Vektor-CD Centrifugal Laboratory Exhaust

®

Plenum and Fan Drainage Piping and  

Trap Detail (by others)

There are multiple locations for pipe connections, one 
on each plenum section, and another on each tubular 
fan housing located at the bottom of the scroll. Each 
drain should be properly connected to a drainage 
system to ensure proper disposal of any water or 
condensate that may occur.
  •  Installed piping to have a downward angle to 

  allow for drainage

  •  Fill trap to recommended level before start-up

Y Dim ≥ System Pressure
X Dim ≥ 1/2 System Pressure
Dimension of X and Y are inches.

Bypass Air Plenum (BAP), Isolation 

Damper Access & Actuator Mounting

Depending on the configuration and intended 
operation of the system supplied, every Vektor plenum 
section may not have a weatherhood and bypass air 
damper. Typically systems that include a fan which 
is on standby will have one less weatherhood and 
BAP damper assembly than plenum sections. Refer 
to submittal drawings for additional information. The 
appropriate guard / cover needs to be removed for 
installation, inspection and maintenance.

For Vektor Fans with a Weatherhood

Access to the bypass air plenum damper and the 
isolation damper, actuator(s) (optional from factory), 
and voltage transformer (optional from factory) is 
gained through the removal of the weatherhood 
guard / cover. The isolation damper assembly can be 
removed from its location by unbolting the frame from 
the plenum and removing the flex connector.

Duct Connections to the Bypass Air 
Plenum (BAP)

Connecting primary exhaust air ducts is allowed 
through the roof curb or through one or more of the 
side access panels. To reduce the potential for system 
effects in the plenum, the duct connection should 
be sized to have a maximum air velocity of 1500 fpm 
when entering. When attaching ductwork to the 
plenum, care should be taken to ensure a tight fit and 
proper seal to prevent leakage of the contaminated 
airstream.
Ductwork that is a different size than the removable 
access panel can either use a transition to the 
plenum’s opening size, or the access panel can be 
field modified by cutting an opening to the size of the 
ductwork.

Vektor Field Coating Repair Procedure for 

Scratched Areas

Standard coating and color for the Vektor laboratory 
exhaust system is Greenheck’s Hi-Pro Polyester Gray 
(041).
The procedure below details the correct method for 
repairing minor scratches in the coating. Each Vektor 
unit is supplied with a repair kit for use after the initial 
installation.
The kit includes: 

•  1 pint Kem Kromik

®

 Universal Metal Primer

  •  1 pint industrial enamel (Industrial 041 Gray)
  •  4 disposable foam brushes
  •  1 sheet of sandpaper
  •  2 tech data sheets for the two paints
  •  1 repair procedure.
  1.   Scuff affected area to be repaired using medium 

sandpaper (provided). Feather the edges.

  2.  Clean affected area to be touched up using an 

alkaline based cleaner and rinse.

  3.  Apply Kem Kromik

®

 primer using the 1 inch foam 

brush (provided). Follow technical data sheet 
instructions.

  4.  Allow primer to dry a minimum of 2-1/2 hours 

before top coating.

  5.  Topcoat with Industrial enamel using 1 inch foam 

brush (provided). Follow technical data sheets 
instructions. Allow painted units to air-dry and 
cure before putting into service. See enclosed 
Technical Data sheets for detailed drying and 
cure schedules at different temperatures.

To order additional coating repair kits please reference 
Greenheck’s part number, HAZ2037 HI-PRO GRAY 
FIELD DAMAGE REPAIR KIT. Please contact factory 
with your fan’s serial number for colors other than our 
standard Gray (041).

Y

X

1 inch of water 

A

B

C

Detail of bypass air 

plenum and blower 

housing 

Clean out location

1 in. drain coupling in blower 

housing and bypass air plenum

Note: Refer to local codes for proper disposal of 
potential hazardous drainage.

Содержание 471555

Страница 1: ...n Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than maximum cataloged fan rpm Adjustments to fan speed significantly effects motor load If the fan RPM is changed the motor current should be checked to make sure it is not...

Страница 2: ...nal use consider using Tectyl 511M Rust Preventive or WD 40 or the equivalent Receiving Upon receiving the product check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The carrier will make notification on the delivery receipt ac...

Страница 3: ...sed sound levels System Identification Tags Vektor fan systems may arrive in component pieces due to shipping restrictions Individual components of a system have matching identification tags which should be used to identify and assemble the complete system Assembling systems with different identification tags can cause reductions in the fan s performance Standard Fan Configurations The following i...

Страница 4: ...ase and the foundation After the fan isolation base and isolators are installed the entire assembly must be leveled Position the level on the isolation base not the fan shaft for proper leveling Additionally the motor and fan shafts must be level and parallel relative to each other for proper alignment Greenheck Roof Curb for Vektor Systems Install 1 2 in bolt 5 1 2 in maximum bolt spacing 4 in ma...

Страница 5: ...n is missing at least one side panel These areas are the locations where the sections are to be joined together If you have two plenum sections then each one would be missing a side panel If you have a three fan system there are three plenum sections The two end plenum sections would each be missing one side panel and the middle section would not have panels on two sides Please refer to the submit...

Страница 6: ...O ROOF DECK FAN PLENUM AND CURB FAN PLENUM AND CURB FAN AND PLENUM NO CURB FAN AND CURB NO PLENUM Field drilled bolted by others Bypass Air Plenum Structural Support by others 3 16 in silicone gasket by Greenheck Weatherhood with birdscreen optional 5 16 in bolt typical by Greenheck Plenum no Curb to Channel Base Fan Plenum and Curb to Roof Deck Plenum Assembly continued An additional side or acce...

Страница 7: ...e designed and installed by others Guy wire attachments Fan Assembly Stack Extension If fan requires a stack or stack extension install on fan before installing nozzle and windband Place gasketing between any sections blower housing and initial stack Use lifting lugs to position each piece into place Attach stack or stack extension to blower housing using 316 stainless steel bolts provided through...

Страница 8: ...ching ductwork to the plenum care should be taken to ensure a tight fit and proper seal to prevent leakage of the contaminated airstream Ductwork that is a different size than the removable access panel can either use a transition to the plenum s opening size or the access panel can be field modified by cutting an opening to the size of the ductwork Vektor Field Coating Repair Procedure for Scratc...

Страница 9: ... diagram above If fan flow motor speed is to be controlled using a VFD the reduced voltage and frequency supplied to the fan will cause control problems with the isolation damper actuator When a Vektor control sequence requires the use of a VFD it is suggested that the control contractor supply the isolation damper actuator voltage independent of the power supplied to the Vektor fan motor For Vekt...

Страница 10: ...lti speed motors should be checked on low speed during initial start up 4 Check for unusual noise vibration or overheating of bearings Refer to the Troubleshooting section of this manual if a problem develops 5 Grease may be forced out of the bearing seals during initial start up This is a normal self purging feature of this type of bearing Vibration Excessive vibration is the most frequent proble...

Страница 11: ...ts off the sheaves After replacing belts ensure that slack in each belt is on the same side of the drive Belt dressing should never be used Do not install new belts on worn sheaves If the sheaves have grooves worn in them they must be replaced before new belts are installed The proper tension for operating a V belt drive is the lowest tension at which the belts will not slip at peak load condition...

Страница 12: ...D fans use Mobil Mobilith SHC 100 synthetic grease conforming to NCGI Grade 2 Never mix greases made with different bases This will cause a breakdown of the grease and possible failure of the bearing For specific information contact the factory representative or the fan system submittals Service V Belt Drives The V belt drive components when supplied by Greenheck Fan Corporation have been carefull...

Страница 13: ... should be checked after the fan has been in operation for 24 hours and before start up after the unit has been serviced Radial gap is adjusted by loosening the inlet cone ring bolts and centering the cone ring on the wheel If additional adjustment is required to maintain a constant radial gap loosening the bearing bolts and centering the wheel is acceptable as a secondary option Overlap is adjust...

Страница 14: ...upply Check fuses circuit breakers Check for switches turned off or disconnected Check for correct supply voltage Drive Check for broken belts Tighten loose pulleys Motor Assure motor is correct horsepower and not tripping overload protector Overheated bearing Lubrication Check for excessive or insufficient grease in the bearing Mechanical Replace damaged bearing Relieve excessive belt tension Ali...

Страница 15: ...______________ _________________________________________________ _________________________________________________ Maintenance Log Date___________________ Time______________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ ____________________...

Страница 16: ...hould be returned to the nearest authorized motor service station Greenheck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Greenheck Catalog Vektor CD provides additional information describing the equipment fan performance available accessories and specificat...

Отзывы: