background image

General Information

Electrical Guidelines

“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 

(see complete marking on product)”
 

Standard 555 & 555S (Listing #R13317)

The following items will aid in completing the damper 
installation in a timely and effective manner.
1)  Check the drawings for proper damper locations 

within the building. Visually inspect the damper for 
damage and verify that the Reusable Resettable Link 
(RRL) is in place and has not activated if provided. 
These electric links have a button for resetting. 
Visually inspect the fusible link (if provided) to verify 
its not missing or broken. Replace link as necessary.

2)  Lift or handle damper using sleeve or frame. Do not 

lift damper using blades or actuators.

3)  Damper must be installed into duct or opening 

square and free of twist or other misalignment. Out 
of square, racked, twisted or misaligned installations 
can cause excessive leakage and/or torque 
requirements to exceed damper/actuator design.

4)  Damper and actuator must be kept clean and 

protected from dirt, dust and other foreign materials 
prior to and after installation. Examples of such 
foreign materials include but are not limited to: 
  a) Mortar dust 
  b) Drywall dust 
  c) Firesafing materials 
  d) Wall texture 
  e) Paint overspray

5)  Damper should be sufficiently covered as to prevent 

overspray if wall texturing or spray painting will be 
performed within 5 feet of the damper. Excessive 
dirt or foreign material deposits on the damper can 
cause excessive leakage and/or torque requirements 
to exceed damper/actuator design.

6)  Caulking is not necessary, nor is it allowed, between 

the damper sleeve and the wall or floor opening 
(annular space). However, caulking may be applied 
to the retaining angles.

7)  ACCESS: Suitable access (such that RRL’s and 

actuators can be maintained, etc.) must be provided 
for damper inspection and servicing. Where it is not 
possible to achieve sufficient size access, it will be 
necessary to install a removable section of duct. 
(Refer to NFPA 90A).

8)  The Code Authority Having Jurisdiction (AHJ) must 

evaluate and provide approval of final installation 
where variations to these instructions are necessary.

Pre-Installation Guidelines

Installation Supplements

Refer to the appropriate Greenheck installation 
supplements for special requirements 
(www.greenheck.com links are underline):
 • 

Fire Resistant Ventilated Duct Assembly

 

• 

Fusible Link Replacement

 

• 

Greenheck Test Switch

 

• 

Metal Stud in Shaftwall Partition

 

• 

Open or Close Indicator (OCI)

 

• 

Resettable Link (RRL)

 

• 

Resettable Link with Blade Indicator (RRL/OCI)

 

• Smoke Detector - Various Types 
• 

Temperature Limited Override (TOR)

Online version to this installation instructions at 
www.greenheck.com.

Electrical Guidelines

All wiring shall be done in accordance with the 
National Electrical Code ANSI/NFPA-70 latest edition, 
any local codes that may apply, and wiring diagrams 
developed in compliance with the job or project 
design and specifications

Important!

Electrical input may be needed for this equipment. 
This work should be performed by a qualified 
electrician. Verify power before wiring actuator. 
Greenheck is not responsible for any damage to, or 
failure of the unit caused by incorrect field wiring. To 
avoid causing death or serious bodily harm to building 
occupants, follow all instructions carefully. Dampers 
must close completely to preserve the integrity of the 
fire smoke separation.

Out of Wall Fire and 
Combination Fire Smoke 
Dampers Instructions

Out of Wall Fire and Combination Fire Smoke Dampers

2

®

Содержание ODFD Series

Страница 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Страница 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Страница 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Страница 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Страница 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Страница 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Страница 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Страница 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Страница 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Страница 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Страница 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Страница 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...

Отзывы: