The airflow on the SYNC-110SE-S1 units can be adjusted up or down. The unit must 
be running for speed alterations to be made.

1.  Set the unit to the speed which is to be adjusted.
2.  Locate the ECM circuit board which is under the metal cover on the side of the 

unit.

3.  Hold both buttons (S1 and S2) at the same time for 6 seconds until the LED lights 

illuminate.

4.  Press UP button (S1) or DOWN button (S2) to adjust the motor speed. Press the 

button multiple times for larger increases. The LEDs will indicate whether the fan 
speed is at the Factory Set speed (F. SET), above (HIGH), or below (LOW).

5.  When the desired airflow has been reached no further action is required and the 

metal cover can be fastened back on. This process may be repeated for any of the 
available speeds.

Balancing the airflows is critical to ensure that the amount of air coming into the building equals the amount of air exhausted to the 
outside of the building. If these two airflows are not properly balanced, the following issues may occur: 

 

 

 

  
•  A positive or negative pressure in the house    

 

 

 

 

 

•  ERV will not operate at its maximum efficiency 

 

 

 

 

 

 

•  ERV will not defrost properly
       
The ASSURE-120S-S1 and SYNC-110SE-S1 are considered “factory balanced”. Due to the design of the unit, if the supply and 
exhaust static pressure of the duct installation are within 0.3 (in w.g.) of each other, the supply and exhaust airflows will be within 10% 
of each other. These units, therefore, do not require balancing during installation if these conditions are met. If these conditions are not 
met then follow the manual balancing procedure below.
         
The SYNC-180SCE-S1 and SYNC-270TCE-S1 should be balanced using the Auto Balance feature of the PrecisionSYNC Control 
(435244).

Airflow Measuring Gauge:
•  A digital manometer is a suitable instrument for the balancing of airflows.

Gauge Attachments:
When sampling an airflow, various attachments are available for use on a digital 
manometer. The illustration below shows a digital manometer with a pitot tube 
attachment. This combination will measure the system air velocity pressure accurately, 
regardless of the duct size or shape (either round or rectangular).

Balancing Preparation:
Prior to performing the air balancing procedure, perform the following steps:

1.  Seal the ductwork.

2.  Confirm the installation and proper operation of all the components of the ERV.

3.  Fully open the balancing dampers.

4.  Turn off all household exhaust devices (range hood, clothes dryer, bathroom fans).

5.  Set the system at high speed.

6.  Prior to balancing the unit, first adjust airflows in the branch lines to specific areas of the house.

7.  If the outdoor temperature is below 0°C (32°F), ensure the unit is not running in defrost.

8.  If the system is a Simplified or Partially Dedicated installation, operate the furnace/air handler at high speed.

Adjusting the EC Motor (SYNC-110SE-S1)

Balancing the Airflows

Manual Balancing

DOWN

UP

10065

ECM01

S1

S2

T1

T2

T3

LO

W

F.SET

HIGH

PWM

GND

GND

UNITS

ON
OFF

ZERO

DUCT

AIR 

FLOW

Digital
Manometer

Pitot Tube

          ATTENTION

Continuous, excessive, positive pressure may drive moist indoor air into the external walls of the building. Once inside the external walls, 

moist air may condense (in cold weather) and degrade structural components or cause locks to freeze.

Continuous, excessive, negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane 

and radon gas may be drawn into the home through basement or ground contact areas and may also cause the backdrafiting of vented 

combustion equipment.

Figure 40. EC Motor Adjusting Circuit Board

Figure 41. Manual Balancing

Residential Energy Recovery Ventilators

29

®

Содержание ASSURE-120S-S1

Страница 1: ...wo Speed Switch with Humidity Sensor 435245 11 PrecisionSYNC Control 435244 12 20 40 60 Minute Timer 435247 13 20 40 60 Minute Wireless Timer 435248 13 Wireless Repeater 435249 13 Overview of Installa...

Страница 2: ...d for ceiling mounting in single family or multi unit residential buildings Fan defrost unit with no balancing or drains required SYNC110 SYNC 110SE S1 50 130 CFM compact high efficiency Energy Recove...

Страница 3: ...r fan operation to be initiated For example the ERV is set to Continuous Ventilation Operation Mode at speed 0 Thermistor This is the temperature sensor that measures electrical resistance as outdoor...

Страница 4: ...78 49 CFM 23 L s 75 64 CFM 30 L s 87 64 CFM 30 L s 81 Sensible Recovery Efficiency 32 F 0 C 49 CFM 23 L s 69 49 CFM 23 L s 72 64 CFM 30 L s 84 64 CFM 30 L s 77 Adjusted Sensible Recovery Efficiency 13...

Страница 5: ...filter is installed for the first time airflow will need to be balanced Condensate Drain Connections Spouts qty 2 1 2 o d Drain Tee qty 1 1 2 o d No No No Yes optional use Drain Plug Included No No N...

Страница 6: ...7 46 42 20 102 48 215 101 0 6 150 92 43 89 42 202 95 0 7 175 87 41 76 36 192 90 0 8 200 80 38 63 30 177 83 0 9 225 72 34 49 23 165 78 1 0 250 34 16 155 73 Speed 3 Medium IN WG PA CFM L s CFM L s CFM L...

Страница 7: ...IDE VIEW 10 in 254 mm 22 in 559 mm 6 in 152 mm Collars Collar mounted balancing ports Core Motorized Impellers Filters Stale Air to Outside Airflow Fresh Air from Outside Stale Air from Inside Fresh A...

Страница 8: ...SYNC 270TCE S1 During defrost a motor driven damper door mechanism closes off the supply air from outside allowing exhaust air to recirculate through the unit s core During the defrost portion of the...

Страница 9: ...0 X 0 03 4 1 X 7 5 97 5 Table Method Example a 2000 square foot building with 4 bedrooms from Section 4 1 1 Table 4 1a a quick reference table predicts 98 cfm The following table complies with ASHRAE...

Страница 10: ...vious setting It is recommended to operate the ERV for the first few days without use of the dehumidistat function to observe if a further dehumidification effect will be required The dehumidistat ope...

Страница 11: ...amper defrost models Table 7 Two Speed Switch with Humidity Sensor Settings Settings Icon Description Turning on the Control Press and release the ON OFF button The light above will illuminate Setting...

Страница 12: ...time interval selected When the timer runs out the unit will return to its previous operating speed Setting the Mode of Operation There are five modes of operation available with the PrecisionSYNC Co...

Страница 13: ...have an estimated range of 40 feet 12 meters with no obstructions To increase the range of the timer a Wireless Repeater may be used Multiple timers can be paired to a single control They are designed...

Страница 14: ...gth approximately 12 inches 300 mm of non metallic flexible duct should be connected between the ERV and the supply exhaust duct system to avoid possible noise transfer through the duct system All duc...

Страница 15: ...tion may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installation Methods Simplified Return Return Figure 13 S...

Страница 16: ...ler Furnace Blower on page 24 The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installat...

Страница 17: ...igures KEY POINTS The ERV unit must be balanced The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for ac...

Страница 18: ...or during adjustment of the straps 4 Level the unit from left to right and front to back Adjust the unit down by lifting up on the buckles Adjust the unit up by pulling down vertically on the hand loo...

Страница 19: ...trated in Figure 23 Drain Holes and P Trap 1 Cut two lengths of hose and connect each piece to an end of the T fitting then connect the other ends to the two drain spouts 2 Position the T fitting to p...

Страница 20: ...aust The pressure drop airflow charts should be referred to when matching the Dual Intake and Exhaust Hood to the ERV The Dual Intake and Exhaust Hood Kit is compatible with 5 or 6 diameter duct ERV D...

Страница 21: ...through the opening in the wall 8 Connect red green and yellow to the wiring terminals located on the back plate Figure 29 Boxes D E or F 9 Attach the back plate to the wall using two supplied screws...

Страница 22: ...If pairing was not successful you now must return to step 1 to restart the pairing process 6 Press the button on the control to exit pairing mode when wireless timers have been successfully paired To...

Страница 23: ...e Wireless Timer and Control To pair additional Wireless Repeater 435249 with the same control repeat steps 1 5 until all Wireless Repeaters 435249 have been paired When installed in its permanent loc...

Страница 24: ...Only The ERV is compatible with two wire dry contact third party mechanical timers This may be useful for retrofit situations where only two wires are available for the timer Install the two wire time...

Страница 25: ...setting the control to ON and selecting speed 0 Timers will initiate high speed ventilation when activated CAUTION Building codes in some areas require fully off functionality Check with your local b...

Страница 26: ...nit Wiring Diagrams Applicable Unit ASSURE 120S S1 Applicable Unit SYNC 110SE S1 Figure 37 ASSURE 120S S1 Wiring Diagram Figure 38 ERV 110E S1 Wiring Diagram Residential Energy Recovery Ventilators 26...

Страница 27: ...otor Damper Defrost Units Only BLUE BLACK WHITE WHITE Door Switch Note If any of the original wires supplied must be replaced use only TEW certified wire Important Control wiring low voltage communica...

Страница 28: ...Defrost cycle enabled Dip 2 Null Switch 2 Dip 1 On R2000 Defrost cycle disabled Dip 1 Off R2000 Defrost cycle enabled Dip 2 Null Switch 1 Auto balance Unit Selection Switch 1 Auto balance Unit Select...

Страница 29: ...Gauge A digital manometer is a suitable instrument for the balancing of airflows Gauge Attachments When sampling an airflow various attachments are available for use on a digital manometer The illust...

Страница 30: ...Air to Inside stream 4 Review the readings and damper down the duct with the highest duct velocity pressure Repeat Steps 2 and 3 until both ducts show identical readings Upon completion of balancing...

Страница 31: ...et value CFM Pause until the airflow values CFM have stabilized Airflow values CFM increase and decrease in increments of 5 CFM CFM fluctuations of 10 CFM from target is acceptable A Balance Indicator...

Страница 32: ...tc Occupant Lifestyle Moisture coming into the home from an non vented or non heated crawl space Moisture remaining in washroom and or kitchen areas Condensation seems to form in the spring and fall s...

Страница 33: ...d any debris 4 Install clean core as follows a Install the bottom flange of the core guide into the bottom H channel approximately 1 4 6 mm b Install the left or right side flange of the core guide ap...

Страница 34: ...attached firmly Seal and tape insulation and moisture barrier not applicable for SYNC 270TCE S1 A capable HVAC service company will best perform this procedure Homeowner Maintenance Information conti...

Страница 35: ...al and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org As a result of our commitment to continuous improvement Green...

Отзывы: