63
Fault Displays
9,000 and 12,000 btuh units
No.
Malfuntiuon
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C Status
Possible Causes
Dual-8
Code
Display
Indicator Display (during
blinking, ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display
status and during blinking, ON
0.5ws and OFF 0.5s
Operation
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
29
Malfunction
of module
temperature
sensor circuit
P7
OFF
3S and
blink 18
times
During cooling and
drying operation,
compressor will stop
while indoor fan will
operate; During heating
operationg the complete
unit will stop
Replace outdoor control
panel AP1
30
Module high
temperature
protection
P8
OFF
3S and
blink 19
times
During cooling and
drying operation,
compressor will stop
while indoor fan will
operate; During heating
operationg the complete
unit will stop
After the complete unit
is de-energized for 20
mins, check whether
the thermal grease on
IPM Module of outdoor
control panel AP1 is
sufficient and whether
the radiator is inserted
tightly. If its no use,
please replace control
panel AP1.
31
Decrease
frequency
due to high
temperature
resistant
during heating
operation
H0
OFF
3S and
blink 10
times
All loads operate
normally, while
operation frequency for
compressor is decreased
Refer to the malfunction
analysis (overload, high
temperature resistant)
32
Static
dedusting
protection
H2
OFF
3S and
blink
twice
33
Overload
protection for
compressor
H3
OFF
3S and
blink 3
times
OFF
3S and
blink 8
times
During cooling and
drying operation,
compressor will stop
while indoor fan will
operate; During heating
operationg the complete
unit will stop
1. Wiring terminal
OVC-COMP is
loosened. In normal
state, the resistance for
this terminal should
be less than 1ohm; 2.
Refer to the malfunction
analysis (discharge
protection, overload)
34
System is
abnormal
H4
OFF
3S and
blink 4
times
OFF
3S and
blink 6
times
During cooling and
drying operation,
compressor will stop
while indoor fan will
operate; During heating
operation, the complete
unit will stop operation.
Refer to the malfunction
analysis (overload, high
temperature resistant)
All manuals and user guides at all-guides.com
Содержание RIO09HP115V1A
Страница 41: ...41 Electrical Schematics 24K Indoor Unit All manuals and user guides at all guides com a l l g u i d e s c o m ...
Страница 42: ...42 Electrical Schematics 24K Indoor Unit All manuals and user guides at all guides com ...
Страница 130: ...130 Gree Electric Appliances Inc C 2014 Cat No DFS RIO HP 2SM All manuals and user guides at all guides com ...