background image

How the Dehumidistat Works

When using either the Two-Speed Switch with Humidity Sensor (435245) or the PrecisionSYNC Control (435244) a built-in 

dehumidistat is present. The following information is provided on how it works.

High indoor humidity levels, during the heating season, have become a problem in many well insulated, tight homes. Excessive 

condensation on the windows is a visual sign of high indoor humidity levels. High indoor humidity levels can result in mold, mildew 

and the eventual degradation of the building structure itself. Your ERV reduces indoor humidity levels when the outdoor air is drier 

than the indoor air.

These conditions usually occur during the heating season when outdoor temperatures are less than 59°F (15°C).

During the heating season, the operation of the ERV may reduce indoor humidity levels sufficiently to eliminate the need for further 

dehumidification. Use the adjustable dehumidistat feature located on the control if your home requires further dehumidification 

during the heating season.

The humidification function aggressively addresses high indoor humidity levels by initiating high speed ventilation when the indoor 

humidity levels rise above the set point on the control. Once the humidity in the house is reduced, the ERV will revert back to its 

previous setting.

It is recommended to operate the ERV for the first few days without use of the dehumidistat function to observe if a further 

dehumidification effect will be required.

The dehumidistat operates in percentage of RH (relative humidity) with 60 being high and 20 being low. If after a few days, further 

dehumidification is required (the building is still too humid), set the humidity level to a lower amount.

The average person is comfortable between 30% and 50% RH. The dehumidistat should be set to OFF for all seasons except the 

heating season since a dehumidifying effect only occurs when the outdoor air is dryer than the indoor air.

Dehumidification Sensing

Every 6 hours the ERV will run and sample the outdoor air temperature (this includes when the unit is in Standby mode) to read 

the outdoor temperature. The unit then resumes operations at the selected mode and speed (approximately 60 second duration). 

Dehumidistat Disable or Dehumidistat Re-enable may be initiated.

Dehumidistat Disable automatically disables the Dehumidistat function on the main wall control when outdoor temperatures exceed 

15°C (59°F) for a full 24-hour period. All other ERV features, and functions operate normally while the Dehumidistat function is 

disabled. 

Dehumidistat Re-enable automatically re-enables the Dehumidistat function if either the outdoor temperature drops below 15°C 

(59°F) for a full 24-hour period or if the ERV is reset (unplugged for 30 seconds).

Residential Energy Recovery Ventilators

10

®

Содержание ASSURE-120S-S1

Страница 1: ...wo Speed Switch with Humidity Sensor 435245 11 PrecisionSYNC Control 435244 12 20 40 60 Minute Timer 435247 13 20 40 60 Minute Wireless Timer 435248 13 Wireless Repeater 435249 13 Overview of Installa...

Страница 2: ...d for ceiling mounting in single family or multi unit residential buildings Fan defrost unit with no balancing or drains required SYNC110 SYNC 110SE S1 50 130 CFM compact high efficiency Energy Recove...

Страница 3: ...r fan operation to be initiated For example the ERV is set to Continuous Ventilation Operation Mode at speed 0 Thermistor This is the temperature sensor that measures electrical resistance as outdoor...

Страница 4: ...78 49 CFM 23 L s 75 64 CFM 30 L s 87 64 CFM 30 L s 81 Sensible Recovery Efficiency 32 F 0 C 49 CFM 23 L s 69 49 CFM 23 L s 72 64 CFM 30 L s 84 64 CFM 30 L s 77 Adjusted Sensible Recovery Efficiency 13...

Страница 5: ...filter is installed for the first time airflow will need to be balanced Condensate Drain Connections Spouts qty 2 1 2 o d Drain Tee qty 1 1 2 o d No No No Yes optional use Drain Plug Included No No N...

Страница 6: ...7 46 42 20 102 48 215 101 0 6 150 92 43 89 42 202 95 0 7 175 87 41 76 36 192 90 0 8 200 80 38 63 30 177 83 0 9 225 72 34 49 23 165 78 1 0 250 34 16 155 73 Speed 3 Medium IN WG PA CFM L s CFM L s CFM L...

Страница 7: ...IDE VIEW 10 in 254 mm 22 in 559 mm 6 in 152 mm Collars Collar mounted balancing ports Core Motorized Impellers Filters Stale Air to Outside Airflow Fresh Air from Outside Stale Air from Inside Fresh A...

Страница 8: ...SYNC 270TCE S1 During defrost a motor driven damper door mechanism closes off the supply air from outside allowing exhaust air to recirculate through the unit s core During the defrost portion of the...

Страница 9: ...0 X 0 03 4 1 X 7 5 97 5 Table Method Example a 2000 square foot building with 4 bedrooms from Section 4 1 1 Table 4 1a a quick reference table predicts 98 cfm The following table complies with ASHRAE...

Страница 10: ...vious setting It is recommended to operate the ERV for the first few days without use of the dehumidistat function to observe if a further dehumidification effect will be required The dehumidistat ope...

Страница 11: ...amper defrost models Table 7 Two Speed Switch with Humidity Sensor Settings Settings Icon Description Turning on the Control Press and release the ON OFF button The light above will illuminate Setting...

Страница 12: ...time interval selected When the timer runs out the unit will return to its previous operating speed Setting the Mode of Operation There are five modes of operation available with the PrecisionSYNC Co...

Страница 13: ...have an estimated range of 40 feet 12 meters with no obstructions To increase the range of the timer a Wireless Repeater may be used Multiple timers can be paired to a single control They are designed...

Страница 14: ...gth approximately 12 inches 300 mm of non metallic flexible duct should be connected between the ERV and the supply exhaust duct system to avoid possible noise transfer through the duct system All duc...

Страница 15: ...tion may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installation Methods Simplified Return Return Figure 13 S...

Страница 16: ...ler Furnace Blower on page 24 The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installat...

Страница 17: ...igures KEY POINTS The ERV unit must be balanced The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for ac...

Страница 18: ...or during adjustment of the straps 4 Level the unit from left to right and front to back Adjust the unit down by lifting up on the buckles Adjust the unit up by pulling down vertically on the hand loo...

Страница 19: ...trated in Figure 23 Drain Holes and P Trap 1 Cut two lengths of hose and connect each piece to an end of the T fitting then connect the other ends to the two drain spouts 2 Position the T fitting to p...

Страница 20: ...aust The pressure drop airflow charts should be referred to when matching the Dual Intake and Exhaust Hood to the ERV The Dual Intake and Exhaust Hood Kit is compatible with 5 or 6 diameter duct ERV D...

Страница 21: ...through the opening in the wall 8 Connect red green and yellow to the wiring terminals located on the back plate Figure 29 Boxes D E or F 9 Attach the back plate to the wall using two supplied screws...

Страница 22: ...If pairing was not successful you now must return to step 1 to restart the pairing process 6 Press the button on the control to exit pairing mode when wireless timers have been successfully paired To...

Страница 23: ...e Wireless Timer and Control To pair additional Wireless Repeater 435249 with the same control repeat steps 1 5 until all Wireless Repeaters 435249 have been paired When installed in its permanent loc...

Страница 24: ...Only The ERV is compatible with two wire dry contact third party mechanical timers This may be useful for retrofit situations where only two wires are available for the timer Install the two wire time...

Страница 25: ...setting the control to ON and selecting speed 0 Timers will initiate high speed ventilation when activated CAUTION Building codes in some areas require fully off functionality Check with your local b...

Страница 26: ...nit Wiring Diagrams Applicable Unit ASSURE 120S S1 Applicable Unit SYNC 110SE S1 Figure 37 ASSURE 120S S1 Wiring Diagram Figure 38 ERV 110E S1 Wiring Diagram Residential Energy Recovery Ventilators 26...

Страница 27: ...otor Damper Defrost Units Only BLUE BLACK WHITE WHITE Door Switch Note If any of the original wires supplied must be replaced use only TEW certified wire Important Control wiring low voltage communica...

Страница 28: ...Defrost cycle enabled Dip 2 Null Switch 2 Dip 1 On R2000 Defrost cycle disabled Dip 1 Off R2000 Defrost cycle enabled Dip 2 Null Switch 1 Auto balance Unit Selection Switch 1 Auto balance Unit Select...

Страница 29: ...Gauge A digital manometer is a suitable instrument for the balancing of airflows Gauge Attachments When sampling an airflow various attachments are available for use on a digital manometer The illust...

Страница 30: ...Air to Inside stream 4 Review the readings and damper down the duct with the highest duct velocity pressure Repeat Steps 2 and 3 until both ducts show identical readings Upon completion of balancing...

Страница 31: ...et value CFM Pause until the airflow values CFM have stabilized Airflow values CFM increase and decrease in increments of 5 CFM CFM fluctuations of 10 CFM from target is acceptable A Balance Indicator...

Страница 32: ...tc Occupant Lifestyle Moisture coming into the home from an non vented or non heated crawl space Moisture remaining in washroom and or kitchen areas Condensation seems to form in the spring and fall s...

Страница 33: ...d any debris 4 Install clean core as follows a Install the bottom flange of the core guide into the bottom H channel approximately 1 4 6 mm b Install the left or right side flange of the core guide ap...

Страница 34: ...attached firmly Seal and tape insulation and moisture barrier not applicable for SYNC 270TCE S1 A capable HVAC service company will best perform this procedure Homeowner Maintenance Information conti...

Страница 35: ...al and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org As a result of our commitment to continuous improvement Green...

Отзывы: