Centrifugal Single-Width Blower

®

Receiving

Upon receiving the product, check to ensure all items 
are accounted for by referencing the delivery receipt or 
packing list. Inspect each crate or carton for shipping 
damage before accepting delivery. Alert the carrier 
of any damage detected. The customer will make 
a notation of damage (or shortage of items) on the 
delivery receipt and all copies of the bill of lading which 
is countersigned by the delivering carrier. If damaged, 
immediately contact your local sales representative. 
Any physical damage to the unit after acceptance is 
not the responsibility of manufacturer.

Unpacking

Verify that all required parts and the correct quantity 
of each item have been received. If any items are 
missing, report shortages to your local representative 
to arrange for obtaining missing parts. Sometimes it 
is not possible that all items for the unit be shipped 
together due to availability of transportation and truck 
space. Confirmation of shipment(s) must be limited to 
only items on the bill of lading.

Handling

Fans are to be rigged and moved by the lifting brackets 
provided or by the skid when a forklift is used. Location 
of brackets varies by model and size. Handle in such 
a manner as to keep from scratching or chipping the 
coating. Damaged finish may reduce the ability of the 
fan to resist corrosion. Fans should never be lifted by 
the shaft, fan housing, motor, belt guard, windband  
or accessories.

Storage

•  Rotate fan wheel monthly and purge bearings once 

every three months

•  Energize fan motor once every three months
•  Store belts flat to keep them from warping  

and stretching

•  Store unit in a location which does not  

have vibration

•  After storage period, purge grease before putting 

fan into service.

If storage of fan is in a humid, dusty or corrosive 
atmosphere, rotate the fan and purge the bearings 
once a month. Improper storage which results in 
damage to the fan will void the warranty.
Fans are protected against damage during shipment. If 
the unit cannot be installed and operated immediately, 
precautions need to be taken to prevent deterioration 
of the unit during storage. The user assumes 
responsibility of the fan and accessories while in 
storage. The manufacturer will not be responsible 
for damage during storage. These suggestions are 
provided solely as a convenience to the user.

INDOOR - 

The ideal environment for the storage of 

fans and accessories is indoors, above grade, in a 
low humidity atmosphere which is sealed to prevent 
the entry of blowing dust, rain or snow. Temperatures 

should be evenly maintained between 30° to 110°F 

(-1° to 43°C)

, wide temperature swings may cause 

condensation and “sweating” of metal parts. All 
accessories must be stored indoors in a clean, dry 
atmosphere.
Remove any accumulations of dirt, water, ice, or snow 
and wipe dry before moving to indoor storage. To avoid 
“sweating” of metal parts allow cold parts to reach room 
temperature. To dry parts and packages, use a portable 
electric heater to remove any moisture build up. Leave 
coverings loose to permit air circulation and to allow for 
periodic inspection.
The unit should be stored at least 3½ inches 

(89 mm)

 

off the floor on wooden blocks covered with moisture 
proof paper or polyethylene sheathing. Aisles between 
parts and along all walls should be provided to permit 
air circulation and space for inspection.

OUTDOOR - 

Fans designed for outdoor applications 

may be stored outdoors, if absolutely necessary. Roads 
or aisles for portable cranes and hauling equipment  
are needed.
The fan should be placed on a level surface to prevent 
water from leaking into the fan. The fan should be 
elevated on an adequate number of wooden blocks 
so it is above water and snow levels and has enough 
blocking to prevent it from settling into soft ground. 
Locate parts far enough apart to permit air circulation, 
sunlight and space for periodic inspection. To minimize 
water accumulation, place all fan parts on blocking 
supports so rain water will run off.
Do not cover parts with plastic film or tarps as these 
cause condensation of moisture from the air passing 
through heating and cooling cycles. 
Fan wheels should be blocked to prevent spinning 
caused by strong winds.

Inspection and Maintenance During 

Storage

While in storage, inspect fans once per month. Keep a 
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, 
the source should be located and eliminated. At 
each inspection, rotate the wheel by hand ten to 
fifteen revolutions to distribute lubricant in motor and 
bearings. If paint deterioration begins, consideration 
should be given to touch-up or repainting. Fans with 
special coatings may require special techniques for 
touch-up or repair.
Machined parts coated with rust preventive should be 
restored to good condition promptly if signs of rust 
occur. Immediately remove the original rust preventive 
coating with petroleum solvent and clean with lint-
free cloths. Polish any remaining rust from surface 
with crocus cloth or fine emery paper and oil. Do not 
destroy the continuity of the surfaces. Thoroughly wipe 
clean with Tectyl

®

 506 (Ashland Inc.) or the equivalent. 

For hard to reach internal surfaces or for occasional 
use, consider using Tectyl

®

 511M Rust Preventive, 

WD-40

®

 or the equivalent.

Содержание CSB

Страница 1: ...to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than the maximum cataloged fan RPM Adjustments to fan speed with Variable Frequency Drives VFD may affect motor load If the fan RPM is changed the motor current should be checked to make sure it is not exceeding the motor nameplate amps 5 Do not allow the pow...

Страница 2: ...atures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts allow cold parts to reach room temperature To dry parts and packag...

Страница 3: ... assure no parts are rubbing 3 Ensure wheel backplate is equidistant from inlet cone ID on both sides in case of double wide wheel for proper wheel centering Table of Contents System Set Up 4 Installation Discharge Positions 5 Method for Wheel Centering 5 V Belt Drive Installation 5 Alignment of Pulleys and Belts 5 Wheel Rotation 5 Unit Start Up Visual Inspection of Equipment 6 Check 6 Additional ...

Страница 4: ... 6 0 4 R o t ati One fan wheel diameter 3 4 to one fan wheel diameter One fan diameter 3 4 to one fan wheel diameter Parallel Fan Installation System Set Up Installations with inlet or discharge configurations that deviate from this manual may result in reduced fan performance Restricted or unstable flow at the fan inlet can cause pre rotation of incoming air or uneven loading of the fan wheel yie...

Страница 5: ...sheaves on shafts Do not drive sheaves on as this may result in bearing damage 3 Align fan and motor sheaves with a straight edge or string and tighten 4 Place belts over sheaves Do not pry or force belts as this could result in damage to the cords in the belts 5 Adjust the tension until the belts appear snug Run the unit for a few minutes and allow the belts to set properly 6 With the fan off and...

Страница 6: ...ding on how it has been wired To reverse rotation of a 3 phase motor interchange any two of the three electrical leads Single phase motors can be reversed by changing internal connections as described on the motor label or wiring diagram 2 Fans with multi speed motors should be checked on low speed during initial start up 3 Check for unusual noise vibration or overheating of bearings Refer to the ...

Страница 7: ...o loose or too tight or misaligned sheaves Abnormally high belt tension or drive misalignment will cause excessive bearing loads and may result in failure of the fan and or motor bearings Conversely loose belts will cause squealing on start up excessive belt flutter slippage and overheated sheaves Either excessively loose or tight belts may cause fan vibration When replacing V belts on multiple gr...

Страница 8: ...ting and until clean grease is seen purging from the bearing The lubrication interval may be modified based on the condition of the purged grease If bearing is not visible to observe purged grease lubricate with number of shots indicated in chart for bore size For conditions including high temperatures moisture dirt or excessive vibration consult the factory for a specific lubrication interval for...

Страница 9: ... procedures Before putting the new bearings on the shaft you may need to break what is called swivel torque on the bearings depending on style of bearing This is done by holding the bearing housing securely and being able to move the inner bearing race around freely 2 Apply light film of oil on shaft then gently slide the new bearings onto the shaft Do not hammer bearing onto shaft 3 Align bearing...

Страница 10: ...tude Resize ductwork Clean filters coils Change fan speed High Motor Amp Draw Fan Check rotation of wheel Reduce fan speed Duct System Resize ductwork Check proper operation of isolation and bypass dampers Check filters and access doors Fan Doesn t Operate Electrical Supply Check fuses circuit breakers Check for switches turned off or disconnected Check for correct supply voltage Drive Check for b...

Страница 11: ...____________________________ ________________________________________________ ________________________________________________ Date________________ Time________________ AM PM Notes ___________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ____________________________...

Страница 12: ...n within the product area tab and in the Technical Data Library info greenheck co in www greenheck co in www greenheck com Our Commitment AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org 484640 CSB Rev 1 June 2020 Copyright 2020 Gree...

Отзывы: