background image

      

Wiring

Deactivate the 24 Vac/dc power supply until all connections 

are made to the device to prevent electrical shock or 

equipment damage. Follow proper electrostatic discharge 

(ESD) handling procedures when installing the device or 

equipment damage may occur. Use 22 AWG shielded wiring 

for all connections and do not locate the device wires in the 

same conduit with wiring used to supply inductive loads 

such as motors. Make all connections in accordance with 

national and local codes.

Connect the 24 Vac/dc power supply to the terminals 

labeled PWR (power) and COM (common) as shown in 

Figure 6.  This device has a half-wave type power supply so 

use caution when wiring multiple devices so that the circuit 

ground point is the same on all devices and the controller. 

Use caution if 24 Vac power is used and one side of the 

transformer is earth-grounded. In general, the transformer 

should NOT be connected to earth ground when using 

devices with RS-485 network connections. The device is 

reverse voltage protected and will not operate if connected 

backwards.

Connect the RS-485 network with twisted shielded pair to 

the terminals marked A-, B+ and SHLD (shield) as shown in 

Figure 6.  The positive wire connects to B(+) and the 

negative wire connects to A(-) and the cable shield must be 

Greystone Energy Systems, Inc.  150 English Drive,   Moncton, NB  E1E 4G7  Canada  Tel: +1-506-853-3057  Tollfree (North America): +1-800-561-5611  Fax: +1-506-853-6014

Email: [email protected]    Web: www.greystoneenergy.com

0001342

B+

A-

SHLD

PWR

COM

EOL

2
4

16

32

1

8

64

BUS ADDRESS

0001342

B+

A-

SHLD

PWR

COM

EOL

2
4

16

32

1

8

64

BUS ADDRESS

0001342

B+

A-

SHLD

PWR

COM

EOL

2
4

16

32

1

8

64

BUS ADDRESS

B+

A-

Shield

24 Vdc

Common

connected to the SHLD terminal on each device. If the device is installed at either end of the network, an end-of-line (EOL) 

termination resistor (121 ohm) should be installed in parallel to the A(-) and B(+) terminals. This device includes a network 

termination jumper and will connect the resistor correctly on the pcb. Simply move the pcb jumper to the EOL position and 

no external resistor is required as shown in Figure 7. The ground wire of the shielded pair should be connected to earth 

ground at the end of the network and the master is not grounded. Do not run bus wiring in the same conduit as line voltage 

wiring.
A network segment is a single shielded wire loop run between several devices (nodes) in a daisy chain configuration. The total 

segment length should be less than 4000 feet (1220 meters) and the maximum number of nodes on one segment is 127. 

Nodes are any device connected to the loop and include controllers, repeaters and sensors such as the RH/T Sensor but does 

not include the EOL terminators. To install more devices, or to increase the network length, repeaters will be required for 

proper communication. The maximum daisy chain length (segment) depends on transmission speed (baud rate), wire size 

and number of nodes. If communication is slow or unreliable, it may be necessary to wire two daisy chains to the controller 

with a repeater for each segment.

0001342

B+

A-

SHLD

PWR

COM

EOL

2

1

BUS ADDRESS

0001342

B+

A-

SHLD

PWR

COM

EOL

2

1

BUS ADDRESS

0001342

B+

A-

SHLD

PWR

COM

EOL

2

1

BUS ADDRESS

B+

A-

Shield

External 24 Vdc 

Power Supply or 

24 Vac Transformer

Common

Modbus Master

Modbus Master

Building Controller

0001342

B+

A-

SHLD

PWR

COM

EOL

2
4

16

32

1

8

64

BUS ADDRESS

EOL

EOL

OFF

ON

Set EOL
Jumper

Figure 5

Figure 6

Figure 7

Building Controller

Device 1

Device 2

Device 3

Device 1

Device 2

Device 3

Connect Shield One End Only 

Connect Shield One End Only 

0001338

B+

A-

SHLD

PWR

COM

EOL

2

4

16

32

1

8

64

BUS ADDRESS

128

Содержание NTDAMOD

Страница 1: ...4 Special care must be taken not to damage any internal components during installation Make wire connections as per the Wiring illustrations on Page 2 Once wiring and set up are complete re install cover and tighten the 2 screws using a Phillips screwdriver Mounting The sensor installs directly into any air duct with a minimum width diameter of 25 5 cm 10 Select a suitable installation area in the...

Страница 2: ...SHLD terminal on each device If the device is installed at either end of the network an end of line EOL termination resistor 121 ohm should be installed in parallel to the A and B terminals This device includes a network termination jumper and will connect the resistor correctly on the pcb Simply move the pcb jumper to the EOL position and no external resistor is required as shown in Figure 7 The ...

Страница 3: ...to ModBus Protocol This section describes the implementation of the ModBus protocol It is intended to assist control system programmers who may need to add support to their systems to communicate with this device This device communicates on standard ModBus networks using RTU mode transmission It operates as a slave device address from 1 to 255 and expects a ModBus master device to transmit queries...

Страница 4: ...ion Codes 0x03 Read holding registers Query Slave address 0x01 to 0xFF Function code 0x03 Starting address MSB Starting address LSB Quantity of registers MSB Quantity of registers LSB CRC LSB CRC MSB Starting address 0x0000 to 0xFFFF Quantity of registers 0x0000 to 0x007D Response Slave address 0x01 to 0xFF Function code 0x03 Byte count 2N Register value MSB Register value LSB CRC LSB CRC MSB N Qu...

Страница 5: ...01 CRC LSB CRC MSB Response Slave address 0x01 to 0xFF 0x03 0x02 Register value MSB Register value LSB CRC LSB CRC MSB Register value 0x0000 to 0x03E8 corresponding to 0 to 100 RH multiplier 10 This register has a multiplier of 10 the application must divide by 10 to obtain the correct value 0x06 Write TEMPERATURE_OFFSET Query Slave address 0x01 to 0xFF 0x06 0x00 0x02 Register Value MSB Register v...

Страница 6: ...o conform to a local reference Register value 0xFFF6 to 0x000A for 10 to 10 corresponding to RH_OFFSET 10 to 10 RH ie 0x0003 3 3 RH offset 0x06 Write TEMPERATURE_UNITS Query Slave address 0x01 to 0xFF 0x06 0x00 0x04 0x00 Register value LSB CRC LSB CRC MSB Response Slave address 0x01 to 0xFF 0x06 0x00 0x04 0x00 Register value LSB CRC LSB CRC MSB Register value 0x0000 sets the device to C operation ...

Страница 7: ...me 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years Temperature Sensor 20KΩ NTC thermistor Accuracy 0 2 C 0 4 F curve matched Range 40 50 C 40 122 F Resolution 0 1 C F Interface Hardware 2 wire RS 485 Software Native ModBus MS TP protocol RTU Baud Rate 38400 Network Address Range Locally set to 1 255 Parity None Stop Bits 1 CRC A001 CRC 16 reverse GreystoneEnergySystems Inc 150EnglishD...

Отзывы: