background image

Unitary Ducted Split AC

18

5.3.7 Make Electrical Connections

NOTE:

The signal line of the wired controller must be separated from the power line and the 

connecting line between the indoor unit and the outdoor unit.

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor termial box cover removed.

Be sure field wiring complies with local and national fire, safety, and electrical codes, and 

voltage to system is within limits shown on unit rating plate. Contact local power company for 
correction of improper voltage. See unit rating plate for recommended circuit protection device. 

NOTE:

 Operation of unit on improper line voltage constitutes abuse and could affect unit 

reliability. See unit rating plate. Do not install system where voltage may fluctuate above or below 
permissible limits. 

NOTE:

 Use copper wire only between disconnect switch and unit. 

NOTE:

 Install branch circuit disconnect of adequate size per NEC to handle unit starting 

current. Locate disconnect within sight from and readily accessible from unit, per Section 440—14 
of NEC.

WARNING: 

 A separate air switch must be furnished for the external power supply of the unit, 

otherwise it would cause damage to the unit or bodily injury or even death.

Table 12

Model Number 

Minimum Circuit 
Ampacity-
MCA(amps)

Maximum 

Over Current 

Protective 

device-

MOCP(amps) 

Compressor 

LRA/RLA 

Capability of Air 

Switch(A)

Minimum 
Sectional Area Of 
Earth Wire(mm2 
(Outdoor/Indoor)

HW18024PNa-D

15

16.9

-/9.7

15

2.1

HW18036PNa-D

24

30.7

-/13.2

30

3.3

HW18042PNa-D 

24

35.4

-/13.2

30

3.3

HW18048PNa-D 

30

48.8

-/21.0

45

5.3

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through 

power wiring hole provided and into unit control box. 

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if 

an electrical fault should occur.

The ground may consist of electrical wire or metal conduit when installed in accordance with 

existing electrical codes.

Содержание HW18024PNa-D

Страница 1: ...you for choosing Commercial Air Conditioners please read this owner s manual carefully before operation and retain it for future reference For R410A Series Unitary Ducted Split AC Commercial Air Condi...

Страница 2: ...3 Main Page 3 4 Function Setting 3 4 1 ON OFF 3 4 2 Mode 4 4 3 Fan 4 4 4 Temperature Adjustment 4 4 5 SET Parameters Functions View and Setting 5 4 6 Enter Hold 9 4 7 Lock Function 10 4 8 Error Displ...

Страница 3: ...This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUT...

Страница 4: ...figure above or decided by the user Step 3 Conduct the wiring and see section 2 for more details Step 4 Reinstall the front panel 2 Wiring Terminals of the Wired Controller Fig 2 Wiring Terminals Diag...

Страница 5: ...lit AC 3 3 Main Page Fig 3 Main Page Fan Cancel Mode Set ON OFF Enter Hold 4 Function Setting 4 1 ON OFF The controller can be turned on off by pressing this button with the corresponding ON OFF symbo...

Страница 6: ...select the desirable fan option by pressing the Fan button Under the FAN ON option the fan will always keep running Under the FAN AUTO option the fan will be automatically shut down or started up in...

Страница 7: ...button Fig 8 Parameters Functions View and Setting 4 5 1 DEMAND After accessing to the DEMAND page it is available to select the desired parameter by pressing the button The upper value indicates the...

Страница 8: ...et press the Enter Hold button for confirmation to make this setting come effective and back to the previous interface If the setting is canceled prior to the confirmation then the related parameter w...

Страница 9: ...ig 12 After the time period is selected press the Enter Hold button to make a confirmation and go the setting status for timing the time period with the HOUR blinking and adjust it through the button...

Страница 10: ...hrough the or button Fig 15 After that press the Enter Hold button to make a confirmation and go back to the page shown in step and then repeat the steps for setting other time periods Fig 16 After th...

Страница 11: ...anceled by pressing the Cancel button Table 4 No Function Function Code Description 01 Memory ON The function is activated OFF The function is deactivated 02 Temperature Unit C Celsius scale F Fahrenh...

Страница 12: ...emperature Protection of the Outdoor Unit 7 F2 Outdoor Unit Tube Temperature Sensor Error 8 F4 Discharge Temperature Sensor Error 9 e5 Main Board Discharge Temperature Sensor Error 10 F3 Main Board Am...

Страница 13: ...value will be HI The wired controller applied to the inverter unit can set the temperature from 10 37 at the COOL mode and 5 32 at the HEAT mode However 16 30 is the real range which can be recognized...

Страница 14: ...ubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tubes through the wall seal opening wi...

Страница 15: ...s contact distributor for details and PE Certification Professional Engineer if required On rooftop applications mount on level platform or frame Place unit above a load bearing wall and isolate unit...

Страница 16: ...tubing lengths up to 36 inch may be buried without further special consideration Do not bury lines longer than 36 inch CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipmen...

Страница 17: ...ce IMPORTANT Do not apply indoor coils which are not factory approved to these units CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Serv...

Страница 18: ...cuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used if the procedure outlined below is followed IMPORTANT Always break a vacuum with dry n...

Страница 19: ...then be free of any contaminants and water vapor Final Tubing Check IMPORTANT Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment Ensure tubes are not ru...

Страница 20: ...of adequate size per NEC to handle unit starting current Locate disconnect within sight from and readily accessible from unit per Section 440 14 of NEC WARNING A separate air switch must be furnished...

Страница 21: ...VER LOAD ENVIRONMENT TEMP SENSOR DISCHARGE GAS TEMP SENSOR Fig 26 Electric Wiring of the Outdoor Unit HW18024PNa D OUTDOOR UNIT SYMBOL NAME XT1 XT2 TERMINAL BOARD AP MAIN PCB L1 L2 INDUCTOR COMP COMPR...

Страница 22: ...r at negative pressure Do not disable low pressure switch in scroll compressor applications Dome temperatures may be hot In 3 phase applications incorrect phasing will cause reverse rotation resulting...

Страница 23: ...HEAT or COOL and fan control to ON or AUTO mode as desired Operate unit for 15 minutes Check system refrigerant charge 5 3 9 Final Checks IMPORTANT Before leaving job be sure to do the following 1 Ens...

Страница 24: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Отзывы: