COMMAND SET
TFT RESPONSE:
TFT Data:
Valid analog Data Range is + 000.0 to + 6550.
Values with (-) sign represent error messages
- 100.0 = “Not Ready Please Wait”
- 101.0 = “Signal Lost”
- 102.0 = “Sensor Short”
- 103.0 = N/A
- 104.0 = “Sensor Open”
- 105.0 = N/A
- 106.0 = N/A
- 107.0 = N/A
Units and mode: Always cm and Level.
Page 23
TFT32 Tank Farm Transmitter
Manual Series 2.4
COMMAND
DEFINITION
COMMAND MESSAGE
(Address 1)
TYPICAL RESPONSE
RA
Read all
parameters
#%1RA
<
CR
>
*%1RA+959.300XXX0AA
<
CR
>
RS
Read Span
(Max Level)
#%1RS
<
CR
>
*%1RS+999.900XXX0BF
<
CR
>
NBxx
New Baud Rate
xx = 00 = 38400
01 = 19200
02 = 9600
03 = 4800
04 = 2400
#%1NBxx
<
CR
>
(TFT will change to new
Baud Rate only after
reset)
*%1NB02
RR
Remote Reset
#%1RR
<
CR
>
*1RR
!RR
Broadcast Reset
#%!RR
<
CR
>
(All units in the Network
will reset)
(No Response)