background image

Page 11

11. BALANCING THE UNIT 

(RNC 1.0 & RNC12 ONLY)

TOOLS REQUIRED TO 

BALANCE THE HRV/ERV

• A Magnehelic gauge capable of 

measuring 0 to 2.0 inch of water  

(0 to 500 Pa) and two (2)  

plastic hoses.

• A balancing reference chart located 

on the HRV/ERV access door panel.

CONSIDERATION WHEN 

BALANCING THE HRV/ERV

• Seal all the unit ductwork with tape. 

Close all windows and doors.

•  Insure all exhaust devices such as range 

hood, dryer and bathroom fans are off.

• That the integrated balancing 

dampers located in the collars are 

fully open.(Fresh Air damper ref Fig. 

11.5, Stale Air damper ref Fig. 11.6)

•  Make sure that all filters are clean 

and that there is no obstruction in 

ductwork 

•  Make sure that the forced air system 

blower is “ON” when connected to an 

existing forced air system ductwork. 

•  If it is a direct duct system installation 

ensure forced air system blower  

is “OFF”.

 

IMPORTANT:

 Insure the HRV/ERV has 

completed the defrost sequence. That 

the dehumidistat is deactivated by 

turning the round dial to the “OFF” 

position, the Range is” NORMAL”, the 

mode is “CONT” and the Cycle per Hour 

is set at “0/0”. 

NOTE: 

The unit is considered balanced 

even if there is a difference of ±10 cfm 

(or ± 5 l/s or 17 m³/h) between the two 

air flows

Note to installer:

 For installation 

purposes, the RNC 1.0 & RNC12 are 

designed with pre-determined airflow 

speed values that are stored in memory. 

The RNC 1.0 & RNC12 platform are 

designed and can be equipped with the 

Duotrol™ speed & balancing control 

system kit. (Item: 102801) This factory 

option must be present to control the 

motors independently, when more 

accurate airflow settings are required 

or for testing purposes. Please contact 

Greentek at 1-888-724-5211  

for further instructions/information  

on this process.

BALANCING PROCEDURES WITH INTEGRATED DAMPERS

Step 1:

 Place the Magnehelic gauge on a level surface and 

adjust the needle to zero.

Step 2:

 Connect the two (2) plastic hoses to the gauge on 

the HIGH & LOW pressure connections.

Step 3:

 Once the total ventilation requirements are 

determined, you can start balancing the HRV/ERV. 

(Refer to 1. Ventilation Requirements)

Step 4:

 Remove the four (4) nylon knock out seals located 

on the HRV/ERV access door. (

Ref Fig 11.3

)

Fig 11.3

Fresh

Air

Stale

Air

Remove all four (4)

nylon knock out seals.

Do not discard.

screw

Front

Stale

Air

HIGH

HIGH

HIGH

HIGH

LOW

LOW

LOW

LOW

screw

Front

Fresh

Air

Air Vicié

Air frais

Enlever les quatre 

(4) bouchons 

à défoncer de nylon.

Ne pas les jeter.

HAUT

HAUT

BAS

BAS

HAUT

HAUT

BAS

BAS

Vis d'adjustement

Devant

Air

vicié

Vis d'adjustement

Devant

Air

frais

 Pressure / Pression 

Fresh air / Air frais 

Stale air / Air vicié 

  IN. W.G. Pascal   

CFM 

L/s 

 

CFM 

L/s

 PO. d’eau 

(Pa) 

PCM 

 

PCM

  0.50 

125 

161 

76

  0.53 

132 

159 

75

  0.56 

139 

156 

74

  0.59 

147 

153 

72

  0.62 

154 

149 

70

  0.65 

162 

146 

69

  0.68 

169 

142 

67

  0.71 

177 

138 

65

  0.74 

184 

149 

70 

133 

63

  0.77 

192 

147 

69 

129 

61

  0.80 

199 

144 

68 

124 

59

  0.83 

207 

141 

67 

119 

56

  0.86 

214 

138 

65 

114 

54

  0.89 

222 

133 

63 

109 

51

  0.92 

229 

128 

60 

103 

49

  0.95 

237 

123 

58 

97 

46

  0.98 

244 

116 

55 

91 

43

  1.01 

252 

109 

51 

85 

40

  1.04 

259 

101 

48 

78 

37

  1.07 

267 

93 

44 

71 

34

  1.10 

274 

84 

40 

64 

30

  1.13 

281 

74 

35 

57 

27

  1.16 

289 

64 

30 

50 

24

  1.19 

296 

53 

25 

42 

20

  1.22 

304 

41 

19 

34 

16

  1.25 

311 

29 

14 

26 

12

Step 5:

 Connect the two (2) plastic hoses from the gauge  

to the HIGH & LOW balancing pressure taps on the fresh  

or stale air side located on the HRV/ERV access door  

(

Ref Fig 11.4

)

Fig 11.4

Fresh

Air

Stale

Air

Remove all four (4)

nylon knock out seals.

Do not discard.

screw

Front

Stale

Air

HIGH

HIGH

HIGH

HIGH

LOW

LOW

LOW

LOW

screw

Front

Fresh

Air

Air Vicié

Air frais

Enlever les quatre 

(4) bouchons 

à défoncer de nylon.

Ne pas les jeter.

HAUT

HAUT

BAS

BAS

HAUT

HAUT

BAS

BAS

Vis d'adjustement

Devant

Air

vicié

Vis d'adjustement

Devant

Air

frais

 Pressure / Pression 

Fresh air / Air frais 

Stale air / Air vicié 

  IN. W.G. Pascal   

CFM 

L/s 

 

CFM 

L/s

 PO. d’eau 

(Pa) 

PCM 

 

PCM

  0.50 

125 

161 

76

  0.53 

132 

159 

75

  0.56 

139 

156 

74

  0.59 

147 

153 

72

  0.62 

154 

149 

70

  0.65 

162 

146 

69

  0.68 

169 

142 

67

  0.71 

177 

138 

65

  0.74 

184 

149 

70 

133 

63

  0.77 

192 

147 

69 

129 

61

  0.80 

199 

144 

68 

124 

59

  0.83 

207 

141 

67 

119 

56

  0.86 

214 

138 

65 

114 

54

  0.89 

222 

133 

63 

109 

51

  0.92 

229 

128 

60 

103 

49

  0.95 

237 

123 

58 

97 

46

  0.98 

244 

116 

55 

91 

43

  1.01 

252 

109 

51 

85 

40

  1.04 

259 

101 

48 

78 

37

  1.07 

267 

93 

44 

71 

34

  1.10 

274 

84 

40 

64 

30

  1.13 

281 

74 

35 

57 

27

  1.16 

289 

64 

30 

50 

24

  1.19 

296 

53 

25 

42 

20

  1.22 

304 

41 

19 

34 

16

  1.25 

311 

29 

14 

26 

12

Step 6:

 Set the unit on high speed by connecting the Vectra 

EHC-1.0 controller to the HRV/ERV, power “ON” and select 

the 20MIN/HR operating mode by pressing the “PREF” 

button on the Vectra EHC 1.0 control.                                                           

ATTENTION: 

If there is no control present on the RNC 1.0, 

will automatically run on a continuous high speed operating 

mode.

Step 7:

 To adjust the 

(fresh air)

, ensure the plastic hoses 

from the gauge are connected to the HIGH & LOW balancing 

pressure taps on the fresh air side located on the HRV/ERV 

access door. (

Ref Fig 11.4

). Adjust the fresh airflow integrated 

balancing damper adjustment screw clockwise until you 

reach the calculated fresh airflow requirements. (

Ref Fig 

11.5

).

Fig 11.5 

Fresh

Air

Stale

Air

Remove all four (4)

nylon knock out seals.

Do not discard.

screw

Front

Stale

Air

HIGH

HIGH

HIGH

HIGH

LOW

LOW

LOW

LOW

screw

Front

Fresh

Air

Air Vicié

Air frais

Enlever les quatre 

(4) bouchons 

à défoncer de nylon.

Ne pas les jeter.

