Duct to Sleeve Connection

Sleeve Gauge and Connection Type Requirements

Sleeve Gauge

Duct Dimension

Type of Duct to Sleeve 

Connection Permitted

14 ga. (0.075 in.) - 

10 ga. (0.138 in.)
[2 mm - 3.5 mm]

All duct sizes

Rigid or 

Breakaway

16 ga. (0.060 in.)

[1.5 mm]

36 in. (914 mm) max. width

24 in. (610 mm) max. height

24 in. (610 mm) diameter

Rigid or Breakaway

16 ga. (0.060 in.)

[1.5 mm]

All duct sizes

Breakaway only

18 ga. (0.048 in.)

[1.2 mm]

85 in. (2159 mm) wide and 

over

20 ga. (0.036 in.)

[0.9 mm]

55 in. - 84 in. wide

(1397 mm - 2134 mm)

22 ga. (.030 in.)

[0.76 mm]

31 in. - 54 in. wide

(787 mm - 1372 mm)

24 ga. (0.024)

[0.6 mm]

13 in. - 30 in. wide

(330 mm - 762 mm)

26 ga. (0.018 in.)

[0.46 mm]

12 in. wide and under

(305 mm)

See Breakaway Connection section for additional information.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.

The size of the damper/duct determines the required sleeve gauge and the required duct to sleeve connection (see 
table to the right). The sleeve thickness must also not be less than the gauge of the connecting duct. Any duct 
connection other than the breakaway connections described below are considered rigid.

Out of Wall Fire and Combination Fire Smoke Dampers

7

®

Содержание ODFD Series

Страница 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Страница 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Страница 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Страница 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Страница 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Страница 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Страница 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Страница 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Страница 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Страница 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Страница 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Страница 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...

Отзывы: