AIR-TO-WATERHEATPUMP MAINTENANCE
102
UNITS MAINTENANCE
1 ERROR CODE LIST
¾
Complete Unit Code
Code
Indication
Error Name
Source of Error Signal
Control Description
F4
Outdoor environment
temp sensor error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
F6
Defrost temp sensor
error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
F7
Discharge temp sensor
error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
F5
Suction temp sensor
error
z
The plug on temperature
sensor is
not correctly connected to the
socket on mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
EF
Outdoor fan error
z
Mainboard of outdoor unit is
damaged.
z
The wire connecting the wiring
terminals of the mainboard
breaks.
If it occurs for 6 times during
one hour, it is cleared by
de-energization. If it occurs for
less than 6 times, it will be
automatically cleared.
E5
Overload protection of
compressor or driver
error
z
It is the compressor overload
switch error or the compressor
drive protection, and please
see the indicating lamp on the
main board of the outdoor unit
or the 88 nixie tube for the
protection code.
Drive failure; it will be
automatically cleared after 1
min.
Содержание SXVD200LCJ/A-K
Страница 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Страница 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Страница 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Страница 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Страница 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Страница 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Страница 115: ...AIR TO WATERHEATPUMP MAINTENANCE 109 2 Comp Low pressure Protection E3 3 Comp Discharge Temp Protection E4...
Страница 116: ...AIR TO WATERHEATPUMP MAINTENANCE 110 4 Overload proection of compressor or driver error E5 5 Outdoor fan error EF...
Страница 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Страница 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Страница 129: ...AIR TO WATERHEATPUMP MAINTENANCE 123 3 2 3 Tripping Fig 3 2 3 Flowchart of diagnosis of Tripping...
Страница 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Страница 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...
Страница 155: ...AIR TO WATERHEATPUMP MAINTENANCE 149 Exploded View of GRS CQ12Pd Na K O GRS CQ14Pd Na K O and GRS CQ16Pd Na K O...