HAUT

HAUT

BAS

BAS

HAUT

HAUT

BAS

BAS

Vis d'adjustement

Devant

Air

vicié

Vis d'adjustement

Devant

Air

frais

 Pressure / Pression 

Fresh air / Air frais 

Stale air / Air vicié 

  IN. W.G. Pascal   

CFM 

L/s 

 

CFM 

L/s

 PO. d’eau 

(Pa) 

PCM 

 

PCM

  0.50 

125 

161 

76

  0.53 

132 

159 

75

  0.56 

139 

156 

74

  0.59 

147 

153 

72

  0.62 

154 

149 

70

  0.65 

162 

146 

69

  0.68 

169 

142 

67

  0.71 

177 

138 

65

  0.74 

184 

149 

70 

133 

63

  0.77 

192 

147 

69 

129 

61

  0.80 

199 

144 

68 

124 

59

  0.83 

207 

141 

67 

119 

56

  0.86 

214 

138 

65 

114 

54

  0.89 

222 

133 

63 

109 

51

  0.92 

229 

128 

60 

103 

49

  0.95 

237 

123 

58 

97 

46

  0.98 

244 

116 

55 

91 

43

  1.01 

252 

109 

51 

85 

40

  1.04 

259 

101 

48 

78 

37

  1.07 

267 

93 

44 

71 

34

  1.10 

274 

84 

40 

64 

30

  1.13 

281 

74 

35 

57 

27

  1.16 

289 

64 

30 

50 

24

  1.19 

296 

53 

25 

42 

20

  1.22 

304 

41 

19 

34 

16

  1.25 

311 

29 

14 

26 

12

Fresh

Air

Stale

Air

Remove all four (4)

nylon knock out seals.

Do not discard.

screw

Front

Stale

Air

HIGH

HIGH

HIGH

HIGH

LOW

LOW

LOW

LOW

screw

Front

Fresh

Air

Air Vicié

Air frais

Enlever les quatre 

(4) bouchons 

à défoncer de nylon.

Ne pas les jeter.

HAUT

HAUT

BAS

BAS

HAUT

HAUT

BAS

BAS

Vis d'adjustement

Devant

Air

vicié

Vis d'adjustement

Devant

Air

frais

 Pressure / Pression 

Fresh air / Air frais 

Stale air / Air vicié 

  IN. W.G. Pascal   

CFM 

L/s 

 

CFM 

L/s

 PO. d’eau 

(Pa) 

PCM 

 

PCM

  0.50 

125 

161 

76

  0.53 

132 

159 

75

  0.56 

139 

156 

74

  0.59 

147 

153 

72

  0.62 

154 

149 

70

  0.65 

162 

146 

69

  0.68 

169 

142 

67

  0.71 

177 

138 

65

  0.74 

184 

149 

70 

133 

63

  0.77 

192 

147 

69 

129 

61

  0.80 

199 

144 

68 

124 

59

  0.83 

207 

141 

67 

119 

56

  0.86 

214 

138 

65 

114 

54

  0.89 

222 

133 

63 

109 

51

  0.92 

229 

128 

60 

103 

49

  0.95 

237 

123 

58 

97 

46

  0.98 

244 

116 

55 

91 

43

  1.01 

252 

109 

51 

85 

40

  1.04 

259 

101 

48 

78 

37

  1.07 

267 

93 

44 

71 

34

  1.10 

274 

84 

40 

64 

30

  1.13 

281 

74 

35 

57 

27

  1.16 

289 

64 

30 

50 

24

  1.19 

296 

53 

25 

42 

20

  1.22 

304 

41 

19 

34 

16

  1.25 

311 

29 

14 

26 

12

Step 8:

 To adjust the 

(stale air)

, ensure the plastic hoses 

from the gauge are connected to the HIGH & LOW balancing 

pressure taps on the stale air side located on the HRV/ERV 

access door. (

Ref Fig 11.4

). Adjust the stale airflow integrated 

balancing adjustment screw until you reach the calculated 

stale airflow requirements. (

Ref Fig 11.6

).

Fig 11.6

Fresh

Air

Stale

Air

Remove all four (4)

nylon knock out seals.

Do not discard.

screw

Front

Stale

Air

HIGH

HIGH

HIGH

HIGH

LOW

LOW

LOW

LOW

screw

Front

Fresh

Air

Air Vicié

Air frais

Enlever les quatre 

(4) bouchons 

à défoncer de nylon.

Ne pas les jeter.

