Intelligent Controller
26
9 Appendix A: Selection of KWH Meter & Current
Transformer
Selection scheme 1
KWH meter model: ENTES EPR-04S-96
Parameters of ENTES EPR-04S-96
(
1
)
Measure the 3-phase voltage and electric current. Calculate the forward and
reverse active electricity quantity.
(
2
)
Working voltage: 45-265V AC/DC.
(
3
)
Measuring voltage: 10-300V AC (L-N), 10-500V AC (L-L).
(
4
)
Frequency: 45-65Hz.
(
5
)
Reference current: 0.05-5.5A.
(
6
)
Communication port: RS-485 port.
(
7
)
Communication protocol: Modbus RTU.
Current transformer: comply with the following parameters.
Parameters of Current Transformer.
(
1
)
Rated voltage & frequency: 630V, 50Hz.
(
2
)
Grade of accuracy: 1.
(
3
)
Secondary rated current: 5A.
(
4
)
Rated output load: 5VA.
(
5
)
Rated primary current of current transformer: Select according to table 1.
Please use the current transformer made by a well-known brand with high
reliability.
Table 1: Reference Table of Load and Mutual-Inductance Ratio
Rated capacity of unit (HP)
Rated capacity of unit (kW)
Mutual-inductance ratio of current
transformer
≤18
≤50.4
50/5A
20~36
56~101
100/5A
38~74
106.4~207.2
200/5A
76~88
212.8~246.4
250/5A
Selection scheme 2
KWH meter model: Wattnode Modbus WNC-3D-240-MB
Parameters of WNC-3D-240-MB:
(
1
)
Measure the 3-phase voltage and electric current. Calculate the forward and
reverse active electricity quantity.