50
Temperature Sensor Check
Troubleshooting Outdoor Components
Temperature
Sensor
Temp
(ºC)
Temp
(ºF)
Resistance
(kΩ)
Temp
(ºC)
Temp
(ºF)
Resistance
(kΩ)
Temp
(ºC)
Temp
(ºF)
Resistance
(kΩ)
0
32.0
49.02
52
125.6
4.986
104
219.2
0.898
1
33.8
46.6
53
127.4
4.802
105
221.0
0.873
2
35.6
44.31
54
129.2
4.625
106
222.8
0.848
3
37.4
42.14
55
131.0
4.456
107
224.6
0.825
4
39.2
40.09
56
132.8
4.294
108
226.4
0.802
5
41.0
38.15
57
134.6
4.139
109
228.2
0.779
6
42.8
36.32
58
136.4
3.99
110
230.0
0.758
7
44.6
34.58
59
138.2
3.848
111
231.8
0.737
8
46.4
32.94
60
140.0
3.711
112
233.6
0.717
9
48.2
31.38
61
141.8
3.579
113
235.4
0.697
Using a glass of ice water, place the sensor into the glass with a digital thermometer. Wait a few minutes for the
reading to stabilize. Compare the readings to the sensor tables in Appendix “A”, it the reading are not comparable,
replace the sensor. When replacing the sensor, be sure to fasten the sensor securely if it is attached to a tube.
All manuals and user guides at all-guides.com
Содержание RIO09HP115V1A
Страница 41: ...41 Electrical Schematics 24K Indoor Unit All manuals and user guides at all guides com a l l g u i d e s c o m ...
Страница 42: ...42 Electrical Schematics 24K Indoor Unit All manuals and user guides at all guides com ...
Страница 130: ...130 Gree Electric Appliances Inc C 2014 Cat No DFS RIO HP 2SM All manuals and user guides at all guides com ...