HAUT

HAUT

BAS

BAS

HAUT

HAUT

BAS

BAS

Vis d'adjustement

Devant

Air

vicié

Vis d'adjustement

Devant

Air

frais

 Pressure / Pression 

Fresh air / Air frais 

Stale air / Air vicié 

  IN. W.G. Pascal   

CFM 

L/s 

 

CFM 

L/s

 PO. d’eau 

(Pa) 

PCM 

 

PCM

  0.50 

125 

161 

76

  0.53 

132 

159 

75

  0.56 

139 

156 

74

  0.59 

147 

153 

72

  0.62 

154 

149 

70

  0.65 

162 

146 

69

  0.68 

169 

142 

67

  0.71 

177 

138 

65

  0.74 

184 

149 

70 

133 

63

  0.77 

192 

147 

69 

129 

61

  0.80 

199 

144 

68 

124 

59

  0.83 

207 

141 

67 

119 

56

  0.86 

214 

138 

65 

114 

54

  0.89 

222 

133 

63 

109 

51

  0.92 

229 

128 

60 

103 

49

  0.95 

237 

123 

58 

97 

46

  0.98 

244 

116 

55 

91 

43

  1.01 

252 

109 

51 

85 

40

  1.04 

259 

101 

48 

78 

37

  1.07 

267 

93 

44 

71 

34

  1.10 

274 

84 

40 

64 

30

  1.13 

281 

74 

35 

57 

27

  1.16 

289 

64 

30 

50 

24

  1.19 

296 

53 

25 

42 

20

  1.22 

304 

41 

19 

34 

16

  1.25 

311 

29 

14 

26 

12

 

Fresh

Air

Stale

Air

Remove all four (4)

nylon knock out seals.

Do not discard.

screw

Front

Stale

Air

HIGH

HIGH

HIGH

HIGH

LOW

LOW

LOW

LOW

screw

Front

Fresh

Air

Air Vicié

Air frais

Enlever les quatre 

(4) bouchons 

à défoncer de nylon.

Ne pas les jeter.

HAUT

HAUT

BAS

BAS

HAUT

HAUT

BAS

BAS

Vis d'adjustement

Devant

Air

vicié

Vis d'adjustement

Devant

Air

frais

 Pressure / Pression 

Fresh air / Air frais 

Stale air / Air vicié 

  IN. W.G. Pascal   

CFM 

L/s 

 

CFM 

L/s

 PO. d’eau 

(Pa) 

PCM 

 

PCM

  0.50 

125 

161 

76

  0.53 

132 

159 

75

  0.56 

139 

156 

74

  0.59 

147 

153 

72

  0.62 

154 

149 

70

  0.65 

162 

146 

69

  0.68 

169 

142 

67

  0.71 

177 

138 

65

  0.74 

184 

149 

70 

133 

63

  0.77 

192 

147 

69 

129 

61

  0.80 

199 

144 

68 

124 

59

  0.83 

207 

141 

67 

119 

56

  0.86 

214 

138 

65 

114 

54

  0.89 

222 

133 

63 

109 

51

  0.92 

229 

128 

60 

103 

49

  0.95 

237 

123 

58 

97 

46

  0.98 

244 

116 

55 

91 

43

  1.01 

252 

109 

51 

85 

40

  1.04 

259 

101 

48 

78 

37

  1.07 

267 

93 

44 

71 

34

  1.10 

274 

84 

40 

64 

30

  1.13 

281 

74 

35 

57 

27

  1.16 

289 

64 

30 

50 

24

  1.19 

296 

53 

25 

42 

20

  1.22 

304 

41 

19 

34 

16

  1.25 

311 

29 

14 

26 

12

Step 9:

 Seal the four (4) balancing pressure taps  

with the nylon knock out seals removed in Step 4.

Step 10:

 Mark down the balanced air flow rates information 

on a label including in the kit. Apply the label to the HRV/ERV 

access door for future reference (e.g. date, balance airflow 

rate, your name, phone number and business address).

