
21
Step 1 Check the Supply Gas Pressure
Check the supply gas pressure and compare it with the unit’s nameplate pressure requirements. Adjust the
supply regulator as needed until the supply gas pressure is within the specified range. See figure #40. The
nameplate is located on the outside of the unit on the control panel side.
Start-Up
IMPORTANT!
For proper unit function and safety, follow the
start-up procedure in the exact order that it is
presented.
“W.C.
“W.C.
“W.C.
F
PSI
“W.C.
“W.C.
MAX BTU/HR
BTU/H MAX
NORMAL MANIFOLD
PRESSURE
PRESSION D’ADMISSION
NORMALE
MIN GAS
PRESSURE
PRESSION DE GAZ
MIN BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR
TYPE OF GAS
NATURE DU GAZ
MIN BTU/HR
BTU/H MIN
MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX
MAX BURNER
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR
MAX GAS
PRESSURE
PRESSION DE GAZ
MAX
DESIGN
∆
T
∆
T NORMALE
EQUIPPED FOR
CONCU POUR
SCFM
“W.C.
EXTERNAL STATIC PRESSURE
PRESSION STATIQUE EXTERIEURE
AGAINST
CONTE
Minimum and
maximum gas
pressures
IMPORTANT!
This start-up should begin after all of the
installation procedures and the Blower start-up
have been completed.
Start-Up - Direct Gas
Step 2 Check the Optional High and Low Gas Pressure Switches
Check the settings on the high and low gas pressure switches. The high pressure setting is typically 8 inches wc
and the low pressure is setting is typically 3 inches wc. The switches are set at the factory and should not need
adjustment. Adjust the setting only if needed. See the gas train layout diagram in the reference section for the
high and low pressure switch location.
NOTE!
The purpose of the high and low gas pressure switches is to automatically shut down the burner if the
inlet gas pressure is too low for the burner to safely light, or if the manifold pressure is to high for the
burner to operate properly.
Figure 40.
Direct Gas Nameplate