Vektor-CD Centrifugal Laboratory Exhaust 

®

Riser Installation

Check curb or structural supports for levelness. Both 
must be level to ensure proper drainage from plenum 
and fan(s).

For side inlet fans, remove panel at end of plenum. 
This opening is the designed connection spot for user 
connected ductwork from building.

Lab Exhaust Riser

Riser duct(s) run up through the curb and are 
flanged over the curb. (by contractor)

Roof Curb—anchor curb to roof 
deck structure in accordance with 
project construction documents 
and local codes.

Plenum Assembly

Note: Gasketing material (shipped with fan) should 
be placed on the top edge of already installed roof 
curb prior to placing the plenum or individual plenum 
sections on the curb.

If the plenum is shipped disassembled, the plenum 
sections can be assembled together into one single 
piece before lifting onto the roof and then fitted on 
the roof curb / support structure, or each section can 
be placed on individually. The method used would be 
dependent on the lifting capacity for the equipment 
on-site. If moving each piece separately onto the 
roof curb or support structure, each section should 
be joined to its mating part before moving another 
section into place.
For a 1x1 system there is only a single plenum section 
and no multiple plenum assembly would be required.

Determine the placement of the plenum 

sections relative to each other  

(Multiple Fan Systems)

When looking at the individual section one will notice 
that each plenum section is missing at least one 
side panel. These areas are the locations where the 
sections are to be joined together. If you have two 
plenum sections, then each one would be missing a 
side panel. If you have a three-fan system, there are 
three plenum sections. The two end plenum sections 
would each be missing one side panel and the middle 
section would not have panels on two sides. Please 
refer to the submittal drawing for the orientation of 
any Bypass Air Plenum (BAP) dampers or air inlet 
locations.

Putting the plenum together

After identifying the plenum sections arrangement 
order, one of the two mating sections has weld nuts 
on the inside of the plenum. The assembly hardware 
(stainless steel bolts) required to join the sections 
is located here for shipping purposes. These bolts 
should be removed and set-aside prior to placing the 
mating sections together. The bolts are located every 
6 to 10 inches to provide the best seal between the 
mating sections.
Before moving the sections into position, gasketing 
must be installed to seal the plenum sections against 
leakage. This silicone gasketing is supplied with 
the fans and only needs to be applied to one of the 
two mating plenum sections. The bands or strips of 
gasketing should be attached around the perimeter of 
the joining face and with an additional strip making a 
triangular area in each corner. 
After the gasketing has been attached and the 
hardware has been removed, place the two mating 
sections together. The stainless steel bolts, which 
were set aside earlier, are now run first through the 
holes of the plenum section without the weld nuts and 
tighten into the weld nuts on the other plenum section.

Plenum Isometric View

Содержание 471555

Страница 1: ...n Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than maximum cataloged fan rpm Adjustments to fan speed significantly effects motor load If the fan RPM is changed the motor current should be checked to make sure it is not...

Страница 2: ...nal use consider using Tectyl 511M Rust Preventive or WD 40 or the equivalent Receiving Upon receiving the product check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The carrier will make notification on the delivery receipt ac...

Страница 3: ...sed sound levels System Identification Tags Vektor fan systems may arrive in component pieces due to shipping restrictions Individual components of a system have matching identification tags which should be used to identify and assemble the complete system Assembling systems with different identification tags can cause reductions in the fan s performance Standard Fan Configurations The following i...

Страница 4: ...ase and the foundation After the fan isolation base and isolators are installed the entire assembly must be leveled Position the level on the isolation base not the fan shaft for proper leveling Additionally the motor and fan shafts must be level and parallel relative to each other for proper alignment Greenheck Roof Curb for Vektor Systems Install 1 2 in bolt 5 1 2 in maximum bolt spacing 4 in ma...

Страница 5: ...n is missing at least one side panel These areas are the locations where the sections are to be joined together If you have two plenum sections then each one would be missing a side panel If you have a three fan system there are three plenum sections The two end plenum sections would each be missing one side panel and the middle section would not have panels on two sides Please refer to the submit...

Страница 6: ...O ROOF DECK FAN PLENUM AND CURB FAN PLENUM AND CURB FAN AND PLENUM NO CURB FAN AND CURB NO PLENUM Field drilled bolted by others Bypass Air Plenum Structural Support by others 3 16 in silicone gasket by Greenheck Weatherhood with birdscreen optional 5 16 in bolt typical by Greenheck Plenum no Curb to Channel Base Fan Plenum and Curb to Roof Deck Plenum Assembly continued An additional side or acce...

Страница 7: ...e designed and installed by others Guy wire attachments Fan Assembly Stack Extension If fan requires a stack or stack extension install on fan before installing nozzle and windband Place gasketing between any sections blower housing and initial stack Use lifting lugs to position each piece into place Attach stack or stack extension to blower housing using 316 stainless steel bolts provided through...

Страница 8: ...ching ductwork to the plenum care should be taken to ensure a tight fit and proper seal to prevent leakage of the contaminated airstream Ductwork that is a different size than the removable access panel can either use a transition to the plenum s opening size or the access panel can be field modified by cutting an opening to the size of the ductwork Vektor Field Coating Repair Procedure for Scratc...

Страница 9: ... diagram above If fan flow motor speed is to be controlled using a VFD the reduced voltage and frequency supplied to the fan will cause control problems with the isolation damper actuator When a Vektor control sequence requires the use of a VFD it is suggested that the control contractor supply the isolation damper actuator voltage independent of the power supplied to the Vektor fan motor For Vekt...

Страница 10: ...lti speed motors should be checked on low speed during initial start up 4 Check for unusual noise vibration or overheating of bearings Refer to the Troubleshooting section of this manual if a problem develops 5 Grease may be forced out of the bearing seals during initial start up This is a normal self purging feature of this type of bearing Vibration Excessive vibration is the most frequent proble...

Страница 11: ...ts off the sheaves After replacing belts ensure that slack in each belt is on the same side of the drive Belt dressing should never be used Do not install new belts on worn sheaves If the sheaves have grooves worn in them they must be replaced before new belts are installed The proper tension for operating a V belt drive is the lowest tension at which the belts will not slip at peak load condition...

Страница 12: ...D fans use Mobil Mobilith SHC 100 synthetic grease conforming to NCGI Grade 2 Never mix greases made with different bases This will cause a breakdown of the grease and possible failure of the bearing For specific information contact the factory representative or the fan system submittals Service V Belt Drives The V belt drive components when supplied by Greenheck Fan Corporation have been carefull...

Страница 13: ... should be checked after the fan has been in operation for 24 hours and before start up after the unit has been serviced Radial gap is adjusted by loosening the inlet cone ring bolts and centering the cone ring on the wheel If additional adjustment is required to maintain a constant radial gap loosening the bearing bolts and centering the wheel is acceptable as a secondary option Overlap is adjust...

Страница 14: ...upply Check fuses circuit breakers Check for switches turned off or disconnected Check for correct supply voltage Drive Check for broken belts Tighten loose pulleys Motor Assure motor is correct horsepower and not tripping overload protector Overheated bearing Lubrication Check for excessive or insufficient grease in the bearing Mechanical Replace damaged bearing Relieve excessive belt tension Ali...

Страница 15: ...______________ _________________________________________________ _________________________________________________ Maintenance Log Date___________________ Time______________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ ____________________...

Страница 16: ...hould be returned to the nearest authorized motor service station Greenheck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Greenheck Catalog Vektor CD provides additional information describing the equipment fan performance available accessories and specificat...

Отзывы: