Unit Start-Up

Visual Inspection of Equipment

The equipment type and arrangement should be verified 
as ordered at once when it arrives at the job site. When 
a discrepancy is found, the local sales representative 
must be notified immediately so that corrective action 
may be investigated, also verify electrical conformance 
to specifications. Unauthorized alterations and 
unauthorized back charges will not be recognized by 
the manufacturer.

After the unit has been assembled, installed and all 
utilities have been hooked up, the unit is now ready for 
operation.

Check

Before starting the unit, check the following:

  1.  Confirm that building supply voltage matches the 

voltage for which the unit is wired.

  2.  Check all piping and wiring penetrations made by 

contractors for water tightness. All penetrations 
must be made watertight to prevent water damage 
to the unit and building.

  3.  Rotate the fan wheel manually to be sure that it is 

free to operate. Remove any dirt or debris that may 
have accumulated during installation.

  4.  Check the fan bearing setscrews for tightness.

  5.  Check alignment of sheaves and V-belts (See 

maintenance section).

  6.  Inspect all fasteners to ensure that none have 

loosened during shipment.

  7.  Check flex coupling for proper alignment and 

connect between motor shaft and fan shaft (direct 
drive).

  8.  Check all guarding to ensure that it is securely 

attached and not interfering with rotating parts.

  9.  Check all electrical connections for proper 

attachment.

 10.  Check housing and ductwork, if accessible, for 

obstructions and foreign material that may damage 
the fan wheel.

 11.  Fill drainage piping trap.

Additional Steps for Initial Start-Up

1.  Check for proper wheel rotation by momentarily 

energizing the fan. Access to view the wheel can be 
gained through the blower housing access panel.

 

One of the most frequently encountered problems 
are motors that are wired to rotate the wheel in the 
wrong direction. This is especially true with 3-phase 
installations where the motor will run in either 
direction, depending on how it has been wired. To 
reverse rotation of a 3-phase motor, interchange any 
two of the three electrical leads. Single phase motors 
can be reversed by changing internal connections as 
described on the motor label or wiring diagram. 

2.  Fans with multi-speed motors should be checked on 

low speed during initial start-up.

3.  Check for unusual noise, vibration or overheating of 

bearings. Refer to the “Troubleshooting” section of 
this manual if a problem develops.

4.  Grease may be forced out of the bearing seals during 

initial start-up. This is a normal self-purging feature 
for the type of bearing used on this product.

Vibration

On start-up and during operation, the unit should 
operate smoothly with minimal vibration. It is possible 
that a higher degree of vibration may be experienced. 
Excessive vibration if left unchecked, can cause a 
multitude of problems, including structural and/or 

component failure. 
The most common 
sources of vibration 
are listed.

Many of these 
conditions can be 
discovered by careful 
observation. Refer to 
the troubleshooting 
section of this 
manual for corrective 

actions. If observation cannot locate the source of 
vibration, a qualified technician using vibration analysis 
equipment should be consulted. If the problem is wheel 
unbalance, in-place balancing can be done through the 
access panel located on the side of each fan’s tubular 
housing. Any correction weights added to the wheel 
should be welded to either the wheel back (single-plane 
balance) or to the wheel back and wheel cone (two-
plane balance).

Common Sources of Vibration

1.  Wheel Unbalance
2.  Drive Pulley Misalignment
3.  Incorrect Belt Tension
4.  Bearing Misalignment
5.  Mechanical Looseness
6.  Faulty Belts
7.  Drive Component Unbalance
8.  Poor Inlet/Outlet Conditions
9.  Foundation Stiffness

WARNING

Disconnect and secure to the 

OFF

 position all 

electrical power to the fan prior to inspection or 
servicing. Failure to comply with this safety precaution 
could result in serious injury or death.

DANGER

Pour écarter les risques de blessure grave ou de mort, 
débrancher et verrouiller l’alimentation électrique en 
position « Arrêt » avant tout contrôle ou entretien.

Содержание FumeJet FJC-300

Страница 1: ...peut tre suffisamment chaud pour provoquer une douleur voire une blessure Laisser le moteur refroidir avant toute maintenance ATTENTION Faire preuve de pr caution dans les atmosph res explosives FJC 3...

Страница 2: ...phere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweati...

Страница 3: ...m Storage 3 General Information Unit and System Identification Tags 4 Pre Installation Information 4 Electrical Disconnects 4 Moving Parts 4 Guards Motor Cover Weatherhood 4 Access Doors 4 Air Pressur...

Страница 4: ...ormation unique to the unit When contacting your local manufacturer s representative with future needs or questions please have the information on this label available Tags are mounted in an area whic...

Страница 5: ...t Installations Inlet Duct Turns Installation of a duct turn or elbow too close to the fan inlet reduces fan performance because air is loaded unevenly into the fan wheel To achieve full fan performan...

Страница 6: ...coating repair section of this manual for details involving touch up of damaged surfaces Lift unit before mounting the stack to the fan body Use standard lifting and rigging practices ALL lifting bra...

Страница 7: ...illustrate three common methods used to install roof curbs for FumeJet systems Methods used to attach a unit are dependent on local codes roof construction design and roof construction materials Consu...

Страница 8: ...installation of the duct drop Duct support will be supplied with roof curb from fan manufacturer or by others Duct Drop and Connection by others Duct Spacing FJC 300 FJI Duct Support inches mm 306 11...

Страница 9: ...ons with application appropriate sealant or tape Stack Installation NOTE Fans should never be lifted by the shaft motor motor cover or accessories Equipment Supports Model GESS equipment supports are...

Страница 10: ...closed Any increase in fan speed represents a substantial increase in load on the motor To avoid motor overheating and possible burnout motor load amperes should always be checked and compared to nam...

Страница 11: ...ening the inlet cone ring bolts and centering the cone ring on the wheel If additional adjustment is required to maintain a constant radial gap loosening the bearing bolts and centering the wheel is a...

Страница 12: ...for colors other than our standard TOUCH UP PAINT REPAIR KIT CONTENTS One pint of Kem Kromik primer including a technical data sheet One pint of industrial enamel including a technical data sheet Four...

Страница 13: ...ere the motor will run in either direction depending on how it has been wired To reverse rotation of a 3 phase motor interchange any two of the three electrical leads Single phase motors can be revers...

Страница 14: ...easing the upper limiting frequency Always check the fan rpm when adjusting the operating frequency Do not exceed maximum class fan rpm of the wheel Belt Span De ection Belt Span 64 Once the unit has...

Страница 15: ...ing to NLGI Grade 2 Factory recommends Mobilux EP 2 The use of synthetic lubricants will increase lubrication intervals by approximately 3 times In addition to lubricating the bearings at speci ed int...

Страница 16: ...cturers procedures for removal and installation 3 Before removing the bearing bolts make sure the shaft is supported slightly Remember to consider the wheel weight on the shaft 4 Remove both bearings...

Страница 17: ...make certain unit is not capable of operation during repairs CAUTION La pr sence d un moteur antid flagrant sur un ventilateur ne garantit pas que tout l appareil est antid flagrant Pour conna tre les...

Страница 18: ...ith optional curb cap inlet box and inlet flanges Stack Motor Cover Disconnect Switch Motor Plate Motor Integrated Mounting Rails Access Door Curb Cap Isolation Damper Roof Curb Scroll Housing Inlet C...

Страница 19: ...s in system Use correction factor to adjust for temperature altitude Resize ductwork Clean lters coils Change fan speed High Motor Amp Draw Fan Check rotation of wheel Reduce fan speed Duct System Res...

Страница 20: ..._____ AM PM Notes __________________________________________ ________________________________________________ ________________________________________________ _________________________________________...

Отзывы: