah 5 0kWh 200Ah 10 0kWh 4 Rated Capacity Energy 90Ah 4 6kWh 180Ah 9 2kWh 5 Rated Voltage 51 2V 6 Operating Voltage 46 4 57 6V 7 Rated Charging...

Страница 13: ...1P16S 3P M 0 50 90 IFpP 51 161 119 1P16S 4P M 0 50 90 26 Multiple clusters in parallel Max 8 Clusters No Items Specification 1 Parallel number of Battery systems 5 6 2 Battery Model AXE 25 0L C1 X1 A...

Страница 14: ...P16S 7P M 0 50 90 IFpP 51 161 119 1P16S 8P M 0 50 90 26 Multiple clusters in parallel Max 8 Clusters No Items Specification 1 Parallel number of Battery systems 9 10 2 Battery Model AXE 45 0L C1 X1 AX...

Страница 15: ...arge and over discharge alarm t 1S RUN ALM light flicker green Over charge and over discharge protection t 1S RUN ALM light flicker green Charging current limit does not respond t 1S RUN ALM light fli...

Страница 16: ...er red External CAN communicat ion failure t 1S RUN ALM light flicker red Interior CAN communicat ion failure t 1S RUN ALM light flicker red Parallel connection failure t 1S RUN ALM light flicker red...

Отзывы: