Actuator and Temperature Response Device Connections

Actuator Connections

Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping 
diagrams developed in compliance with applicable codes, ordinances and regulations (see 

Electrical Guidelines

).

Temperature Response Device Connections

RRL:  

The RRL (resettable link device) incorporates a single thermostat. When the thermostat temperature is reached 
the sensor interrupts power to the actuator and the actuator's spring return mechanism causes the damper to 
close. Refer to 

Figure 17

 for wiring of the RRL thermostat.

OCI

:  The OCI (open or closed indicator) option contains two single pole single throw switches used to indicate the 

damper blade position. The switches provide a positive open and closed signal and can be used in conjunction 
with remote indicator lights. Refer to 

Figure 18 

for wiring of the OCI option.

RRL /OCI

:  The RRL/OCI performs the function of an RRL and OCI (see description above). Refer to 

Figure 19 

for 

wiring of the RRL/OCI option.

TOR

:  The TOR (temperature override device) option incorporates two thermostats with fixed settings (usually 

165°F [74°C] and 350°F [177°C]). The primary sensor (the sensor with the lower temperature setting) can be 
bypassed by an external contact closure allowing the damper to reopen until the secondary temperature is 
reached (the sensor with the higher temperature setting). See 

Figure 20.

 

 The TOR assembly contains two single pole single throw switches used to indicate damper blade position. 
The switches provide a positive open and closed signal and can be used in conjunction with remote indicator 
lights. See 

Figure 20

 for wiring of the TOR thermostats and indicator switches.

 

 If either the TOR or the RRL is ordered with a pneumatic actuator, an EP switch is required with an appropriate 
electric power circuit to allow the electric thermostat to control the pneumatic actuator.

Figure 19: RRL Wiring

Figure 20: OCI

Ratings (Figure 19, 20, 21, & 22)

Integral Switch Type:

 Single Pole, double throw

Electrical Capacity:

 10 Amps, 

1

3

 hp, 120 or 240 Vac 

 

 

1/2 Amp, 125 Vdc;  

 

 

1/4 Amp 250 Vdc 

 

 

5 Amps, 120 Vac “L” (lamp load) 

 

 

1.0 Amps, 24 Vac 

 

 

1.5 Amps, 24 Vdc

Temperature Limit: 165° F (standard primary sensor) 
 

 

212° F (optional primary sensor) 

 

 

250° F (secondary sensor )* 

 

 

350º F (secondary sensor)* 

* based on actuator temperature rating

Figure 21: RRL/OCI

Figure 22: 

TOR

Out of Wall Fire and Combination Fire Smoke Dampers

10

®

Содержание ODFD Series

Страница 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Страница 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Страница 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Страница 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Страница 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Страница 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Страница 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Страница 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Страница 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Страница 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Страница 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Страница 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...

Отзывы: