ALTAIR 120 H
ALTAIR 160 H

False ceiling mounting

EN

Содержание ALTAIR 160 H

Страница 1: ...ALTAIR 120 H ALTAIR 160 H False ceiling mounting EN...

Страница 2: ...or air ODA 4 Extract air ETA 5 Supply air SUP 6 G4 lter extract air 7 G4 lter outdoor air 8 Supply air fan 9 Exhaust air fan 10 Counter ow heat exchanger 11 Humidity sensor 12 Condensation water conne...

Страница 3: ...e chemical agents Means for disconnection must be incorporated in the xed wiring according with the wiring rules An external disconnecting device which will function as the designated disconnect devic...

Страница 4: ...ce the parts or the unit whose operation is recognized defective by our departments except for all damages and interests or penalties such as operating losses commercial prejudice or other immaterial...

Страница 5: ...densation Supply air SUP To avoid thermal losses and optimize the per formance of the installation it is recommended to use insulated duct Extract air ETA To avoid thermal losses and optimize perfor m...

Страница 6: ...D 94 mm 123 mm E 22 mm 22 mm F 660 mm 729 mm G 850 mm 970 mm H 30 mm 32 mm I 178 mm 211 mm J 91 mm 106 mm K 208 mm 231 mm A 104 80 26 52 60 17 blue DO D1 12V COM red green white L N L N 230V 50 60Hz...

Страница 7: ...lly insulated type GP ISO 125 25 6M ECOSOFT 5209346000 lateral view ALTAIR 120 H X 30 mm ALTAIR 160 H X 20 mm X Z Y Dim ALTAIR 120 H ALTAIR 160 H Y 874 mm 994 mm Z 516 mm 516 mm The drain pipe should...

Страница 8: ...d Potentiometer position 0 1 2 3 4 5 6 7 8 9 A B C D E F ALTAIR 120 H Assigned value m3 h 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 120 ALTAIR 160 H Assigned value m3 h 40 48 56 64 72 80 88 96 1...

Страница 9: ...change Of course after the installation the extract air is dusty and not representative During the second lter check if you notice that the lters are clean you can increase the time if you notice the...

Страница 10: ...to adjust the velocity in dependence of the relative humidity in the extract air The upper limit of the relative humidity can be adjusted with the potentiometer as shown below factory setting positio...

Страница 11: ...ou to con nect the ALTAIR unit with the S P IoT Platform CONNEC TAIR To connect the SPCM 1 module to the ALTAIR you must rst disconnect the control 14 and then connect the SPCM 1 with the cable suppli...

Страница 12: ...right fan symbol increase speed ORZ VSHHG PHGLXP VSHHG KLJK VSHHG Automatic mode Pressing the button A there can be activated the automatic mode In the automatic mode works the unit proportio nal in...

Страница 13: ...chan ging the lter put back the plastic taps Everytime when lters are replaced the lter main tenance period has to be reseted pressing the but ton A during 5 seconds 2 6 STANDBY FUNCTION Push and hold...

Страница 14: ...r 8 red blinks normal operation 7 ETA sensor error extract air 9 red blinks normal operation 8 EHA sensor error exhaust air 10 red blinks normal operation 9 Filter alarm Red continous after 60 days th...

Страница 15: ...nd power level LWA 47 48 k Reference ow rate m s 0 023 0 031 l Reference pressure difference Pa 50 0 96 m SPI W m h 0 262 0 222 n Control factor 0 85 0 85 Control typology Central demand Central deman...

Страница 16: ...S P SISTEMAS DE VENTILACI N S L U C Llevant 4 Pol gono Industrial Llevant 08150 Parets del Vall s Barcelona Espa a Tel 34 93 571 93 00 www solerpalau com Ref 9023110800 03...