AIR-TO-WATER HEAT PUMP CONTROL
62
FL
Malfunction of the first sanitary water tank temperature sensor
F3
Malfunction of gas pipe temperature sensor inside refrigerant
dF
Malfunction of other thermal outlet temperature sensor
F0
Malfunction of remote room temperature sensor
Ec
Malfunction of water switch
E2
Indoor anti-frozen protetion
No display
Over temperature of sanitary water tank temperature
Ed
Over temperature of outlet temperature(This error code will not displayed on wired
controller but only on mainboard of outdoor unit)
No display
Over temperature of solar outlet temperature
EH
Malfunction of the first internal electric heater connection
EH
Malfunction of the second internal electric heater connection
EH
Malfunction of sanitary water tank electric heater connection
dU
Pull-out gate-controller
3.2.3.15 Test Mode
The test mode setting is as follow
:
(1). Operate the wired controller to let the heating/cooling operation OFF and water
heating OFF and then hold down ESC and Return buttons at the same time for 10
seconds into test mode.
(2). In test mode, except
▲
,
▼
,Set, Esc and Return buttons all buttons are
shielded.
(3). In test mode
Press
▲
or
▼
button to select the type of test mode. There are 2 types in total for
selection.
If the minute display area of CLOCK is 01, it means test mode 1
①
---cooling
operation.
If the minu
②
te display area of CLOCK is 02, it means test mode 2---heating
operation.
The compressor
′
s frequency during the operation will be adjusted according to the
difference between the actual leaving water temperature and target set temperature, so
test mode is mainly for nominal performance testing.
3.3Installation
(1). Open front panel of indoor unit and release the clasp of wired controller as shown
in Fig 1.
Содержание SXVD200LCJ/A-K
Страница 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Страница 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Страница 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Страница 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Страница 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Страница 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Страница 115: ...AIR TO WATERHEATPUMP MAINTENANCE 109 2 Comp Low pressure Protection E3 3 Comp Discharge Temp Protection E4...
Страница 116: ...AIR TO WATERHEATPUMP MAINTENANCE 110 4 Overload proection of compressor or driver error E5 5 Outdoor fan error EF...
Страница 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Страница 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Страница 129: ...AIR TO WATERHEATPUMP MAINTENANCE 123 3 2 3 Tripping Fig 3 2 3 Flowchart of diagnosis of Tripping...
Страница 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Страница 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...
Страница 155: ...AIR TO WATERHEATPUMP MAINTENANCE 149 Exploded View of GRS CQ12Pd Na K O GRS CQ14Pd Na K O and GRS CQ16Pd Na K O...