)XQFWLRQDQG&RQWURO
'HVFULSWLRQRI(DFK&RQWURO2SHUDWLRQ
1Temperature Parameters
Indoor preset temperature (Tpreset)
Indoor ambient temperature (Tamb.)
2 Basic functions
(The temperature in this manual is expressed by Centigrade. If Fahrenheit is used, the switchover between them is
Tf=TcX1.8+32.)
Once the compressor is energized, there should be a minimum interval of 3 minutes between two start-ups. But if the unit is
de-energized and then energized, the compressor can restart within 3 minutes.
2.1 Cooling mode
2.1.1 Cooling conditions and process
When Tamb. ≥1
, the unit starts cooling operation. In this case, the compressor and the outdoor fan operate and the indoor
fan operates at set speed.
When Tamb. ≤Tpreset-1
, the compressor and the outdoor fan stop while the indoor fan runs at set speed.
When Tpreset-1
Tamb.
1
, the unit will maintain its previous running status.
In cooling mode, the four-way valve is de-energized; temperature setting range is 16
30
; the indoor unit displays operation icon,
cooling icon and set temperature.
2.1.2 Protection Functions
Freeze protection
If the system is under freeze protection, the compressor and the outdoor fan stop operation, and the indoor fan operates at set speed. If
freeze protection is eliminated and the compressor has been out of operation for 3 minutes, the unit will resume its previous running
status.
2.1.3 Overcurrent Protection
If the system current exceeds the specified value in 3 successive seconds, the complete unit will stop operation except for the indoor fan.
After 3 minutes, if the overcurrent is eliminated, the complete unit will resume previous operation.
If overcurrent protection occurs for 6 successive times (If the compressor operates for 6 minutes continuously, the protective times will
be cleared.), the complete unit will stop operation except for the indoor unit. In this case, you are expected to turn off the unit with the
remote controller and then restart. During overcurrent protection, the indoor unit displays error code “E5”; the operation indicator lamp
blinks (OFF for 3 seconds and blinks 5 times).
T1 ˚C
Tpreset –1 ˚C
Compressor
Outdoor fan
Indoor fan
Run
Tamb.
Stop
Stop cooling
Start cooling
Original operating status
≥ 6 min.
≥ 3 min.
≥ 6 min.
Set fan speed
During
freeze
protection
Compressor
Outdoor fan
Indoor fan
min
Preset speed
Run
Stop