AIR-TO-WATER HEAT PUMP CONTROL
61
5) Press
button or
button to return to the main menu. The system will
automatically release without any input after 20 seconds.
3.2.3.14 Error Code Display
When the error is occurred to indoor unit or outdoor unit, the error code will be
displayed on control panel. Icon
will show.
The table of error code
Error code
Error description
F4
Malfunction of outdoor environment temperature sensor
F6
Malfunction of defrost temperature sensor
F7
Malfunction of discharge temperature sensor
F5
Malfunction of suction temperature sensor
EF
Malfunction of outdoor fan
E5
Overload protection of compressor or malfunction of driver
E1
High pressure protection of compressor
E3
Low pressure protection of compressor
E4
High-temperature protection of discharge
C5
Malfunction of indoor capacity switch
E6
Communications failure between outdoor and indoor mainboard
E6
Communications failure between outdoor mainboard and wired controller
Fc
Malfunction of high pressure sensor
F9
Malfunction of outlet temperature sensor
dH
Malfunction of backup outlet temperature sensor
F1
Malfunction of liquid pipe temperature sensor inside refrigerant
F8
Malfunction of inlet temperature sensor
FE
Malfunction of the second sanitary water tank temperature sensor
Содержание SXVD200LCJ/A-K
Страница 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Страница 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Страница 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Страница 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Страница 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Страница 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Страница 115: ...AIR TO WATERHEATPUMP MAINTENANCE 109 2 Comp Low pressure Protection E3 3 Comp Discharge Temp Protection E4...
Страница 116: ...AIR TO WATERHEATPUMP MAINTENANCE 110 4 Overload proection of compressor or driver error E5 5 Outdoor fan error EF...
Страница 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Страница 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Страница 129: ...AIR TO WATERHEATPUMP MAINTENANCE 123 3 2 3 Tripping Fig 3 2 3 Flowchart of diagnosis of Tripping...
Страница 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Страница 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...
Страница 155: ...AIR TO WATERHEATPUMP MAINTENANCE 149 Exploded View of GRS CQ12Pd Na K O GRS CQ14Pd Na K O and GRS CQ16Pd Na K O...