55
Troubleshooting Outdoor Components
The exhaust temperature sensor monitors the refrigerant discharge temperature and will send information to the
inverter control board for system operation.
The following actions can occur:
Exhaust Temperature > 208 F - Compressor will not rise above present level
Exhaust Temperature > 217 F - Compressor will run at reduced frequency
Exhaust Temperature < 194 F - Compressor off for 3 minutes minimum, the compressor will restart
Error Code F5 will be generated if the sensor is open or shorted. Please refer to the troubleshooting section for
more detailed information.
Exhaust Temperature Sensor