background image

Securing the Damper/Sleeve Assembly to Wall/Floor Openings

Damper/sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated 
and described below.
  •  Flange on front (grille end) of sleeve must be a minimum of 16 ga. (1.5 mm) steel and have 

5

8

 in.(16 mm) 

minimum flange leg (refer to 

Figure 8

). Using #10 (19 mm) sheet metal screws, screw from inside of sleeve 

through the rear portion of the studs (as shown in 

Figures 3 & 4

). Space screws a maximum of 6 in. (152 mm) 

O.C. and a maximum of 2 in. (51 mm) from the corners (minimum of 2 screws per side). No retaining angles are 
required on the side of the wall opposite from the grille.

  •  Retaining angles for 1

1

2

 hour rated dampers with a width 48 in. (1219 mm) or less must be a minimum of 20 ga. 

(1 mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1

1

4

 in. (32 mm). The leg of 

the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor 
by a minimum of 1 in. (25 mm). See 

Figure 9

.

  •  Retaining angles must be attached to the damper using one or more of the following methods of attachment:
    - Tack or spot welds
    -  #10 (

3

4

 in. [19 mm] max.) sheet metal screws

   - 

1

4

 in. (6 mm) bolts and nuts

   - 

3

16

 in. (5 mm) steel pop rivets

Attachments must be spaced a maximum of 6 in. (152 mm) on center and a maximum of 2 in. (51 mm) from corners. 
The angles must be attached to all four sides of the sleeve. A minimum of two attachments are required on each 
side, top and bottom. The angles need not be attached to each other at the corners.

Caution! Do not tear the thermal blanket during installation.

Horizontal mount: thermal
blanket (installed around
entire outside surface
of sleeve)
Vertical mount: thermal
blanket (installed around
only on the top and sides)

 

Wall

Flange

Figure 8: Sleeved Damper with Thermal Blanket (duct 

termination)

Retaining Angle

2 in. Max.

6 in. Max.

6 in. Max.

2 in. Max.

Wall

Horizontal mount: thermal
blanket (installed around
entire outside surface
of sleeve)
Vertical mount: thermal
blanket (installed around
only on the top and sides)

Figure 9: Sleeved Damper with Thermal Blanket (duct 

continuation).

Out of Wall Fire and Combination Fire Smoke Dampers

6

®

Содержание ODFD Series

Страница 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Страница 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Страница 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Страница 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Страница 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Страница 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Страница 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Страница 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Страница 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Страница 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Страница 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Страница 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...

Отзывы: