background image

Page 8

6. CONDENSATION DRAIN LINE

7. DEDICATED ELECTRIC RECEPTACLE

Insert the threaded drain adapter thru the 

bottom of the HRV/ERV and hand tighten 

the plastic nut, and with a wrench tighten 

the nut another half turn to assure a 

better seal.
Install the condensate line. Insert 

condensate tubing by pushing clear 

plastic line over drain adapter. Make 

condensate trap by looping the clear 

plastic tubing. This procedure is to 

avoid foul odor to enter the HRV or ERV.

IMPORTANT: 

Always consult a certified 

technician to insure proper installation 

of main power.

Note:

 If LED light on the Duotrol 

remains green, motors not energized 

controls do not operate. Polarization in 

main AC outlet are inverted.
It is recommended that the HRV/ERV 

have a dedicated receptacle with 120v. 

It is not recommended to connect unit 

with an extension cord.

figure 7.1

 Insert the power cord on top of the unit. Press 

firmly

 to make 

sure the power cord is secure.

figure 7.2

 It is recommended that the HRV or ERV have a dedicated 

receptacle with 115v. It is not recommended to connect unit with an 

extension cord.  If no receptacle is available please call an electrical 

contractor and have one installed. Insure polarized is correct

figure 6.1 Make a loop in condensate line, not be subject to  

freezing temperatures.

figure 6.2 Use a condensate pump if you don’t have access to a drain.

8. OUTSIDE FRESH AIR AND EXHAUST AIR HOODS

Tip to installer:

 We recommend and 

it is 

good practice

 to have a minimum 

of 6ft (1.83 m) between the supply 

and exhaust vents, unless using a 

concentric vent design to prevent 

contamination of intake air.
Always properly seal the supply & 

exhaust hoods to the exterior of the 

thermal envelope of the building with 

caulk or other similar material to inhibit 

air leakage.
Note: Outdoor air intake hoods shall 

be located to avoid contamination from 

sources such as:
• Exhaust air openings
• Driveways (auto exhaust)
• Combustion appliances
• Gas meters, oil fill pipes
• Garbage containers
• Attics or crawl spaces
• Under deck or other areas of 

questionable air quality

figure 8.1

 Locating Outside Hoods

6ft (1.83 m)

18" (457 mm)

IMPORTANT:

 Always consult your national and 

local regulations, building and safety codes.

Содержание RNC 1.0 HRV

Страница 1: ...C 2 0 HRV Item No 463125 RNC 2 0ES HRV Item No 463117 Product of Greentek Greentek reserves the rights to modify a product without prior notice whether in price design color or codes in order to offer...

Страница 2: ...icated Electric Receptacle 8 8 Outside Fresh Air and Stale Air Hoods 8 9 The matrix High Performance Ventilation Hood 9 10 Benefits of the Duotrol System 9 11 Balancing the unit 10 12 Controls Connect...

Страница 3: ...CFM L S CFM REQUIRED Master Bedroom x 20 cfm 10 L s With Basement x 20 cfm 10 L s Single Bedroom x 10 cfm 5 L s Living Room x 10 cfm 5 L s Dinning Room x 10 cfm 5 L s Family Room x 10 cfm 5 L s Recre...

Страница 4: ...t length 35 ft 10 7 m Round plastic diffuser equivalent length 100 ft 30 5 m NOTE Maximum airflow assumes diffuser is in full open position Tee take off equivalent length 50 ft 15 24 m Angle boot equi...

Страница 5: ...or the forced air system s manufacturer The HRV and forced air system must be in continuous mode to achieve maximum comfort and to avoid cross contamination NOTE TO INSTALLER Dwellings with multiple...

Страница 6: ...tems requires one HRV ERV per system Insure the unit runs in conjunction with forced air system Ref wiring diagram for furnace interlock For minimum distance between return and forced air system check...

Страница 7: ...and seal with a Tie wrap figure 5 2 Insert insulation inside the double collar figure 5 3 Finish by taping the vapor barrier to the collar to insure proper seal Once insulated flex is attached to the...

Страница 8: ...icated receptacle with 115v It is not recommended to connect unit with an extension cord If no receptacle is available please call an electrical contractor and have one installed Insure polarized is c...

Страница 9: ...outside AIRFLOW INSTALLATION IMPORTANT Install ventilation hood a minimum of 18 457mm above grade Do not install under a deck enclose porch patio garages crawl spaces or attics WARNING Insure the ven...

Страница 10: ...177 84 180 85 0 54 135 172 81 176 83 0 52 130 167 79 173 82 0 50 125 162 76 169 80 0 48 120 157 74 165 78 0 46 115 152 72 161 76 0 44 110 146 69 156 74 0 42 105 141 67 152 72 0 40 100 136 64 147 69 0...

Страница 11: ...the HIGH LOW balancing pressure taps on the fresh air side located on the HRV ERV access door Ref Fig 11 4 Adjust the fresh airflow integrated balancing damper adjustment screw clockwise until you re...

Страница 12: ...B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R COM NC NO B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R COM NC NO B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R...

Страница 13: ...Controller Y W R G Y W R G Thermostat B INTERLOCK COM N O N C RLY1 4 3 2 1 D1 SW3 TIMER REMOTE W B1 G R G B R MASTER PROG J2 C Y W R G B INTERLOCK COM N O N C RLY1 4 3 2 1 D1 SW3 TIMER REMOTE W B1 G...

Страница 14: ...ll bracket is used for hanging the units Verify that flexible duct connections are use between the HRV or ERV and the rigid duct Verify that the motors are operating and are not obscured by any debris...

Страница 15: ...it as required consult your owner s manual for instructions on inspecting and cleaning the core A build up of dust and dirt can restrict airflow and reduce the efficiency of your HRV ERV After inspect...

Страница 16: ...air LOW BAS LOW BAS LOW BAS LOW BAS HIGH HAUT HIGH HAUT HIGH HAUT HIGH HAUT Pressure Pression Fresh air Air frais Stale air Air vici IN W G Pascal CFM L s CFM L s PO d eau Pa PCM PCM 0 50 125 161 76...

Отзывы: