   Installation Instructions 

Duct RH/Temp Sensor

NTDAMOD

Before Installation

Read these instructions carefully before installing and commissioning 

the RH/T sensor. Failure to follow these instructions may result in 

product damage. Do not use in an explosive or hazardous environment, 

with combustible or flammable gases, as a safety or emergency stop 

device or in any other application where failure of the product could 

result in personal injury.

 Take electrostatic discharge precautions 

during installation and do not exceed the device ratings. 

Figure 1

Figure 2

Figure 4

Figure 3

EMT/Cable Gland Connection Holes

EMT Connector

Connection Hole Plug

A foam gasket is provided on the back of the enclosure that provides a 

tight seal against any air leaks. 

Using a Phillips screwdriver, remove the (2) cover screws, as shown in 

Figure 2.  Remove cover and set aside with screws for re-installing after 

wiring and set up.  

Two 21 mm (0.8125”) holes are provided for connection of either 

12.77mm (0.5” ) EMT or a cable gland style connector as shown in Figure 3. 

Insert the EMT or cable gland connector through the hole and securely 

fasten using a locknut.   If only one connection hole is required, use the 

included hole plug to cap off the unused one as shown in Figure 4.  

Special care must be taken not to damage any internal components 

during installation. 

Make wire connections as per the “Wiring” illustrations on Page 2. 

Once wiring and set up are complete, re-install cover and tighten the (2) 

screws using a Phillips screwdriver. 

Mounting

The sensor installs directly into any air duct with a minimum width/diameter of 25.5 cm (10”).  Select a suitable installation 

area in the middle of the duct wall.  To achieve the best reading, do not place in an area where air stratification may be 

present.  

Mount the sensor at least 1.5 m (5 ‘ ) in either direction from elbows, dampers, filters or other duct restrictions.  

Avoid areas where the transmitter is exposed to vibrations or rapid temperature changes.

Once a suitable spot is selected, drill a  15 -20 mm (0.6” - .75“ ) hole for the probe.

Slide the probe in the drilled hole until the enclosure is flush against the duct.  The airflow direction is not important.  Secure 

the enclosure to the duct with (2) #10 x 1” (25 mm) self tapping screws (Not provided).  Tighten screws until the enclosure is 

tight against the duct and there is no movement of the enclosure as shown in Figure 1.  

Introduction

The duct RH/T network sensor uses a highly accurate and reliable 

Thermoset Polymer based capacitance humidity sensor and 

curve-matched NTC thermistor temperature sensor together with 

state-of-the-art digital linearization and temperature compensated 

circuitry to monitor humidity and temperature levels in a duct and 

transmit values via Modbus communication to a building automation 

system.  The sensors are encapsulated in a 60 micron HDPE filter at the 

end of a 230 mm (9”) S/S probe and a compact enclosure. 

Содержание NTDAMOD

Страница 1: ...4 Special care must be taken not to damage any internal components during installation Make wire connections as per the Wiring illustrations on Page 2 Once wiring and set up are complete re install cover and tighten the 2 screws using a Phillips screwdriver Mounting The sensor installs directly into any air duct with a minimum width diameter of 25 5 cm 10 Select a suitable installation area in the...

Страница 2: ...SHLD terminal on each device If the device is installed at either end of the network an end of line EOL termination resistor 121 ohm should be installed in parallel to the A and B terminals This device includes a network termination jumper and will connect the resistor correctly on the pcb Simply move the pcb jumper to the EOL position and no external resistor is required as shown in Figure 7 The ...

Страница 3: ...to ModBus Protocol This section describes the implementation of the ModBus protocol It is intended to assist control system programmers who may need to add support to their systems to communicate with this device This device communicates on standard ModBus networks using RTU mode transmission It operates as a slave device address from 1 to 255 and expects a ModBus master device to transmit queries...

Страница 4: ...ion Codes 0x03 Read holding registers Query Slave address 0x01 to 0xFF Function code 0x03 Starting address MSB Starting address LSB Quantity of registers MSB Quantity of registers LSB CRC LSB CRC MSB Starting address 0x0000 to 0xFFFF Quantity of registers 0x0000 to 0x007D Response Slave address 0x01 to 0xFF Function code 0x03 Byte count 2N Register value MSB Register value LSB CRC LSB CRC MSB N Qu...

Страница 5: ...01 CRC LSB CRC MSB Response Slave address 0x01 to 0xFF 0x03 0x02 Register value MSB Register value LSB CRC LSB CRC MSB Register value 0x0000 to 0x03E8 corresponding to 0 to 100 RH multiplier 10 This register has a multiplier of 10 the application must divide by 10 to obtain the correct value 0x06 Write TEMPERATURE_OFFSET Query Slave address 0x01 to 0xFF 0x06 0x00 0x02 Register Value MSB Register v...

Страница 6: ...o conform to a local reference Register value 0xFFF6 to 0x000A for 10 to 10 corresponding to RH_OFFSET 10 to 10 RH ie 0x0003 3 3 RH offset 0x06 Write TEMPERATURE_UNITS Query Slave address 0x01 to 0xFF 0x06 0x00 0x04 0x00 Register value LSB CRC LSB CRC MSB Response Slave address 0x01 to 0xFF 0x06 0x00 0x04 0x00 Register value LSB CRC LSB CRC MSB Register value 0x0000 sets the device to C operation ...

Страница 7: ...me 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years Temperature Sensor 20KΩ NTC thermistor Accuracy 0 2 C 0 4 F curve matched Range 40 50 C 40 122 F Resolution 0 1 C F Interface Hardware 2 wire RS 485 Software Native ModBus MS TP protocol RTU Baud Rate 38400 Network Address Range Locally set to 1 255 Parity None Stop Bits 1 CRC A001 CRC 16 reverse GreystoneEnergySystems Inc 150EnglishD...

Отзывы: