Configuring Controllers
Page 22
For
RS485 connectivity
, configure
controllers as follows:
Give the controller a name. We
suggest using a name that identifies
its location or purpose.
1
Choose the connection mode:
Relay
to define a Relay controller or
485 Only
for all other controllers in a RS485 chain. Different addressing options appear.
For
Relay controllers
: define the IP settings and set the baud rate for the
RS485 line (defaults to 19200).
One controller must be configured as a
Relay
controller: it acts as a line header
and requires an IP connection as well
as a RS485 line.
All other linked controllers must be
configured as
485 only
.
2
3
For
485 Only controllers
: choose the managing Relay controller and set the
baud rate (defaults to 19200)
4
1
2
3
4