background image

Page 4

2. FITTING EQUIVALENT LENGTHS 

-  Flex pipe equivalent length is smooth 

pipe x2

-  Flex fitting equivalent length is 

smooth fitting x2

-  45º perimeter pipe elbow equivalent 

length = 5 ft. (1.52 m)

NOTE

: Where flex duct is used  

to make 45º elbow  

equivalent length =  

10 ft. (3.0 m)

-  Y-equal sides  

equivalent length = 10 ft. (3.0 m)

-  Y-Side branch  

equivalent length =  

35 ft. (10.7 m)

-  Round plastic diffuser  

equivalent length = 100 ft. (30.5 m)

 

NOTE:

 Maximum airflow assumes 

diffuser is in full open position. 

-  Tee take-off  

equivalent length =  

50 ft. (15.24 m)

-  Angle boot  

equivalent length = 30 ft. (9.14 m)

-  90º perimeter pipe elbow equivalent 

length = 10 ft. (3.0 m)

NOTE

: Where flex duct is used  

to make 90º elbow  

equivalent length = 20 ft. (6.1 m)

-  Round wall cap spring  

damper or screen  

equivalent lengths =  

60 ft. (18.29 m)

-  Wall grill 50% free area 

equivalent length = 15 ft.  (4.6 m)

- Increaser/Reducer  

equivalent length  

= 8 ft. (2.43 m)

Содержание RNC 1.0 HRV

Страница 1: ...C 2 0 HRV Item No 463125 RNC 2 0ES HRV Item No 463117 Product of Greentek Greentek reserves the rights to modify a product without prior notice whether in price design color or codes in order to offer...

Страница 2: ...icated Electric Receptacle 8 8 Outside Fresh Air and Stale Air Hoods 8 9 The matrix High Performance Ventilation Hood 9 10 Benefits of the Duotrol System 9 11 Balancing the unit 10 12 Controls Connect...

Страница 3: ...CFM L S CFM REQUIRED Master Bedroom x 20 cfm 10 L s With Basement x 20 cfm 10 L s Single Bedroom x 10 cfm 5 L s Living Room x 10 cfm 5 L s Dinning Room x 10 cfm 5 L s Family Room x 10 cfm 5 L s Recre...

Страница 4: ...t length 35 ft 10 7 m Round plastic diffuser equivalent length 100 ft 30 5 m NOTE Maximum airflow assumes diffuser is in full open position Tee take off equivalent length 50 ft 15 24 m Angle boot equi...

Страница 5: ...or the forced air system s manufacturer The HRV and forced air system must be in continuous mode to achieve maximum comfort and to avoid cross contamination NOTE TO INSTALLER Dwellings with multiple...

Страница 6: ...tems requires one HRV ERV per system Insure the unit runs in conjunction with forced air system Ref wiring diagram for furnace interlock For minimum distance between return and forced air system check...

Страница 7: ...and seal with a Tie wrap figure 5 2 Insert insulation inside the double collar figure 5 3 Finish by taping the vapor barrier to the collar to insure proper seal Once insulated flex is attached to the...

Страница 8: ...icated receptacle with 115v It is not recommended to connect unit with an extension cord If no receptacle is available please call an electrical contractor and have one installed Insure polarized is c...

Страница 9: ...outside AIRFLOW INSTALLATION IMPORTANT Install ventilation hood a minimum of 18 457mm above grade Do not install under a deck enclose porch patio garages crawl spaces or attics WARNING Insure the ven...

Страница 10: ...177 84 180 85 0 54 135 172 81 176 83 0 52 130 167 79 173 82 0 50 125 162 76 169 80 0 48 120 157 74 165 78 0 46 115 152 72 161 76 0 44 110 146 69 156 74 0 42 105 141 67 152 72 0 40 100 136 64 147 69 0...

Страница 11: ...the HIGH LOW balancing pressure taps on the fresh air side located on the HRV ERV access door Ref Fig 11 4 Adjust the fresh airflow integrated balancing damper adjustment screw clockwise until you re...

Страница 12: ...B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R COM NC NO B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R COM NC NO B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R...

Страница 13: ...Controller Y W R G Y W R G Thermostat B INTERLOCK COM N O N C RLY1 4 3 2 1 D1 SW3 TIMER REMOTE W B1 G R G B R MASTER PROG J2 C Y W R G B INTERLOCK COM N O N C RLY1 4 3 2 1 D1 SW3 TIMER REMOTE W B1 G...

Страница 14: ...ll bracket is used for hanging the units Verify that flexible duct connections are use between the HRV or ERV and the rigid duct Verify that the motors are operating and are not obscured by any debris...

Страница 15: ...it as required consult your owner s manual for instructions on inspecting and cleaning the core A build up of dust and dirt can restrict airflow and reduce the efficiency of your HRV ERV After inspect...

Страница 16: ...air LOW BAS LOW BAS LOW BAS LOW BAS HIGH HAUT HIGH HAUT HIGH HAUT HIGH HAUT Pressure Pression Fresh air Air frais Stale air Air vici IN W G Pascal CFM L s CFM L s PO d eau Pa PCM PCM 0 50 125 161 76...

Отзывы: