INSERTION FLOW SENSOR
(OPTION ISE)
Insertion Depth: 1/8th pipe inside diameter plus 3/4" (20 mm).
Orientation: Screw head marks the active face and should point
upstream ±5°.
Average Flow Rate: Before permanent tightening of swage lock fitting,
the probe can be inserted to variable depths to determine the flow
profile. Theoretical average flow occurs at 1/8 pipe diameter.
Installation Procedure: Install a 1" NPT Female Nipple on the Pipe.
Insert probe. Tighten swage lock until it just grips the Probe - then
tighten 3/4 of a turn. Do not use above 100 psi.
HIGH TEMPERATURE SENSOR
(OPTION SE3H)
Mount with coupling compound and stainless steel pipe clamp
(supplied). Protect Sensor cable from contact with hot pipes.
SE3H Specifications:
Operating Temperature:
-40° to 302°F (-40° to 150°C)
Minimum Pipe Diameter:
0.5" (12.5 mm) ID, 0.6" (15 mm) OD
Maximum Pipe Diameter: 180" (4.5 m) O.D.
Operating Frequency:
640 KHz
Exposed Materials:
stainless steel with epoxy face
Sensor Cable:
20 ft (6 m) RG174U shielded coaxial pair
Page 31
DFM-IV Doppler Flow Meter
Manual Series A.6
MARKER
POINTS
UPSTREAM
ADJUSTABLE
SWAGE-LOCK
FITTING
1" NPT
20' (6 m) CONTINUOUS
SHIELDED COAXIAL PAIR
(50' / 15 m OPTIONAL)
316
STAINLESS
STEEL
PVC
6", 12" OR
SPECIAL
ORDER
STANDARD
50' (15 m) OPTIONAL
5/16" (8 mm) O.D.
HIGH TEMPERATURE
SENSOR MODEL SE3H
OVERALL LENGTH 13" (330 mm)