For Balancing Charts,

- Refer to page 16 of this manual
- Visit www.greentek.ca
- Scan QR code with your smartphone

 

RNC 1.0 

Balancing Chart

RNC12 

Balancing Chart 

NOTE:

 Turning the 

damper adjustment 

screw clockwise 

will reduce the 

airflow, turning 

counterclockwise will 

increase the airflow

NOTE:

 Turning the 

damper adjustment 

screw clockwise 

will reduce the 

airflow, turning 

counterclockwise will 

increase the airflow

Содержание RNC 1.0 HRV

Страница 1: ...C 2 0 HRV Item No 463125 RNC 2 0ES HRV Item No 463117 Product of Greentek Greentek reserves the rights to modify a product without prior notice whether in price design color or codes in order to offer...

Страница 2: ...icated Electric Receptacle 8 8 Outside Fresh Air and Stale Air Hoods 8 9 The matrix High Performance Ventilation Hood 9 10 Benefits of the Duotrol System 9 11 Balancing the unit 10 12 Controls Connect...

Страница 3: ...CFM L S CFM REQUIRED Master Bedroom x 20 cfm 10 L s With Basement x 20 cfm 10 L s Single Bedroom x 10 cfm 5 L s Living Room x 10 cfm 5 L s Dinning Room x 10 cfm 5 L s Family Room x 10 cfm 5 L s Recre...

Страница 4: ...t length 35 ft 10 7 m Round plastic diffuser equivalent length 100 ft 30 5 m NOTE Maximum airflow assumes diffuser is in full open position Tee take off equivalent length 50 ft 15 24 m Angle boot equi...

Страница 5: ...or the forced air system s manufacturer The HRV and forced air system must be in continuous mode to achieve maximum comfort and to avoid cross contamination NOTE TO INSTALLER Dwellings with multiple...

Страница 6: ...tems requires one HRV ERV per system Insure the unit runs in conjunction with forced air system Ref wiring diagram for furnace interlock For minimum distance between return and forced air system check...

Страница 7: ...and seal with a Tie wrap figure 5 2 Insert insulation inside the double collar figure 5 3 Finish by taping the vapor barrier to the collar to insure proper seal Once insulated flex is attached to the...

Страница 8: ...icated receptacle with 115v It is not recommended to connect unit with an extension cord If no receptacle is available please call an electrical contractor and have one installed Insure polarized is c...

Страница 9: ...outside AIRFLOW INSTALLATION IMPORTANT Install ventilation hood a minimum of 18 457mm above grade Do not install under a deck enclose porch patio garages crawl spaces or attics WARNING Insure the ven...

Страница 10: ...177 84 180 85 0 54 135 172 81 176 83 0 52 130 167 79 173 82 0 50 125 162 76 169 80 0 48 120 157 74 165 78 0 46 115 152 72 161 76 0 44 110 146 69 156 74 0 42 105 141 67 152 72 0 40 100 136 64 147 69 0...

Страница 11: ...the HIGH LOW balancing pressure taps on the fresh air side located on the HRV ERV access door Ref Fig 11 4 Adjust the fresh airflow integrated balancing damper adjustment screw clockwise until you re...

Страница 12: ...B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R COM NC NO B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R COM NC NO B G INTERLOCK TIMER MINUTERIE R B B1 W G CONTROL COMMANDE R...

Страница 13: ...Controller Y W R G Y W R G Thermostat B INTERLOCK COM N O N C RLY1 4 3 2 1 D1 SW3 TIMER REMOTE W B1 G R G B R MASTER PROG J2 C Y W R G B INTERLOCK COM N O N C RLY1 4 3 2 1 D1 SW3 TIMER REMOTE W B1 G...

Страница 14: ...ll bracket is used for hanging the units Verify that flexible duct connections are use between the HRV or ERV and the rigid duct Verify that the motors are operating and are not obscured by any debris...

Страница 15: ...it as required consult your owner s manual for instructions on inspecting and cleaning the core A build up of dust and dirt can restrict airflow and reduce the efficiency of your HRV ERV After inspect...

Страница 16: ...air LOW BAS LOW BAS LOW BAS LOW BAS HIGH HAUT HIGH HAUT HIGH HAUT HIGH HAUT Pressure Pression Fresh air Air frais Stale air Air vici IN W G Pascal CFM L s CFM L s PO d eau Pa PCM PCM 0 50 125 161 76...

Отзывы: