Intelligent Controller
25
(
2
)
Before the intelligent controller is energized, all KWH meters must work
normally, and the RS485 bus of the KWH meter must be connected to the
RS485-A interface of the intelligent controller;
(
3
)
Before the intelligent controller is energized, please ensure that all units are
powered on;
(
4
)
After the intelligent controller is energized, please wait for 3 minutes before
using the software for detection.
8.5.2 Software function debugging
Intelligent Remote Eudemon is the window of man-machine interaction. The
Intelligent Remote Eudemon can realize the functions of controller configuration,
engineering information configuration, billing information export, bill output, etc. In
order to ensure the accuracy of billing information, please confirm the following
information before setting the software.
(
1
)
It must be ensured that the controller to be debugged has been energized
and connected with PC through router;
(
2
)
It must be ensured that the room information corresponds to the
engineering number of indoor unit accurately; otherwise, the bill well be
abnormal due to configuration error;
(
3
)
The corresponding relationship between the KWH meter and air
conditioning system must be accurate, otherwise, the bill will be abnormal
due to the wrong configuration of the corresponding relationship;
(
4
)
The software must be installed in the required operating system (see the
software statement for specific requirement);
(
5
)
It’s necessary to ensure that the computer is dedicated to the Intelligent
Remote Eudemon System and it’s forbidden to install anti-virus, system
management, game and other software, otherwise, the stable operation and
usage of software will be affected.
Please refer to the software manual for specific installation and usage.