![Gree GWH18ND-K3NNA2A Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/gree/gwh18nd-k3nna2a/gwh18nd-k3nna2a_service-manual_2260547068.webp)
7URXEOHVKRRWLQJ
M alfunction is
eliminated.
No
Yes
“U8” is
displayed on
the unit.
Re-energize 1
minute after
de-erergization
Is“U8”
still displayed?
The zero-cross detection
circuit of the mainboard is
defined abnormal. Replace
the mainboard.
The unit returns to normal.
Conclusion: U8 is displayed due to
instant energization after de-
energization while the capacitor
discharges slowly.
80DOIXQFWLRQ